The instrument  has two menus accessible to the user :
 

Configuration menu

’ (key SQ) (

<

)

 

Fast access

’ menu (key UP) (

5

)

Configuration menu

The ‘

configuration menu

’ modifies the configuration parameters to 

adapt the instrument to the application needs. To access the ‘

con-

figuration menu

’ press for 1 second the SQ (

<

) key. This access can 

be  blocked  by  activating  the  ‘

Password

’  (‘

PASS

’)  function.  While 

operating the ‘

configuration menu

’, the alarm status is ‘hold’ to the 

status they had before accessing the menu, and the output and con

-

trol modules remain in ‘

error

’ state. When leaving the ‘

configuration 

menu

’,  the  instrument  applies  a  system  reset,  followed  by  a  brief 

disconnection  of  the  alarms  and  the  output  and  control  modules. 

Functionality is then recovered.
For a detailed explanation on the ‘

configuration menu

’ see section 

1.12

and for a full view of the ‘

configuration menu

’ structure see 

section 

1.13

.

Fast access

’ menu

The ‘

fast access

’ menu is an operator configurable menu, providing 

fast and direct access to the most usual functions of the instrument 

with a single key pad stroke. Press key UP (

5

) to access this menu.

See section 

1.12.5

 for a list of functions eligible for ‘

fast access

’ in 

this instrument. The ‘

Password

’ (‘

PASS

’) function does not block ac

-

cess to this menu. Accessing and modifying parameters in the ‘

fast 

access

’ menu does not interfere with the normal functionality of the 

instrument, and it does not generate any system reset when validat

-

ing the changes.

Front key pad description

Key SQ

 (

<

) - press the SQ (

<

) key for 1 second to access the ‘

con-

figuration  menu

’.  Inside  the  menu,  the  SQ  (

<

)  key  functions  as  a 

‘ENTER’ key. It selects and accesses the menu option currently dis

-

played. At menus with numerical value entries, it validates the num

-

ber displayed.

Key UP

 (

5

) - the UP (

5

) key gives access to the ‘fast access’ menu. 

Inside the menus, it moves vertically through the different menu op

-

tions. At menus with numerical value entries, it modifies the digit 

selected by increasing its value to 0, 1, 2, 3, 4, 5, 6, 7, 8, 9.

Key LE

 (

3

) - inside the menus, the LE (

3

) key functions as the ‘

ES-

CAPE

’ key. It leaves the selected menu, and eventually, will leave the 

whole menu. When leaving the ‘

configuration menu

’ with the LE (

3

key, the changed parameters are activated. At menus with numeri

-

cal value entries, the LE (

3

) key allows to select the active digit. To 

modify the value of the selected digit use the UP (

5

) key.

Menu ‘rollback’

After 30 seconds without interaction from the operator, the instru

-

ment will rollback and leave the ‘

configuration menu

’ or the ‘

fast ac-

cess

’ menu. All changes will be discarded.

1.10 How to operate the menus

Messages and errors

‘h.udr’

 

‘h.oVr’

Hardware underrange (‘

h.udr

’) / overrange (‘

h.ovr

’). In

-

put  signal  is  lower  /  higher  than  the  minimum  /  maxi

-

mum signal the instrument can detect.

‘d.udr’

 

‘d.oVr’

display  underrange  (‘

d.udr

’)  /  overrange  (‘

d.ovr

’).  The 

instrument  already  displays  the  minimum  /  maximum 

value possible (-1999 / 9999).

‘hoLd’

the ‘

hold

’ function is active. Display is on hold.

‘P.hLd’

the ‘

Peak&Hold

’ function is active.

‘Err.0’*

at the ‘

scaling

’ (‘

ScAL

’) menu entry, the defined slope is 

higher than ‘5000’ (slope almost vertical). Entered values 

are dismissed and default values are activated.

‘Err.1’

incorrect password.

‘Err.2’

at ‘

oPt.X

’ menu entry. Installed module is not recognized.

Table 5 - Messages and error codes

The error messages are shown on display in flash mode.

(dhI-dLo)  [counts]

 (IhI-ILo)   [mA or Vdc]< 5000

*slope calculation for error ‘

Err.0

’.

1.11 

Messages and errors

Example  of  operation  inside  the  

configuration menu

’.

1. The SQ (

<

) key enters into the 

‘configuration menu’.
2. The SQ (

<

) key enters into the 

InP

’ option menu.

3. The UP (

5

) key moves through 

the menu options.
4.  The  SQ  (

<

)  key  selects  the 

desired range and returns to the 

InP

’ menu.

5. The LE (

3

) key leaves the ac

-

tual menu level and moves to the 

previous menu level.
6. The LE (

3

) key leaves the ‘con

-

figuration menu’. Changes are ap

-

plied and saved at this moment.

Input

(2)

(3)

(3)

(3)

(3)

(3)

(4)

(4)

(4)

(4)

(5)

(5)

(5)

(5)

(3)

(3)

(6)

(6)

(1)

(3)

(3)

(3)

(5)

(5)

(5)

Содержание K K40-A Series

Страница 1: ...x 48 mm size 1 8 DIN Reading with 4 digit dis play Fast access to alarm setpoints on power up function measure function configurable reading brightness Universal AC and DC power Up to 3 optional modules for output and control relays tran sistor control SSR analog outputs Modbus RTU communications RS 485 ASCII RS 232 www fema es Tel 34 93 729 6004 info fema es User s Manual ELECTRONICS FOR INDUSTRI...

Страница 2: ... for maximum and minimum reading password protection 5 brightness levels 1 1 How to order Index 1 Panel meter K40 A 2 1 1 How to order 2 1 2 Front view 3 1 3 Rear view 3 1 4 Power connections 3 1 5 Signal connections AC voltage 3 1 6 Signal connections AC current 3 1 7 Technical specifications 4 1 8 Mechanical dimensions mm 5 1 9 Coupling AC or AC DC 5 1 10 How to operate the menus 6 1 11 Messages...

Страница 3: ...e section 1 4 Detail of the plug in screw terminals provided with the instrument The instrument is provided with all terminals needed both male and female To configure the voltage AC measure select the jumper for the de sired scale as indicated in the table below Then activate the selected scale in the configuration menu see section 1 12 1 and connect the input signal to the signal terminals Scale...

Страница 4: ...z for AC currents minimum frequency 25 Hz for reading oscillation 1 count 1 7 Technical specifications Power power H 85 a 265 Vac dc power L 11 a 60 Vdc y 24 48 Vac isolation 2500 Veff with power H 1500 Veff with power L all units tested during 60 seconds consumption 1 5 W only meter 4 0 W meter with options Configuration 3 buttons front keypad and rear jumper Front protection IP65 Output and cont...

Страница 5: ...Password configuration block 1 12 10 Measure yes 1 12 5 Peak Hold yes 1 12 4 Display brightness 5 levels 1 12 13 Table 4 Functions included 1 7 Technical specifications cont 1 8 Mechanical dimensions mm 1 9 Coupling AC or AC DC The instrument provides and internal jumper to block the DC component of the signal By default the blocking of the DC com ponent is disabled To block the DC component of th...

Страница 6: ... through the different menu op tions At menus with numerical value entries it modifies the digit selected by increasing its value to 0 1 2 3 4 5 6 7 8 9 Key LE 3 inside the menus the LE 3 key functions as the ES CAPE key It leaves the selected menu and eventually will leave the whole menu When leaving the configuration menu with the LE 3 key the changed parameters are activated At menus with numer...

Страница 7: ... low F Lo function Then the following sequence will start message with signal type mA or Vdc message wait WAIt in flash mode after 5 seconds message ok oK appears at this point press key SQ the menu returns to menu entry Field Low F Lo The instrument has read the input signal and automatically config ures the Input low I Lo for you Repeat the process generating the maximum input signal and access ...

Страница 8: ...hing of the alarm relays due to fluctuating input signals around the set point at Activation delay dEL 0 configure the delay to apply before alarm activation The activation delay starts counting when the set point value is passed Value from 0 0 to 99 9 seconds at Deactivation delay dEL 1 configure the delay to apply before alarm deactivation The deactivation delay starts counting when the setpoint...

Страница 9: ...displays the maximum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see section 1 12 5 the Memory of minimum MAX function displays the minimum reading value stored in memory It also provides a way to reset the value This parameter is eligible for configuration through the Fast access menu see sectio...

Страница 10: ... Setpoint 3 Measure The UP 5 key at the front of the instrument gives access to a list of functions configurable by the operator See section 1 10 for an ex planation on how to operate the fast access menu The Key UP Fast access K uP menu allows to select which func tions will be accessible through the fast access menu Select on to activate each function the Setpoint 1 ALr1 function allows to visua...

Страница 11: ...ent light intensity Menus OPt 1 OPt 2 and OPt 3 give access to the configuration menus of the output and control modules installed at slots Opt 1 Opt 2 and Opt 3 See section 2 for a list of output and control modules available for each slot The configuration menu of each module is described at the User s Manual of each module At the Factory reset FAct menu select yes to load the default factory co...

Страница 12: ...m 1 Setpoint Hysteresis Active Alarm type Activation delay Setpoint 2 Deactivation delay Left zeros Steps Average filters 0 0 to 99 9 Display Fixed digits Memory of maximum Memory of minimum Peak Hold Time seconds Alarm 2 menu Alarm 3 menu Relay inverted Locked alarm Scale 600 Vac Scale 100 Vac Scale 10 Vac Scale 1 Vac Scale 100 mVac Scale 5 Aac Scale 1 Aac Field correction Correction high Correct...

Страница 13: ...tpoint 3 Measure On power up Delay Seconds Key LE Alarm unlock No function Option 1 Configuration menu for the module installed at Opt 1 Option 2 Configuration menu for the module installed at Opt 2 Option 3 Configuration menu for the module installed at Opt 3 Minimum Brightness Maximum Standard Password Firmware version Factory reset AC deadband ...

Страница 14: ...qualified personnel only To open the housing use a flat screwdriver to free the fixation clips if possible in the following order D C B and A Remove the front cover Let the inside of the instrument slide out of the housing To reinsert the instrument make sure that all modules are correctly connected to the pins on the display module Place all the set into the housing assuring that the modules corr...

Страница 15: ... manufacturer eligible for responsibility on additional damages or costs Scale 0 600 Vac Scaling and decimal point 0 600 Vac 0 600 0 Alarms 1 2 and 3 Active off disabled Type alarm as maximum Setpoint 1000 Hysteresis 0 counts Activation delay 0 0 seconds Deactivation delay 0 0 seconds Setpoint 2 off Inverted relay off Locked alarms off Display Fixed digits off Average off Steps off Left zeros off ...

Страница 16: ...ntinuous Isolation 3500 Veff Type of terminal plug in screw terminal pitch 5 08 mm Slots allowed Opt 1 Opt 2 Opt 3 Terminal A Common Terminal B NO Normally open Terminal C NC Normally closed Power Opt 2 Opt 1 Opt 3 A B C A B C Signal A B C The T1 module provides 1 transistor output to install at digital panel meters from Series K up to a maximum of 3 transistors in a single meter Configuration is ...

Страница 17: ... special configuration Terminal A Vexc Terminal B Signal in mA or Vdc Terminal C GND Jumper M closed for mA Jumper V closed for Vdc For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Power Opt 2 Opt 1 Opt 3 A B C A B C Signal A B C MV MV MV The SSR module provides 1 output to control SSR relays to install at digital panel meters from Series K up to a maximum of 3 SSR co...

Страница 18: ... Opt 2 Opt 1 Opt 3 B A G B A G Signal B A G Terminal B B signal from RS 485 bus Terminal A A signal from RS 485 bus Terminal G GND For more information http fema es docs 4254_SERIES_M K S_ OPTIONS_manual_i pdf Protocol Modbus RTU Functions implemented 4 Read_Input_Registers Bus type RS 485 up to 57 6 Kbps Isolation 1000 Vdc Slots allowed Opt 1 Opt 2 Opt 3 The RTU module provides a Modbus RTU commu...

Страница 19: ...programs Access to display values alarm status memory of maximum and minimum alarm setpoints Configuration from instrument front keypad through menu entries Opt 1 Opt 2 or Opt 3 depending on the position the module is installed The S2 module can be ordered pre installed into a Series M panel meter or standalone for delayed installation as it does not require soldering or special configuration Rela...

Страница 20: ... without front key pad To configure the instrument remove the meter from the panel and remove the front filter Inter nal press buttons for configuration are accessible Optionally request the instrument preconfigured from factory Without front keypad 3 1 Option NBT ...

Страница 21: ...older 4 1 THM benchtop housing Adapter96 x 96 mmfor96 x 48 mm instruments Adapter for DIN rail mount for Series M and Series K of panel meters Front IP65 protector for Series M and Series K of panel meters Wall mount housing Together with the KIP protector offer a full IP65 protection For Series M and Series K of panel meters 4 2 Adapter DRA M 4 3 Adapter KA96 4 4 WME housing 4 5 Protector KIP ...

Страница 22: ...FEMA ELECTRÓNICA Series K K40 A 22 Notes ...

Страница 23: ...FEMA ELECTRÓNICA Series K K40 A 23 Notes ...

Страница 24: ......

Отзывы: