F-35-60

October 2018

1

FEATURES

Safe start with DETECT-A-FLAME

®

 flame sensing 

technology

Custom pre-purge and inter-purge timings

*

Single or three trials for ignition

System  diagnostic  LED

Flame current test points

Local or remote flame sensing

Automatic  reset

**

Alarm output (normally closed contact)

APPLICATIONS

Commercial cooking

Gas furnaces

Boilers 

Water  heaters

Other gas-fired appliances

DESCRIPTION

The 35-60 is a 24 VAC direct spark ignition (DSI) control 
designed for use in all types of gas-fired appliances. The control 
uses a microprocessor circuit to provide precise, repeatable 
timing and operating sequences. On-board diagnostics with LED 
output makes troubleshooting easy and ensures safe and 
efficient operation.

Export Information (USA)

Jurisdiction: EAR
ECCN: EAR99

Agency Certifications

Pre-purge time cannot exceed inter-purge time on CE 

Approved models.

** 

Automatic reset is not allowed for CE Approved models.

*** EMC emission requirements shall be verified after 
incorporation of the burner control system into the end use 
appliance.

SPECIFICATIONS

Recognized under the UL component program, UL 
372. Software certified to ANSI/UL 1998. UL File 
MH8817

Design Certified to ANSI Z21.20,
CAN/CSA C22.2 No. 199-M89

CE Approved to EN 298-2012

Code Compliant to:

AS 4625 - 2008
AS 4622 - 2004

Input Power

Control: 18-30 VAC 50/60Hz 
(Class 2 transformer)

Input Current

300 mA @24 VAC with gas valve 
relay energized (control only)

Gas Valve

2.0A max @ 24 VAC

Operating Temperature

-40°F to +176°F 
(-40°C to +80°C)

Storage Temperature

-40°F to +185°F 
(-40°C to +85°C)

Flame Sensitivity

0.7 

µ

A minimum

Flame Failure Response

0.8 seconds maximum

Flame Detector Self-check 
Rate

Once per second minimum

Gas Types

Natural, LP, or manufactured

Spark Rate:

Remote
Local

50/60 sparks/sec
25/30 sparks/sec

Size (LxWxH) 
with enclosure

5.69 x 3.94 x 1.87 inches
(14.45 x 10.01 x 4.75 cm)

Moisture Resistance

Conformal coated to operate non-
condensing to 95% R.H. Module 
should not be exposed to water

Ingress Protection

Not rated, protection provided by 
appliance in which it is installed

Tries for Ignition

One or three try versions available

Trial for Ignition Periods

4, 7, 10, 15 seconds available

Pre-purge and 
Inter-purge Timings

0, 15 or 30 seconds available

SERIES 35-60

24 VAC Microprocessor-Based 

Direct Spark Ignition Control

R

Содержание 35-60 Series

Страница 1: ...PECIFICATIONS Recognized under the UL component program UL 372 Software certified to ANSI UL 1998 UL File MH8817 Design Certified to ANSI Z21 20 CAN CSA C22 2 No 199 M89 CE Approved to EN 298 2012 Code Compliant to AS 4625 2008 AS 4622 2004 Input Power Control 18 30 VAC 50 60Hz Class 2 transformer Input Current 300 mA 24 VAC with gas valve relay energized control only Gas Valve 2 0A max 24 VAC Ope...

Страница 2: ...n trials before de energizing the gas valve and entering lockout The LED will indicate the fault code for ignition lockout FLAME FAILURE RE IGNITION MODE If the established flame signal is lost while the burner is operating the control will respond within 0 8 seconds by immediately energizing the H V spark for the TFI period in an attempt to relight the flame If the burner does not light within th...

Страница 3: ... Factory for longer lengths CAUTION All wiring must be performed in accordance with both local and national electrical codes CAUTION Label all wires prior to disconnection when servicing controls Wiring errors may cause improper and dangerous operation A functional checkout of a replacement control should always be performed WARNING This product uses voltages of shock hazard potential Wiring and i...

Страница 4: ...urrent Measurement Flame current is the current that passes through the flame from sensor to ground To measure flame current connect a True RMS or analog DC micro ammeter to the FC and FC terminals Readings should be 1 0 µA DC or higher If the meter reads negative or below 0 on scale meter leads are reversed Re connect leads with proper polarity Alternately a Digital Voltmeter may be used to measu...

Страница 5: ... 04 26 42 1 04 26 42 4 00 101 60 4 00 101 60 5 38 136 53 5 38 136 53 1 04 26 37 1 04 26 37 2 25 57 09 2 25 57 09 1 FS NC GND V2 TH PWR V1 1 FS NC GND V2 TH PWR V1 190 005 190 005 4 82 13 4 82 13 DIA 2 HOLES DIA 2 HOLES 25 6 35 25 6 35 2 53 64 21 2 53 64 21 1 79 45 44 1 79 45 44 1 27 32 10 1 27 32 10 1 NC GND V2 TH PWR V1 Remote Flame Sense 6 Pin Local Flame Sense 5 Pin Note All dimensions are in i...

Страница 6: ...s Tries for Ignition and Methods for Flame Sense 0 Single Try Local Sense 1 Single Try Remote Sense 5 Three Tries Local Sense 6 Three Tries Remote Sense Enclosure 0 Noryl Gray Enclosure 1 Integral Standoffs 2 HHVT w Enclosure 3 HHVT No Enclosure Product Designation 2 Standard CE Approved Model 3 Special CE Approved Model 5 Standard 6 Edge Connector 8 Aftermarket Kit 9 Special Configuration On CE A...

Страница 7: ...3 SERIES 35 60 61 63 608 SERIES 35 65 66 SERIES 35 9X The object of the declaration described above is in conformity within the relevant union harmonization legislation Gas Appliance Regulation EU 2016 426 Low Voltage Directive 2014 35 EC EMC Directive 2014 30 EC Rohs 2011 65 EU The following harmonized standards and technical specifications have been applied EN298 2012 Automatic Burner Control sy...

Отзывы: