2

Federal Signal

 signaling.fedsig.com

Certification

Certificate Nos:

• 

ATEX Cert No.: Baseefa15ATEX0155X

• 

IECEx Cert No.: IECEx BAS 15.0104X

• 

UKEX Cert No.: SGS23UKEX0086X

• 

ATEX coding: 

 II 2 G D

Protection:

• 

Ex db IIB T5 Gb or Ex db e IIB T5 Gb

• 

Ex tb IIIC T100°C Db IP66 

 

(Tamb= -55°C to + 49°C)

• 

Ex db IIC T4 Gb or Ex db e IIC T4 Gb

• 

Ex tb IIIC T135°C Db IP66 

 

(Tamb= -55°C to + 70°C)

Standards:

• 

EN60079-0:2018

• 

EN60079-1:2014

• 

EN IEC 60079-7:2015+A1:2018

• 

EN60079-31:2014

• 

IEC60079-0:2017 7th Ed

• 

IEC60079-1:2014-06 7th Ed

• 

IEC60079-7:2017 5.1 Ed

• 

IEC60079-31:2013 2nd Ed.

Specific Conditions of Use

1. 

The Modular Audible Device enclosure incorporates a sinter and the volume is greater than 100 cm

3

; therefore, use 

of the Modular Audible Device in carbon disulphide gas atmospheres is not permitted.

2. 

The Modular Audible Device has external non-metallic surfaces that may provide an electrostatic charging hazard. 

See the manufacturer’s instructions for further information.

3. 

The Modular Audible Device has metallic components in the non-metallic walls of the enclosure, which can store 

electrical charge and therefore may provide a potential electrostatic discharge. The metallic brass inserts have a 

capacitance of 24 pF. See the manufacturer’s instructions for further information.

cULus Zone Certifications

This equipment is for use in Class I, Zone 1, and Zone 21 hazardous (classified) locations. It has been investigated with 

reference to risks to life and property and for conformity to the installation and use in provisions of Articles 505 and 506 

of NFPA 70 (NEC).

These models use protections:

• 

Class I, Zone 1, AEx db IIC T4 Gb or AEx db eb IIC T4 Gb

• 

Zone 21, AEx tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)

• 

Ex db IIC T4 Gb or Ex db eb IIC T4 Gb

• 

Ex tb IIIC T135°C Db IP66 (Tamb= -55°C to +70°C)

Unpacking the Device:  

After unpacking the device, examine it for damage and verify parts. If a part is missing or 

damaged, do not attempt to install, and contact Federal Signal Customer Support. 

Creating Combination Fixtures in the Field

The Federal Signal Global Series Ex de products can be connected together in the field using interchangeable E-box end 

caps and a proprietary coupling system.

The proprietary coupling system allows for simple and cost-effective wiring from product to product, often eliminating 

the need for expensive Ex wiring practices and Ex rated glands. The E-box is available only when factory installed on 

an Ex d unit or when used as an E-box spacer adjoining an existing E-box. Please refer to the accessories listed on 

page 11 for available options. When creating certain fixture combinations, it is necessary to replace E-box end caps 

before mounting the product. If you are creating combination fixtures, refer to instruction manual 25500259 for specific 

instructions and details.

Содержание Global Series

Страница 1: ...tightened After installation test the loudspeaker system to ensure that it is operating properly Keep the unit tightly closed when in operation After testing is complete provide a copy of this instruc...

Страница 2: ...equipment is for use in Class I Zone 1 and Zone 21 hazardous classified locations It has been investigated with reference to risks to life and property and for conformity to the installation and use...

Страница 3: ...apparatus must be securely attached to the mounting surface in accordance with the installation instructions Use installer supplied fasteners suitable for the mounting surface The mounting method and...

Страница 4: ...ing the six 8 5 mm mounting holes Use installer supplied fasteners suitable for the surface to which the device will be mounted Figure 3 Front view of Ex de surface mount 2X 8 5 mm 103 2 mm 4 06 in 12...

Страница 5: ...or reassembling the unit Painting and surface finishes other than those applied by Federal Signal Corporation are not permitted Cable termination should be in accordance with the specifications that...

Страница 6: ...the application Gland entry threads are M20 1 5 x 6 H Tools needed 1 5 mm A F hexagon key No 1 Phillips screwdriver Wire stripper Figure 5 Ex d in out PCB connections 2 8 V 0 8 VRMS 1 2 3 4 Wiring th...

Страница 7: ...y or death This section has wiring instructions for the increased safety models G SPK 70 V and 100 V Ex de units are supplied with a six pole spring tension clamp style terminal block The maximum wire...

Страница 8: ...intaining the Loudspeaker SAFETY MESSAGES TO MAINTENANCE PERSONNEL Listed below are some important safety instructions and precautions you should follow Read and understand all instructions before ope...

Страница 9: ...is as resistant to concentrated acids and alkalis as most metal products However if abnormal or unusual environment conditions occur due to plant damage or accident etc visual inspection of the louds...

Страница 10: ...ervice A return authorization is required Contact your Authorized Distributor or Federal Signal Customer Support Defective products under warranty will be repaired or replaced at Federal Signal s disc...

Страница 11: ...ion Box Spacer Kit G KIT EXTB Single Trunnion Kit G KIT ST Dual Trunnion Kit G KIT DT Adapter M20 Male to 1 2 Female NPT K231246A Adapter M20 Male to 3 4 Female NPT K231247 15 W Audible Acoustic Inser...

Страница 12: ...ranslations available at signaling fedsig com Traducciones adicionales disponibles en signaling fedsig com Customer Support 1 800 344 4634 1 708 534 4756 iordersup fedsig com Technical Support 1 800 7...

Отзывы: