TST
Startup
FU3E
FEIG ELECTRONIC GmbH
Page 5 of 29
FU3E_Inbetriebnahme_7_GB.doc
2
Technical Data for TST FU3E
Abmessungen Gehäuse (B x H x T):
FU3E: 300x400x120mm (excl. wall bracket)
Installation:
Vertical using wall bracket on housing bottom
Supply voltage through L, N, PE:
400 V
AC
±
10%, 50...60 Hz
Permissible range: 200...480V ± 10% / 50...60Hz.
Fuse: 16A K-type
Controller internal power consumption:
max. 50W fully assembled and with motor not running
External supply voltage 1 (230 V):
230 V
AC
±
10%, 50...60 Hz
(fused on the circuit board: F202 / 1 AT)
Control voltage / external supply 2:
24 V
DC
regulated (
±
5% at nominal voltage 230 V)
max. 500 mA incl. optional plug-in modules.
With circuit breaker, short-circuit protected by central switching regulator.
Control voltage / external supply 3:
For electronic limit switches and safety edge
Nominal value 11.5V / max. 130mA
Control inputs:
24 VDC / typ.15 mA, max. 26VDC / 20mA
all inputs are to be connected potential-free or:
< 5 V: inactive
Æ
logical 0
< 7 V: active
Æ
logical 1
min. signal duration for input control commands: >
100 ms
galvanically isolated via optocouplers on the circuit board
Inputs INK 1 and INK 2:
For two 24V active 90° offset pulse inputs, max. 20mA load.
< 5V: inactive
Æ
logical 0, > 16V active
Æ
logical 1
Limit frequency: 1kHz
RS485 A and B:
For electronic limit switches only.
RS485 level, terminated with 100
Ω
.
Safety chain / Emergency-Stop
all inputs are to be connected potential-free
Contact load capacity
≥
26 VDC /
≥
120 mA
When safety chain is interrupted, no movement of the drive is possible, not even in
deadman mode
Factory setting unjumpered
Safety edge input:
For electrical safety edges with 1.2k
Ω
or 8.2k
Ω
termination resistor and for dynamic
optical systems..
Relay outputs
If inductive loads are switched (e.g., additional relays), these must be equipped with
recovery diodes and appropriate noise suppression means (regenerative diodes,
varistors, RC elements)
Relay K3:
Standard brake relay:
Changeover contact for enabling electromechanical brakes with interposed brake
rectifier.
230VAC / 3A.
When the E-STOP is tripped, the brake output immediately becomes active.
Relays K4 and K5
“Fault / Door position messages / Lamp functions
Changeover contact potential-free
min. 10mA
max. 230VAC / 3A
230V permitted only when connecting
the same phase as the supply voltage.
Contacts used once for power
switching can no longer switch low
currents.
Drive output:
For drives up to 2.2kW (Version –A) resp. 4KW (Version –C) at 230V
Motor constant current at 100% duty factor and 40°C ambient temperature: 5A
Motor constant current at 60% duty factor and 50°C ambient temperature: 5A
Version –A: 5A, Version –C: 10A
Short-time overload capacity up to 15A resp. 22A for 0.5s
Max. length of motor cable: 30m
Brake resistance load (optional):
max. 1.5KW for max. 0.5 seconds.
Repetition rate min. every 20 seconds.
Temperature range Operating:
Storage:
-10...+50°C
-25...+70°C
Relative humidity
up to 80% non-condensing
Vibration
low-vibration installation, e.g. on a concrete wall
Enclosure rating
IP54
Weight
approx. 5 kg
Directives
Standards:
EMC Directive:
89/336/EWG
superceded by:
91/263/EWG
92/031/EWG
93/068/EWG
EN 50081-1 / 03.93:
Noise emission, residential
EN 50081-2 / 03.94:
Noise emission, industrial
EN 61000-6-2 / 2001:
Noise immunity, industrial
Low-Voltage Directive:
73/023/EWG
superceded by:
93/068/EWG
EN 60335-1 / 2003:
Safety of Household and similar electrical
appliances / Part 1
Type-tested according to:
EN12453 / 2001:
Industrial, commercial and garage doors and gates.
Safety in use of power operated doors and gates.
Requirements
EN12445 / 2001:
Industrial, commercial and garage doors and
gates—Test procedures
Applied national technical specifications
related to the above Directives
EN12978 / 2003:
Doors and gates - Protection devices –
Requirements and testing procedures