background image

15 

 

- Check the cleanliness of boiler lamellas. If these are dirty then after draining water off the appliance 
demount the heat exchanger and flush it by water jet. After drying the heat exchanger is to be sprayed 
by heat resistant silver paint to prevent flue-gas corrosion. 
- In case of boilers older than 4-5 years inside the coil scale or other deposits may develop (this effect 
is signed by rumbling of the boiler). Deposits deteriorate efficiency to a high degree. Flush by solution 
of acid is needed. It is to be done in a workshop where an acidifying instrument (plastic pump), a 
protecting equipment, the possibility of compactness check and of pipe loss measurement is provided 
and the laws of environment protection may be kept entirely.  
- Every mark referring to a leakage is to be terminated by change of seals. 
- Check compactness of gas armature. 
- Check gas quantity. In case of deviation adjust it to the specified or desired value. 
- Check close of gas valves and safe operation of thermoelectric flame cut-out and flue-gas backflow     
sensor. 
- Check pull of flue-gas. 
- Check safety temperature limiter. 
- Check operation of electronic control panel. 
- Check thermistor, grease of contact surfaces with heat-conductive metal paste. 
- Check operation of room thermostat. 
 
In case of detecting a fault during these checks, terminate it immediately. 
The technician is liable to make a note and justify it with his signature on the accomplishment of 
periodic maintenance. In this case the withdrawal of warrant letter is PROHIBITED. Maintenance is 
not an action of guarantee. 
 

3. Instructions for use and maintenance for users  

First installation of the appliance may only be made by an expert of the service network of NOVUM-
FÉG Ltd. He is bound to get convinced of the proper operation and mounting of the appliance and 
after a test operation to instruct the user about handling. 

Operating of the heating equipment is the following: 
Connect the appliance by opening the shut-off valves to the heating system properly filled up 

with water. Open the gas valve located before the appliance.  
 

3.1. Ignition 

Push the knob located on the front of the appliance until it butts on (see Fig. 8.). 
- Light the pilot flame by a match. 

- Keep the button pushed for about 15 seconds after lighting the pilot flame. On releasing the 
button the flame must keep on burning. 
 

3.2. Operating 

Attach mains to the heating equipment. Only earthed socket may be used! After attachment to mains 
the pump carries out a 1-minute pre-circulation without heating. 

On room thermostat adjust the desired temperature. After this the operation of heating 
equipment is entirely automatic, by switching on-off the main burner it keeps the temperature 
of the room constant. 
 

3.3. Advice for economical operating 

If you spend a longer while outdoors decrease the temperature set on the room thermostat! It is 
advisable to reduce the temperature for nights as well. By this way an energy saving of 8-10% can be 
reached. 
Decrease of delivery water to 70-75 ºC increases the lifetime of boiler and the feeling of comfort. It 
may be achieved by the adjustment knob of water temperature controller located at the bottom of 
electric box (Temperature controller knob Fig. 8.). 
 
 
 
 
 
 

Содержание C 24 H

Страница 1: ...USER S MANUAL Wall mounted boiler for central heating C 24 H F t stechnikai K sz l kgy rt Ltd Hungary 6900 Mak Aradi street 136...

Страница 2: ...4 FLUE GAS PIPING 7 2 5 FILLING AND PUTTING INTO OPERATION 8 2 6 ELECTRIC DESCRIPTION 8 2 7 CONNECTING OF ROOM THERMOSTAT 9 2 8 INSTALLATION 10 2 9 FROST PROTECTION 11 2 10 FIRST INSTALLATION 12 2 11...

Страница 3: ...electric appliance do not move any electric wall plug do not employ an open fire In case of further gas leakage turn off the main gas valve under the gas meter The gas leakage must be reported to the...

Страница 4: ...Pilot flame holder Flue gas backflow sensor Limiter thermostat Pump Electric control box Purging screw Thermocouple Gas inlet pipe 19 20 Thermistor Display A G B Delivery water Gas connection Returni...

Страница 5: ...s inlet 3 Thermocouple 4 Burner 5 Heat exchanger 6 Delivery temperature sensor NTC 7 8 Flue gas backflow sensor Limiter thermostat 9 Deflector 10 Purging screw 11 11 Pilot flame pipe 12 12 Magnetic va...

Страница 6: ...temperature controller 5 30 C Weight kg 22 At 15 C and 1013 mbar Table 1 2 General instructions for installation 2 1 Placement of the appliance Make sure that the wall is suitable for mounting the app...

Страница 7: ...nt Gas connections The cross section of the connecting pipe must be at least the same or bigger than of the gas pipe in the boiler A closing fitting must be mounted before the appliance The furnace ca...

Страница 8: ...if the boiler is placed into a cabinet then it is to be built from floor to ceiling its walls and door must be made of non burnable material If possible its door should be gridded 2 4 Flue gas piping...

Страница 9: ...hed wall socket placed beside the appliance or in case of a bathroom in zone 3 and connect it to the electric network of the house Max current drain of the boiler is not bigger than 1Amper Attention T...

Страница 10: ...rent input e g Floor heating module electronic temperature controller etc mains input can be connected from points 5 and 6 which inputs stop when the mains plug of boiler is disconnected Table 1 Sign...

Страница 11: ...a request for heating on the part of room thermostat Turn potentiometer located on electronic panel and marked P1 by a screwdriver while checkig the display As a result of adjustment display changes f...

Страница 12: ...in burner Cause of failure can be Minimum required quantity of water is not provided Temporary lack of water in the leaking heating system Notes Above 91 C the electronics consider thermistor dead sho...

Страница 13: ...ce is to be modified for operation by the supplied gas SEE CHAPTER ADJUSTMENT FOR ANOTHER TYPE OF GAS gas valve must be opened leakages are to be terminated Mains 230V IN 1 2 3 4 7 8 9 10 11 12 13 141...

Страница 14: ...n order to adjust the combined gas valve correctly follow the next steps Connect a pressure gauge to stub C after loosening of closing screw Pressure of connecting gas can be measured on stub E in cas...

Страница 15: ...r 10 and the label on back panel 11 Adjustment from LPG to natural gas After loosening the screw M 4x8 remove the flame trap 3 altogether with the pilot flame pipe 4 After loosening of other fixing sc...

Страница 16: ...er is PROHIBITED Maintenance is not an action of guarantee 3 Instructions for use and maintenance for users First installation of the appliance may only be made by an expert of the service network of...

Страница 17: ...rotective heating operates until 25 C DWT Reaching this value the boiler stops after 1 minute of post circulation Notes frost protection starts to operate only when the gas supply of boiler is ensured...

Страница 18: ...pliance every five years ATTENTION The boiler has got a flue gas backflow sensor When it starts operation the boiler stops automatically Restart can only be made by manual ignition of pilot flame Disa...

Отзывы: