Motor data P.100 – P.103
The following parameter setting is used to teach the TST FU3E door controller the motor type being
used. Read the data from the nameplate and enter in the corresponding parameters.
manufacturer
Type signification
0,5 KW
50 Hz
Iso.Kl.: F
IP 55
Fig. 13: Typical motor nameplate (may vary)
IMPORTANT Be sure to note the Y/
∆
wiring of the motor. The motor data must be entered according
to the motor wiring.
U1
V1
W1
W2
U2
V2
L1
L2
L3
U1
V1
W1
W2
U2
V2
L1
L2
L3
Star wiring
Delta wiring
Fig. 14: Star/Delta wiring
)
Automatic querying of the basic data can be cancelled by pressing the
¿
OPEN key while the controller
is being turned ON. This takes you directly to the parameterizing level.
6.2 Changing
parameters
)
Changing the basic data is not necessary if they were previously automatically queried and set.
To modify the preset parameters, proceed as
follows:
-
Disconnect the mains plug
-
Set the DIP switch to on.
-
Connect the mains plug.
- Press
Å
STOP and
¿
OPEN at the same
time for approx. 3 sec. to open
parameterizing mode for the door
controller.
-
Change the desired parameter.
-
After making your settings, exit
parameterizing mode by pressing the
Å
STOP key for approx. 3 sec.
-
X1
2
1
ON
2
1
X7
OFF
ON
OFF
Fig. 15: Position DIP-switch
cos
ϕ
0,85
P.101:
Motor current
P.102: Cos
ϕ
P.100: Motor frequency
P.103: Motor voltage
∆
/ Y 2,4 / 1,4 A
∆
/ Y 230 / 400 V