1.19 Configuration menu (cont.)

The ‘

Alarms

’ (‘

ALr

’) menu configures the independent activation of 

up to 3 relay outputs, installed with the R1 optional modules 

(see 

section 2.1). For outputs up to 4 and 6 relays, see special modules r2, 

R4 and R6 at section 

2.6

. The alarm states are indicated in the front 

display with leds marked as ‘1’, ‘2’ and ‘3’.
To configure an alarm, enter into the alarm menu (‘

ALr1

’, ‘

ALr2

’ or 

ALr3

’) and configure the following parameters :

• select ‘

Active

’ (‘

Act

’) to ‘

on

• at ‘

Alarm type

’ (‘

TypE

’) select the alarm to act as a maximum type 

alarm (‘

MAX

’) or a minimum type alarm (‘

MIn

’). the maximum type 

alarm (or minimum type alarm) activates when the display value is 
higher (or lower) than the setpoint value.
• at ‘

Setpoint

’ (‘

SEt

’) enter the value for the alarm activation point

. 

This parameter is eligible for configuration through the ‘

Fast access’ 

menu (see section 1.19.12).

• configure the hysteresis value at ‘

Hysteresis

’ (‘

hySt

’). the hyster-

esis applies to the deactivation process of the alarm. The alarm de

-

activates when the reading has passed the setpoint value plus the 
hysteresis value. Hysteresis helps to avoid repetitive switching of the 
alarm relays, due to fluctuating input signals around the setpoint.
• at ‘

Activation delay

’ (‘

dEL.0

’) configure the delay to apply before 

alarm activation. The activation delay starts counting when the set

-

point value is passed. Value from 0.0 to 99.9 seconds.
•  at  ‘

Deactivation  delay

’  (‘

dEL.1

’)  configure  the  delay  to  apply 

before alarm deactivation. The deactivation delay starts counting 
when the setpoint value plus the hysteresis value, is passed. Value 
from 0.0 to 99.9 seconds.
• to work with ‘windowed alarms’ (see graphical example below) 
activate ‘

Setpoint

 

2

’ (‘

SEt2

’) to ‘

on

’ and then configure the desired 

second setpoint value. Second setpoint must always be higher in 
value than the first setpoint.
• the ‘

Relay inverted

’ (‘

r.Inv

’) parameter inverts the normal relay 

connections. When set to ‘

on

’ the relay will be active when alarm is 

inactive. For security applications where an inactive relay controls 
the shutdown of the system.
•  the  ‘

Locked alarm

’  (‘

A.Lck

’)  parameter  disables  the  automatic 

deactivation of the alarm. Alarm deactivation must be performed 
manually, by pressing the ‘LE’ front button 

(see section 1.19.15)

• the ‘

On alarm

’ (‘

on.AL

’) parameter assigns a predefined behav

-

iour  when  alarm  is  activated.  Select  ‘

cont

’  to  continue  counting. 

Select  ‘

to_0

’  to  load  ‘0’  on  displays.  Select  ‘

to_p

’ to load preset 

value on display. Parameter ‘

dEL.1

’ is set to 1 second when ‘

to_0

’ 

or ‘

to_p

’ are selected.

1.19.11 Alarms

On alarm

Continue

To zero

To preset

Alarm 1

Setpoint

Hysteresis

Setpoint 2

Active

Alarm type

Alarms

Activation delay

Deactivation delay

Relay inverted

Locked alarm

reading

time

setpoint

hysteresis

Alarm as maximum,  
no hysteresis, no delays

on

off

time

activation 
delay

on

off

deactivation 
delay

time

Alarm as maximum,  
with hysteresis and delays

on

off

time

Alarm as minimum,  
no hysteresis, no delays

reading

time

Setpoint 2

Setpoint 1

Alarm as minimum, 
with double setpoint, 
no hysteresis, no delays

on

off

time

Содержание M60-C1

Страница 1: ...N Reading with 6 digit display Fast access to alarm setpoints special modes for fast counting and for slow ratemeter applications on power up function configurable reading brightness Universal AC and...

Страница 2: ...tion 1 19 10 Function Trigger Sense helps to detect the correct trigger level see section 1 13 Multiple display filters memory for maximum and minimum reading password protection 5 brightness levels I...

Страница 3: ...ith scalable read ing The quadrature ratemeter mode has 2 inpur channels available for detection of sense of turn when working with quadrature signals Scalable reading with configurable multiplier fac...

Страница 4: ...e SnSr menu entry will configure the sen sor parameters to the values indicated in the table The table also indicates the typical con nections for each type of sensor Param eters can be manually modif...

Страница 5: ...ee section 3 2 Output and control options relays analog outputs serial communi cations see section 2 Mechanical mounting panel connections plug in screw terminal housing material ABS polycarbonate V0...

Страница 6: ...or falling edge after the instrument restart power up or configuration change is used for internal initialization and will not be counted as impulse 1 14 Function cycle counter 1 15 SLOW mode The tri...

Страница 7: ...TER key It selects and accesses the menu option currently dis played At menus with numerical value entries it validates the num ber displayed Key UP 5 the UP 5 key gives access to the fast access menu...

Страница 8: ...es input at channel A Channel B disabled Access the Decimal point dP menu to select the decimal point position Move the decimal point by pressing the LE 3 key Configure the function mode selected cnF...

Страница 9: ...nnel B is at logical state 1 Select on_0 to inhibit the counting when channel B is at logical state 0 1 19 4 Configuration for cnI 3 Configuration menu for mode counter control add substract cnc 4 Tot...

Страница 10: ...the SLoW mode and assign the Maximum waiting time between 1 and 1000 seconds See section 1 15 for more information on the SLoW mode in case of unstable signals activate the average filter AVr func tio...

Страница 11: ...ture cycle Select 1 4 for 4 impulses per quadra ture cycle for slow frequencies activate the SLoW mode and assign the Maximum waiting time between 1 and 1000 seconds See section 1 15 for more informat...

Страница 12: ...channel Act r configures the activa tion of the reset channel by rising edge on_h or by falling edge on_0 Excitation voltage V EXc configures the value of the excita tion voltage at 5Vdc 9Vdc 15Vdc an...

Страница 13: ...ivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint value plus the hysteresis value is passed Value from 0 0 to 99 9 sec...

Страница 14: ...instrument gives access to a list of functions configurable by the operator See section 1 17 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu allows to sele...

Страница 15: ...1 19 20 Firmware version 1 19 21 Brightness The Counter overrange c orG and Counter underrange c urG parameters configure the behavior of the instrument when reading is higher than 9999 overrange or...

Страница 16: ...unter inhibition Multiplier Divider Preset Preset value 199999 to 999999 Mode Up Down Inhibition Inhibits if chan nel B is high Inhibits if chan nel B is 0Vdc Multiplier 1 to 999999 Divider 1 to 99999...

Страница 17: ...utomatic conf Edges 1 imp per cycle 2 imp per cycle 4 imp per cycle Average filter SLOW mode Max waiting time 1 to 1000 Sec Filter strength by rising edge by falling edge Activation for channel A Trig...

Страница 18: ...s Setpoint2 Active Alarm type Alarms Activation delay Deactivation delay Relay inverted Locked alarm Tools Key UP fast access Memory of maximum Memory of minimum Setpoint1 Setpoint2 Setpoint3 Memory o...

Страница 19: ...Vdc Activation for channel A on rising edge on_h Excitation voltage 5Vdc Antirrebound filter 0mSeconds Tools Fast access Key UP off On Power Up Delay 0seconds Key LE reset function Memory of maximum 1...

Страница 20: ...ation for the position of each module You may need to access the inside of the instrument to add or re place internal modules Use a flat screwdriver to unlock the upper clips marked with A Then unlock...

Страница 21: ...z Criteria A 61000 4 11 0 1 cycle Criteria A 40 10 cycles Criteria A 70 25 cycles Criteria B 0 250 cycles Criteria B Barber del Vall s April 2013 Daniel Junc Quality Manager 1 25 Warranty 1 26 CE decl...

Страница 22: ...tandalone for delayed installation as they do not require soldering or special configuration 2 Output and control modules 2 1 Module R1 2 2 Module AO Terminal A Common Terminal B NO Normally Open Term...

Страница 23: ...module for M Series of panel meters ASCII protocol with Master Slave archi tecture Addressable with up to 31 modules Frames codified in rep resentable ASCII characters codes 32 to 255 directly visibl...

Страница 24: ...patible with standard R1 modules The R2 R4 and R6 modules can be ordered pre installed into a M Series panel meter or standalone for delayed installation as they do not require soldering or special co...

Страница 25: ...FEMA ELECTR NICA Series M M60 C1 25 T h i s p a g e b l a n k...

Страница 26: ...ve the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad Front...

Страница 27: ...r96x48mm instruments Front IP65 protector for M Se ries and K Series panel meters Benchtop housing for M Series and K Series panel meters Handle with three selectable positions Power connector with ma...

Страница 28: ...info fema es www fema es Panel meters Standard 96x48mm Panel meters Compact 72x36mm Panel meters Miniature 48x24mm Large format meters Signal converters Isolators Bar meters Low cost Customized instr...

Отзывы: