SMART SN TRANSMITTER – OPERATING INSTRUCTIONS 

MU2B-0328GE51 R0207A 

7

CODE

NOT

VALID

Put code

0000

OK

-

+

0

Put code

0000

-

+

8

Put code

0000

-

+

9

Put code

0009

-

+

0

Put code

0009

-

+

1

Put code

0009

-

+

4

Put code

0009

-

+

5

ESCAPE

OK

OK

LEFT

LEFT

LEFT

OK

OK

OK

OK

Put code

0000

-

+

1

OK

LEFT

LEFT

LEFT

LEFT

LEFT

 

Fig. 13. Entering the ENTRY CODE 

 

PARAMETRIZATION LEVEL 

Once you have successfully entered the ENTRY CODE and 
thus gained access to the PARAMETRIZATION LEVEL, you 
can edit values and reconfigure the device. 

NOTE:

 

The currently set option (e.g. "yes," "no," 
"4…20 mA", etc.) is always marked in the display 
screen with a small dot to the left (see Fig. 5). 

 

Function

N.O.

OK

N.C.

ESCAPE

Function

N.O.

N.C.

ESCAPE

OK

DOT

 

Fig. 14. Dot indicating present setting 

 

START-PT. 

In this screen, you can select the start-point. This is defined 
as the pressure at which you want the device to begin 
providing an analog output signal. 
The default setting is "0". 
 

ERROR MESSAGE: "VALUE OUT OF RANGE" 

If you have entered a start-point outside of the device's 
specified pressure measurement range or which is for any 
other reason not rational, this error message will appear, 
whereupon you should then enter a correct value. 
 

END-PT. 

In this screen, you can select the end point. This is defined as 
the pressure at which you want the device to stop providing 
an analog output signal. 
The default setting is 100% of full-scale. 
 

ERROR MESSAGE: "VALUE OUT OF RANGE" 

If you have entered an end-point outside of the device's 
specified pressure measurement range or which is for any 
other reason not rational, this error message will appear, 
whereupon you should then enter a correct value. 
 

OUTPUT 

MODE 

Here, you can set the device's mode. Four different modes 
are possible: 

  0…10V: the voltage range is set to 0…10 V; 

  0…20mA: the current range is set to 0…20 mA; 

  2…10V: the voltage range is set to 2…10 V; 

  4…20mA: the current range is set to 4…20 mA (default). 

NOTE:

 

The only mode supported by the SN 2-Wire Trans-
mitter is "4…20 mA". However, it can be inverted 
to "20…4 mA" (see section "Function" below). 

 

FUNCTION 

Here, you can invert the device's function (see also Fig. 15): 

  Non-invert.: the mode (current range or voltage range, as 

the case may be) is set to 0/4…20 mA or 0/2…10 V (as 
the case may be) (default); 

  Inverted: the mode (current range or voltage range, as the 

case may be) is set to 20…0/4 mA or 10…0/2 V (as the 
case may be). 

The default setting is "non-invert." 
 

U

/I

MAX MAX

U

/I

MAX MAX

U /I

MIN MIN

U /I

MIN MIN

output U/I

output U/I

NORMAL OPERATION

INVERTED OPERATION

pressure

pressure

pressure

start

pressure

start

pressure

end

pressure

end

 

Fig. 15. SN Transmitter output (normal/inverted) 

 

AUTO ZERO 

The purpose of the auto zero function is to allow the user to 
adjust the device to local ambient atmospheric pressure and 
to compensate for drift. To use this function properly, the 
device must be mounted in the application and the pressure 
sensor exposed to local ambient atmospheric pressure (i.e. 
0 bar relative pressure). 

  Yes: The device takes the current local ambient 

atmospheric pressure as its zero. 

  No: The device setting remains unchanged. 

The default setting is "No". 
 

SET ZERO 

The difference between the pressure value you enter in this 
screen and the pressure which the device is currently 
measuring will be taken as the offset. This offset can be reset 
to zero using the reset zero option (see section "Reset Zero" 
below). 
The default setting is the pressure which the device is 
currently measuring (meaning that the offset is then zero). 
 

ERROR MESSAGE: "VALUE OUT OF RANGE" 

If you have set a zero outside the permissible range (±25% 
full-scale), this error message will appear, whereupon you 
should then enter a correct value. 
 

RESET ZERO 

Here, you can reset the zero: 

  Yes: The pressure offset will be set to zero. 

  No: The device setting remains unchanged. 

The default setting is "No". 
 

ATT. FILTER 

Here, you can attenuate (dampen) the outputted portion of 
the peak. Possible values range from 0 to 99%. The default 
setting is "10" percent. 
The formula for calculating the attenuation is as follows: 

1

100

)

100

1

(

+

=

n

n

n

y

n

attenuatio

x

n

attenuatio

y

 

Содержание Smart DCM

Страница 1: ...0 95 r h non condensing Temperature of medium 30 100 C 16 bar models 40 100 C 16 bar models Storage temperature Versions non HMI 40 80 C 16 bar 40 100 C 16 bar Versions HMI 30 80 C Climate class Indo...

Страница 2: ...here the device will check the plausibility of your values and if necessary redirect you back to the PARAMETRIZATION LEVEL and The CONFIRMATION LEVEL where you can review your edited values before per...

Страница 3: ...to local ambient atmospheric pressure and to compensate for drift To use this function properly the device must be mounted in the application and the pressure sensor exposed to local ambient atmosphe...

Страница 4: ...e simulation mode is started No The device remains in its normal operating mode The default setting is No WARNING After you have completed testing in the simulation mode do not forget to return to thi...

Страница 5: ...250 mA the load is disconnected and the WARN output is set to 0 5 V in a loop Table 2 DCM Switch functions and definitions definition function equa tion active inactive max monitor N O 1 closed open m...

Страница 6: ...ausibility of your values and if necessary redirect you back to the PARAMETRIZATION LEVEL and The CONFIRMATION LEVEL where you can review your edited values before permanently storing them START SCREE...

Страница 7: ...2 Wire Trans mitter is 4 20 mA However it can be inverted to 20 4 mA see section Function below FUNCTION Here you can invert the device s function see also Fig 15 Non invert the mode current range or...

Страница 8: ...e contrast is increased to its maximum value The default setting is Mean EXTRAS SIMUL SIMULATION MODE The simulation mode allows the user to test the device within the application without actually app...

Страница 9: ...passive 0 mA 3 Wire 0 10 V passive 0 V The output limits of the device s outputs at overpressure and underpressure are as follows Table 4 SN Transmitter output limits at over underpressure device out...

Страница 10: ...er The Y axis displays the generated output in the range according to the output definition see Fig 15 on page 7 and Table 5 on page 9 DCM SWITCH Measuring pressures is the safety function of the dire...

Страница 11: ...output pin 2 If due to miswiring or electronic failure the signal output cannot reach the desired high failure state it will auto matically go to the low failure state Table 6 SN Transmitter error rep...

Страница 12: ...ontact FEMA 6 Device memory check failure R U Hardware reset as described above Contact FEMA 7 Device program flow failure R U If unrecoverable Contact FEMA 8 Environment too hot or electronics failur...

Страница 13: ...sionen mit HMI 20 70 C Rel Luftfeuchtigkeit 0 95 nicht kondensierend Mediumtemperatur 30 100 C 16 bar Modelle 40 100 C 16 bar Modelle Lagertemperatur Versionen ohne HMI 40 80 C 16 bar 40 100 C 16 bar...

Страница 14: ...ener Einstellwerte PR FBEREICH berpr fung auf korrekte Eingabe und ggfls Zur ckstufung in den PARAMETRISIERUNGS BEREICH und BEST TIGUNGSBEREICH Nochmalige Best tigung der Einstellwerte bevor sie dauer...

Страница 15: ...st N O AUTO ZERO Die auto zero Funktion erm glicht es dem Anwender das Ger t entsprechend den lokalen atmosph rischen Druck verh ltnissen einzustellen sowie die Drift auszugleichen Um diese Funktion r...

Страница 16: ...das Ger t wieder in Sicherheitsanwendungen eingesetzt werden Yes Der Simulationsmodus wird aufgerufen No Das Ger t bleibt in seiner normalen Betriebsart Die Werkseinstellung ist No VORSICHT Nach Absc...

Страница 17: ...annungsversorgung gestellt Falls der Strom immer noch h her als 250 mA ist wird die Last getrennt und der WARN Ausgang auf 0 5 V in eine Schleife gestellt Tabelle 2 DCM Funktionen und Definitionen Def...

Страница 18: ...ung auf korrekte Eingabe und ggfls Zur ckstufung in den PARAMETRISIERUNGS BEREICH und BEST TIGUNGSBEREICH Nochmalige Best tigung der Einstellwerte bevor sie dauerhaft gespeichert werden STARTANZEIGE B...

Страница 19: ...tiert werden siehe Abschnitt Function Funktion unten FUNCTION FUNKTION Hier k nnen Sie die Ger tefunktion invertieren siehe auch Abb 15 Non invert der Modus Strom bzw Spannungsbereich wird auf 0 4 20...

Страница 20: ...Simulationsmodus erm glicht es dem Anwender die reibungslose Funktion des Ger ts zu pr fen ohne das System unter Druck zu setzen Nach Aufrufen des Simulationsmodus sind die Diagnostik funktionen nicht...

Страница 21: ...V passiv 0 V Die Ausgangsgrenzen der Ger teausg nge bei ber und Unterdruck sind wie folgt Tabelle 4 SN Transmitter Ausgangsgrenzen bei ber und Unterdruck Ger t Ausgangs signal bereich min Ausgangs gre...

Страница 22: ...te besteht darin Dr cke zu messen Je nach dem wie das Ger t eingestellt ist l t es sich mit einer Genauigkeit von 5 als Max Min oder Window W chter Schalter ausgang und WARN Ausgang betreiben Wenn di...

Страница 23: ...er automatisch in den niedrigen Fehlerzustand fallen Tabelle 6 SN Transmitter Fehlermeldung Fehlermeldung Modell Aus gangs signal Bereich prim rer hoher Fehler zustand sekund rer niedriger Fehler zust...

Страница 24: ...ntaktieren 6 Speicherpr fung fehlgeschlagen B NB Wie oben beschrieben Hardware Reset durchf hren FEMA kontaktieren 7 Programmlauffehler B NB Falls nichtbehebbar FEMA kontaktieren 8 Umgebung zu hei ode...

Отзывы: