FEMA ELECTRÓNICA . Series M . M60-C1
8
Decimal point
Press ‘SQ’ (
<
) for 1 second to access the ‘
configuration menu’.
For a description on how to operate inside the menus see section
1.17
. For a full vision of the ‘
configuration menu’ structure see
section
1.20
.
To configure the initial set up of the instrument, select the function
mode, the decimal point position, scale the reading and configure
the mode selected and the sensor.
Enter the ‘
Function mode
’ (‘
Func
’) menu and select the desired func
-
tion, from the 5 counting modes, 2 ratemeter modes and the period
-
meter mode available.
• ‘
Counter
’ (‘
cn. 1
’) - normal counter mode. Impulses input at chan-
nel A. Channel B disabled.
• ‘
Counter quadrature
’ (‘
cnq.2
’) - counter mode for quadrature sig
-
nals. Impulses input at channel A and B, in quadrature.
• ‘
C inhibition
’ (‘
cnI.3
’) - counter mode with inhibition con
-
trol. Impulses input at channel A. Inhibition control on channel B.
• ‘
C control add
/
substract
’ (‘
cnc.4
’) - counter mode with
control for add / substract. Impulses input at channel A. Control for
the add or substract function on channel B.
• ‘
Counter differential
’ (‘
cnd.5
’) - counter mode with differential
function. Impulses received at channel A add. Impulses received at
channel B substract.
• ‘
Ratemeter
’ (‘
rt.6
’) - ratemeter mode. Impulses input at channel
A. Channel B disabled.
• ‘
Ratemeter quadrature
’ (‘
rtq.7
’) - ratemeter mode for quadrature
signals. Impulses input at channel A and B, in quadrature.
• ‘
Periodmeter
’ (‘
Prd.8
’) - periodmeter mode. Impulses input at
channel A. Channel B disabled.
Access the ‘
Decimal point
’ (‘
dP
’) menu to select the decimal point
position. Move the decimal point by pressing the ‘LE’ (
3
) key.
Configure the function mode selected (‘
cnF.2
’ to ‘
cnF.8
’). See sec-
tions
1.19.2 to 1.19.9.
Configure the sensor at the ‘
SnSr
’ menu. See section
1.19.10.
Function
mode
Counter
Counter quadrature
C inhibition
C control add / substract
Counter differential
Ratemeter
Ratemeter quadrature
Periodmeter
Configuration menu for mode ‘
counter
’ (‘
cn.1
’). total impulses re-
ceived are multiplied by the value of the ‘multiplier’ (‘
MuLt
’) register
and divided by the ‘divider’ (‘
dIV
’) register. Result is refreshed on the
display.
• assign the value for parameter ‘
Multiplier
’ (‘
MuLt
’) from 1 to
999999.
• assign the value for parameter ‘
Divider
’ (‘
dIV
’) from 1 to 999999.
• assign the value for ‘
Preset
’ (‘
PrSt
’) from -199999 to 999999. Reset
activation loads on display the preset value.
• select the counting mode (‘
ModE
’) to ‘
uP
’ for upwards counting
(impulses received add) or ‘
doWn
’ for downwards counting (impuls
-
es received substract).
• to activate the ‘
FAST
’ mode (‘
FASt
’) select ‘
on
’. See section
1.16
for
more information on the ‘
FAST
’ mode.
1.19.2
Configuration for ‘cn.1’
The next menu accesses the configuration parameters for the ‘
function mode
’ (‘
Func
’)
selected. Configuration parameters are slightly different for each ‘
function mode
’. In
the next entries, all 7 possible configuration menus are explained, ‘
cnF.1
’ to ‘
cnF.7
’, one
for each ‘
function mode
’.
Multiplier
1 to 999999
Divider
1 to 999999
Configuration
counter
Multiplier
Divider
Preset
Preset value
-199999 to 999999
Mode
Up
Down
‘FAST’ mode
1.19
Configuration menu
1.19.1
Initial set-up