Fenwal Controls Series 35-703 Скачать руководство пользователя страница 2

Effective: March 2020

2

F-35-703

SEQUENCE OF OPERATION / FLAME 

RECOVERY / SAFETY LOCKOUT

Start Up - Heat Mode

When a call for heat is received from the thermostat supplying 
120VAC to L1, the control will reset, perform a self-check 
routine, flash the diagnostic LED and begin a pre-purge delay. 
Following the pre-purge period, the pilot gas valve is energized 
and sparking commences for the Trial For Ignition (TFI) period.

When flame is detected during the TFI, the sparking process is 
terminated and the main gas valve is energized. The thermostat 
and pilot burner flame are constantly monitored to assure proper 
system operation. When the thermostat is satisfied and the 
demand for heat ends, the pilot and main valves are immediately 
de-energized.

Failure to Light - Lockout

SINGLE TRIAL MODEL
Should the pilot burner fail to light, or the pilot flame is not 
detected during the TFI period, the pilot gas valve will de-
energize and the control will go into lockout. The LED will 
indicate the fault code for ignition lockout.

MULTI TRIAL MODEL
Should the pilot burner fail to light or the pilot flame is not 
detected during the TFI period, the pilot gas valve will de-
energize. The control will then go through an inter-purge delay 
before an additional ignition attempt. The control attempts two 
additional ignition trials before de-energizing the pilot gas valve 
and entering lockout. The LED will indicate the fault code for 
ignition lockout.

FLAME FAILURE - RE-IGNITION MODE
If the established pilot flame signal is lost while the burner is 
operating, the control will respond within 0.8 seconds by de-
energizing the main gas valve and energizing the spark for the 
TFI period in an attempt to relight the flame. If the burner does 
not light within the TFI, the pilot gas valve will immediately de-
energize and single try models will enter lockout. On multi-try 
models, a new TFI sequence will begin after an inter-purge 
delay. Multi-try models perform two additional attempts to light 
the burner before de-energizing the gas valves and entering 
lockout. If the pilot burner relights, normal operation resumes.

FLAME FAILURE-RECYCLE MODE

With the “Recycle After Loss of Flame" option, upon loss of 
flame, the pilot and main gas valves are de-energized and the 
control proceeds to inter-purge before attempting to relight the 
flame. Multi-try models permit three tries for ignition including 
inter-purges. If the pilot burner relights, normal operation 
resumes. If the pilot burner does not relight, the control will 
enter lockout.

Lockout Recovery

Recovery from lockout requires a manual reset by either 
resetting the thermostat, or removing 120 VAC for a period of 5 
seconds. On models with automatic reset, if the thermostat is 
still calling for heat after one hour, then the control will 
automatically reset and attempt to ignite the burner.

MOUNTING AND WIRING

The Series 35-703 control is not position sensitive and can be 
mounted vertically or horizontally. The control may be mounted 
on any surface and fastened with #6 sheet metal screws. Secure 
the control in an area that will experience a minimum of 
vibration and remain below the maximum ambient temperature 
of 160°F (71°C).

All connections should be made with UL Approved, 105°C rated, 
18 gauge, stranded, .054” thick insulated wire. Refer to the 
appropriate wiring diagram when connecting the 35-703 to 
other components in the system.

CAUTION

All wiring must be performed in accordance with
both local and national electrical codes.

CAUTION

Label  all  wires  prior  to  disconnection  when
servicing  controls.  Wiring  errors  may  cause
improper and dangerous operation. A functional
checkout of a replacement control should always
be performed.

WARNING

This  product  uses  voltages  of  shock  hazard
potential.  Wiring  and  initial  operation  must  be
performed by a qualified service technician.

WARNING

Operation  outside  specifications  could  result  in
failure of the Fenwal Controls product and other
equipment with potential for injury to people and
property.

Terminal Designations

Terminal

Description

Quick 
Connect 
(inch)

PV1

Pilot Valve Power

3/16” 

L2

120 VAC (Neutral)

3/16”

L2

120 VAC (Neutral)

3/16”

V2

Valve Neutral

3/16”

L1

120 VAC Input (Hot)

1/4”

MV1

Main Valve Power

1/4”

B. GND

Burner Ground

3/16”

S1

Remote Flame 
Sensor

1/4”

Содержание Series 35-703

Страница 1: ... to ANSI Z21 20 CAN CSA C22 2 No 199 M89 Input Power 102 to 138 VAC 50 60 Hz Input Current 350 mA 120 VAC with main and pilot gas valve relays energized control only Main Gas Valve 1 5A max 120 VAC Pilot Gas Valve 1 5A max 120 VAC Operating Temperature 40 F to 160 F 40 C to 71 C Storage Temperature 40 F to 185 F 40 C to 85 C Flame Sensitivity 1 0 µA minimum Flame Failure Response 0 8 seconds maxim...

Страница 2: ...and entering lockout If the pilot burner relights normal operation resumes FLAME FAILURE RECYCLE MODE With the Recycle After Loss of Flame option upon loss of flame the pilot and main gas valves are de energized and the control proceeds to inter purge before attempting to relight the flame Multi try models permit three tries for ignition including inter purges If the pilot burner relights normal o...

Страница 3: ...HOOTING Note During a fault condition the LED will flash on for 1 4 second and off for 1 4 second as needed to indicate the fault code The code will repeat every 3 seconds Removing power from the control will clear the fault code L2 SPARK BURNER BURNER GROUND H V OUT 120V THERMOSTAT OR CONTROL DEVICE L1 PV MV L2 L2 V2 L1 B GND PV1 MV1 L1 L2 120V THERMOSTAT OR CONTROL DEVICE PV MV L2 L2 V2 L1 B GND...

Страница 4: ...the meter A jumper wire must be installed across the terminals of the meter Once the flame is established and sparking terminates remove the jumper wire to measure flame current The flame sense current must be 0 7 uA minimum for proper operation REMOTE FLAME SENSE With power off remove sense wire from S1 terminal and install a DC microamp meter between the S1 terminal and sense wire Establish flam...

Страница 5: ...rge 0 None Single Try Only 1 15 Seconds 2 30 Seconds 3 45 seconds 4 4 minutes Pre Purge 0 None 1 15 Seconds 2 30 Seconds 3 45 Seconds 4 4 minutes Tries for Ignition Flame Sense Method and Reset Method 0 1 try local sense 1 1 try remote sense 2 1 try local sense 3 1 try remote sense 5 3 try local sense 6 3 try remote sense 7 3 try local sense 8 3 try remote sense Configuration and Wiring Options 5 ...