background image

6

1. If the furnace and air conditioner are on separate

thermostats, turn the furnace thermostat off during the
cooling season to prevent simultaneous operation of the
heating and cooling systems. Reverse the procedure during
the heating season. 

Adjust thermostat temperature and fan settings according
to the thermostat manufacturer’s recommendations. It is not
recommended to vary the temperature settings more than 5
degrees. Varying the temperature more than 5 degrees or
turning the thermostat off for periods less than 12 hours can
actually cost you more in energy consumption than keeping
the temperature constant. Consider indoor plants and pets
when varying the temperature from the normal comfort
level.

2. IMPORTANT:  Wait at least 3 minutes after turning the air

conditioner off before trying to restart. If an attempt is
made to start the compressor before the refrigerant
pressures are equalized, the compressor motor may trip on
its overload. An additional waiting period will be required
before restarting.

OPERATION INSTRUCTIONS

For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on
this equipment. Frequency of maintenance may vary depending
upon geographic areas, such as costal applications.

MAINTENANCE INSTRUCTIONS

1. Keep the condenser (outdoor coil) clean. Wash it down with

a garden hose if necessary.

WARNING

BE SURE THE UNIT DISCONNECT IS IN THE “OFF”
POSITION AND THAT ALL ELECTRICAL POWER TO THE
UNIT IS TURNED “OFF” BEFORE CLEANING THE SYSTEM.

2.  Remove any loose grass, leaves, papers, etc., from the area

around the condenser coil. These could reduce the air supply
through the coil and reduce the amount of cooling. 

3. Always install and keep system filters clean. Consult your

licensed Contractor for filter replacement schedules and
instructions.

WARNING

SERIOUS PERSONAL INJURY OR DEATH MAY RESULT IF
WATER SPRAY IS DIRECTED TOWARD LIVE ELECTRICAL
CONNECTIONS OR POWER SOURCES. 

CIRCUIT DIAGRAM

WIRE NUT

Содержание C18ABZ1VF

Страница 1: ...alve Step Valve 3 REFRIGERANT PIPING 4 Precautions 4 Liquid Line Sizes 4 Suction Line Sizes 4 SUBCOOLING CHARGING 5 OPERATION INSTRUCTIONS 6 MAINTENANCE INSTRUCTIONS 6 CONDENSING UNIT NOMENCLATURE 7 CIRCUIT DIAGRAM 6 NOTE THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS EQUIPMENT READ THE ENTIRE INSTRUCTION MANUAL THO...

Страница 2: ...local state and federal codes and or regulations pertaining to this type of equipment and its installation Such codes and or regulations should take precedence over any recommendations contained herein in lieu of local codes Installations SHALL be made in accordance with the National Electrical Code local codes and recommendations made by the National Board of Fire Underwriters Consult local build...

Страница 3: ...ssible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop and will make the system less susceptible to liquid migrations due to less refrigerant charge 1 The installer shall check available power to make certain it matches the unit rating plate located inside control box cover and that constant voltage can be maintained to the unit Unsatisfacto...

Страница 4: ...d wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG wire to avoid excessive voltage drop 3 All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power Note Use of available 24 volt accessories may exceed the minimum power requir...

Страница 5: ...cessary use hanger straps which are 1 in wide and conform to shape of tubing insulation Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation Condensing units are available with pre charged sweat type copper connecting fittings Units are factory charged for 15 of line set tubing Adjust charge 0 65 oz per foot of variation from chart for 1 4 and 5 8 lin...

Страница 6: ...function NOTE When removing refrigerant always use standard reclaim procedures FINAL CHECKS FOR INSTALLER 1 Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub through or wire pinching 2 Ensure that all wiring and tubing is secure in unit before adding panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with o...

Страница 7: ...res are equalized the compressor motor may trip on its overload An additional waiting period will be required before restarting OPERATION INSTRUCTIONS For continuing high performance and to minimize possible equipment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as costal applications MAINTENANCE INSTRUCTION...

Страница 8: ...e Township NJ 08831 24 A B 1 V Z C 18 18000 BTU H 5 28 kW 24 24000 BTU H 7 03 kW 30 30000 BTU H 8 79 kW 36 36000 BTU H 10 55 kW 42 42000 BTU H 12 31 kW 48 48000 BTU H 14 07 kW 60 60000 BTU H 17 5 kW 1 208 230 Volts 1 Phase 60 Hz 2 230 Volts 1 Phase 50 Hz 3 208 230 Volts 3 Phase 60 Hz 4 460 Volts 3 Phase 60 Hz 5 230 Volts 3 Phase 50 Hz 6 380 Volts 3 Phase 50 Hz C Air Conditoner CH Heat Pump A Poduc...

Отзывы: