Figure 21 Replacing the glass
APPLY PRESSURE ON
BOTTOM EDGE AT
TRIANGLES AND
ANGLE IN
REPLACEMENT PANEL
TOWARDS 3 RETURN
SPRINGS
REPLACEMENT
PANEL HELD IN
PLACE BY TWO
CORNER
BOSSES
AGAINST 3
COMPRESSION
SPRINGS
ACTIVATION INDICATOR IN
ALARM STATUS MODE
4.
Reattach the front faceplate.
5.
Note that the activation indicator is in ALARM status mode. With the reset keyway attached, rotate the indicator
about 60° counter-clockwise if it is desired to return to NORMAL status mode.
Figure 22 Returning to a normal state
MODEL CP-BG: NORMAL STATE
RESET KEYWAY
MAY ONLY
REMAIN
ATTACHED ON
CP-BG MODELS
Installing/Servicing the Reset Keyway
The reset keyway is factory-attached on the CP-PB and CP-BG stations. On the CP-BG-x-x-x-xxx-xx-2 (E54-11 approved)
stations, it is provided separately to be used only as a discrete standalone key. On these models, the key should not be
permanently installed for EN-54-11 installations and shall be used only for test purposes. Its purpose is twofold:
1.
Provide a means of resetting all devices after an activated ALARM status by a 60° counter-clockwise rotation of
the activation indicator.
2.
Provide a means of ALARM activation testing of the CP-BG stations without breaking the glass panel.
Figure 23 Reset keyway kit
RESET KEYWAY KIT
M4 SET SCREW (USE A
M2 HEX WRENCH TO
TIGHTEN/LOOSEN)
DIRECTIONAL STATUS
INDICATOR
BEARING WASHER TO
BE BETWEEN STATION
AND RESET KEYWAY
Figure 24 Keyway location