Effective: March 2020

F-35-703

3

Wiring Diagrams - 35-703

Figure 1. Local Sense

Figure 2. Remote Sense

Internal Control Failure

If the control detects a software or hardware error, all outputs 
are turned off and the LED displays a Steady On condition. If this 
condition persists after an attempt to restart, then the control 
must be replaced.

Proper Electrode Location

Proper location of electrode assembly is important for optimum 
system performance. The electrode assembly should be located 
so that the tips are inside the flame envelope and about 1/2-inch 
(1.2 cm) above the base of the flame as shown:

Notes:

Ceramic insulators must not be in or close to the flame.

Electrode assemblies must not be adjusted or 
disassembled. Electrodes are NOT field adjustable.

Electrodes should have a gap spacing of 0.125± 0.031 
in (3.12± 0.81 mm), unless otherwise specified by the 
appliance manufacturer. If spacing is not correct, the 
assembly must be replaced.

Exceeding temperature limits can cause nuisance 
lockouts and premature electrode failure.

Electrodes must be located where they are not exposed 
during normal operation.

TROUBLESHOOTING

Note:

During a fault condition, the LED will flash on for 
1/4 second and off for 1/4 second as needed to 
indicate the fault code. The code will repeat every 
3 seconds. Removing power from the control will 
clear the fault code.

L2

SPARK

BURNER

BURNER GROUND

H.V. OUT

120V THERMOSTAT

OR CONTROL DEVICE

L1

PV

MV

L2
L2

V2

L1

B. GND

PV1

MV1

L1

L2

120V THERMOSTAT

OR CONTROL DEVICE

PV

MV

L2

L2

V2

L1

B. GND

S1

H.V. OUT

SPARK

BURNER

BURNER GROUND

PV1

MV1

Troubleshooting Guide

Symptom

Recommended Actions

1. Control does not start

A. Miswired
B. No 120VAC at L1
C. Fuse or circuit breaker fault
D. Faulty control, check LED 

for fault codes

2. Thermostat on - no spark

A. Miswired
B. Faulty thermostat, no 

voltage at terminal L1

C. Faulty control, check LED 

for fault codes

3. Valve on - no spark during 
TFI

A. Shorted electrode - 

establish 1/8-inch gap

B. Check high voltage cable
C. Miswired

4. Spark on - valve off

A. Valve coil open
B. Valve wire disconnected
C. Faulty control, check 

voltage at gas valve 
terminals PV1 or MV1 and 
V2

5. Flame okay during TFI - no 

flame sense after TFI

A. Check electrode position
B. Check high voltage wire
C. Poor ground at burner
D. Poor flame, check flame 

current

Fault Conditions

LED Indication

Fault Mode

Steady On

Internal Control Failure

2 Flashes

Pilot Flame without call for heat

3 Flashes

Ignition Lockout

Содержание Series 35-703

Страница 1: ... to ANSI Z21 20 CAN CSA C22 2 No 199 M89 Input Power 102 to 138 VAC 50 60 Hz Input Current 350 mA 120 VAC with main and pilot gas valve relays energized control only Main Gas Valve 1 5A max 120 VAC Pilot Gas Valve 1 5A max 120 VAC Operating Temperature 40 F to 160 F 40 C to 71 C Storage Temperature 40 F to 185 F 40 C to 85 C Flame Sensitivity 1 0 µA minimum Flame Failure Response 0 8 seconds maxim...

Страница 2: ...and entering lockout If the pilot burner relights normal operation resumes FLAME FAILURE RECYCLE MODE With the Recycle After Loss of Flame option upon loss of flame the pilot and main gas valves are de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the pilot burner relights normal o...

Страница 3: ...HOOTING Note During a fault condition the LED will flash on for 1 4 second and off for 1 4 second as needed to indicate the fault code The code will repeat every 3 seconds Removing power from the control will clear the fault code L2 SPARK BURNER BURNER GROUND H V OUT 120V THERMOSTAT OR CONTROL DEVICE L1 PV MV L2 L2 V2 L1 B GND PV1 MV1 L1 L2 120V THERMOSTAT OR CONTROL DEVICE PV MV L2 L2 V2 L1 B GND...

Страница 4: ...the meter A jumper wire must be installed across the terminals of the meter Once the flame is established and sparking terminates remove the jumper wire to measure flame current The flame sense current must be 0 7 uA minimum for proper operation REMOTE FLAME SENSE With power off remove sense wire from S1 terminal and install a DC microamp meter between the S1 terminal and sense wire Establish flam...

Страница 5: ...rge 0 None Single Try Only 1 15 Seconds 2 30 Seconds 3 45 seconds 4 4 minutes Pre Purge 0 None 1 15 Seconds 2 30 Seconds 3 45 Seconds 4 4 minutes Tries for Ignition Flame Sense Method and Reset Method 0 1 try local sense 1 1 try remote sense 2 1 try local sense 3 1 try remote sense 5 3 try local sense 6 3 try remote sense 7 3 try local sense 8 3 try remote sense Configuration and Wiring Options 5 ...

Отзывы: