background image

User’s Manual LAP-35

FEMA ELECTRÓNICA - Page 3

Front and rear view

Offset

mA signal loop

(polarity autodetected)

Span

SELECTOR S3

SELECTOR S2

H

G

F

E

D

C

B

A

B

A

SELECTOR S1

F E D C B A

Internal jumpers

Decimal point selection

 1.XXX  S1-C

 1X.XX  S1-A

 1XX.X  S1-B

Select the jumpers for the desired decimal  point position.

Signal range selection

 4/20mA  S2-B

 10/50mA  S2-A

 

1/5mA 

(Abrir S2-A y S2-B)

Select the jumpers for the desired input signal range.

Slope reading selection

 

Direct 

S2-D, S2-E, S3-E, S3-F

 

Inverse 

S2-C, S2-F

Select the jumpers for the desired reading slope.

As standard, the direct slope is used (reading increases 

when  signal  increases). The  inverse  slope  configures  the 

reading to decrease when reading increases.

Span and offset range selection

  Low range 

S3-A, S3-G 

Span from 385 to 785

   

 

Offset from -160 to 100

  Middle range  S3-B, S3-G 

Span from 750 to 1500

   

 

Offset from -260 to 200

  High range 

S3-G 

Span from 1090 to 1999

   

 

Offset from -380 to 560

Select the jumpers for the desired span and offset range.

Manufacturer  FEMA ELECTRÓNICA, S.A.

Pol. Ind. Santiga - Altimira 14, E08210 - Barberà del Vallès  

-BARCELONA, ESPAÑA-SPAIN, www.fema.es

Products : LAP-35. The manufacturer declares that the 

instruments indicated comply with the directives and rules 

indicated below. Directive of electromagnetic compatibility 

2004/108/CEE. Directive of low voltage 73/23/CEE. Safety 

rules 61010-1

Equipment “Fixed”, Pollution degree 1, CAT-

I. 61000-6-4 Generic rules of emission. 61000-6-2 Generic 

rules of immunity

Barberà del Vallès October 2002

Daniel Juncà - Quality Manager

CE Declaration of conformity

Readjustment procedure

1- Take all jumpers out

2- Select appropriate signal range jumpers

3- Select appropriate slope reading jumpers

4- Select appropriate span and offset jumpers. 

Calculate span 

and offset values according to the example below. Example 

given for an adjustment of 4/20mA = 0/1000

  IL (input signal low) = 4mA    RL (reading low)=0

  IH (input signal high)= 20mA  RH (reading high)=1000

  G = ( RH - RL ) / ( IH - IL )

  Offset = RL - ( IL x G )

  Span = RH

If value obtained for G is higher than 125 or values for span 

and offset do not fit into any of the three available ranges, 

then the adjustment is out of the capabilities of the instrument.

5- Select appropriate decimal point jumpers

6- Connect a signal generator to the input terminals 

7- Generate the input signal low (

4mA)

Operate Offset potentiometer until the value for reading 

low is reached (0

)

8- Generate the input signal high 

(20mA)

Operate Span potentiometer, until the value for reading 

high is reached 

(1000)

9- Repeat steps 7 and 8, until desired accuracy is obtained

Offset