FEMA ELECTRÓNICA . SERIES B . Models Bxx-T
11
1.13.2 Initial set-up
To configure the initial set up of the instrument, select the
sensor that is connected to the instrument, and then config
-
ure the parameters at the ‘temperature configuration’ menu.
At the ‘
Input
’ (‘
Inp
’) parameter, select the sensor that is con
-
nected to the instrument. Available options are Pt100 / RTD
with 2 wires, Pt100 / RTD with 3 wires, and thermocouples J,
K, T, E, S, R, N, C, L and X. Thermocouple X is a linear 10 uV/ ºC
signal.
At the ‘
Temperature configuration
’ (‘
cnF.t
’) menu, configure
the following parameters:
• at the ‘
Degrees
’ (‘
dEG
’) parameter select ‘
ºc
’ to read the
temperature in degrees celsius or ‘
ºF
’ to read in degrees
Fahrenheit.
• at the ‘
Resolution Pt100
’ (‘
P.rES
’) parameter select ‘
1º
’ to
read the Pt100 / RTD with 1 degree resolution, or ‘
0.1º
’ for
tenths of degree resolution.
• at the ‘
Reading offset
’ (‘
oFFS
’) parameter introduce a
number of counts that will be directly added to the read
-
ing. This value applies both to the Pt100 \ RTD and thermo
-
couples. This offset allows to easily compensate for errors
due to different types of probes, which can not be correct
-
ed by any other means. Values accepted from -100 to 100
counts of display.
• at the ‘
Thermoc. CJC
’ (‘
t.cJc
’) parameter activate o de
-
activate the automatic compensation of the thermocouple
cold junction. When working with real thermocouples,
compensation must be set to ‘
on
’. When working with
electronic thermocouple simulators, it may be necessary
to deactivate the automatic compensation.
• at the ‘
on break
’ (‘
on.bk
’) parameter configure the be
-
havior of the instrument (and thus, the alarm behavior) in
case of sensor break. Select ‘
to_h
’ to force the reading to
go to high level (overrange), or select ‘
to_L
’) to force the
reading to low level (underrange).
• at the ‘
Alpha
’ (‘
ALPh
’) parameter select the alpha for the
Pt100 / RTD sensor. The two standard industrial values are
‘
385
’ and ‘
390
’.
Press ‘SQ’ (
<
) for 1 second to access the ‘
configuration
menu
’. For a description on how to operate inside the menus
see section
. For a full vision of the ‘
configuration menu
’
structure see section
.
Input
Pt100 / RTD 2 wires
Pt100 / RTD 3 wires
Thermocouple J
Thermocouple K
Thermocouple T
Thermocouple E
Thermocouple S
Thermocouple R
Thermocouple N
Thermocouple C
Thermocouple L
Thermocouple X
Temperature
configuration
Degrees
Degrees Celsius
Degrees Fahrenheit
Resolution Pt100
1º resolution
0.1º resolution
Reading offset
Thermoc. CJC
‘On break’
Reading to maximum
Reading to minimum
Alpha
Alpha 385
Alpha 390