INSTALLATION
Condensing Unit Location

The condensing unit should be located outdoors as close as
possible to the evaporator. Consider the following factors:

Clearances

The air inlet should be located at least 12" from a wall or
other obstruction for unrestricted air flow.
The air outlet should be located so as to direct discharged
air away from the building. Three feet of clearance around
the unit and a minimum of six feet clearance above the
unit is required to avoid recirculation of condenser
discharge air on vertical discharge models.  Avoid locating
unit under low overhanging roofs.

Support

Mount the unit on a sturdy base approximately four to six
inches above the ground. In areas known for snow
accumulation, the unit should be elevated at least 18"
above the ground. A concrete slab is recommended.
Concrete slab should not contact the building foundation
to prevent possible sound or vibration transmission.
Rooftop installation is acceptable in areas of low snow
accumulations, provided the roof will support the unit and
provisions are made for water drainage and the noise or
vibration through the structure.

Exposure

Placement of the unit should be in a well-drained area, or
the unit must be supported high enough so run-off will not
enter the unit.
Avoid installations under roof overhangs without
guttering. Water draining from the roof onto the unit
could produce excessive noise and may cause ice to build
up on the coil or fan during cold weather.

Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.

Do not locate where heat, lint or exhaust fumes will be
discharged on the unit (as from dryer or furnace vent). 

Proximity to Evaporator

Locating the condenser as close as possible to the
evaporator will increase the system capacities by reducing
the line set refrigerant pressure drop, and will make the
system less susceptible to liquid migrations due to less
refrigerant charge.

1. The installer shall check available power to make certain it

matches the unit rating plate (located inside control box
cover) and that constant voltage can be maintained to the
unit. Unsatisfactory performance would otherwise result.
The local power company should be contacted regarding
any problems or questions concerning power supply.

Electrical Connections

WARNING

ELECTRICAL EQUIPMENT SHOULD BE INSTALLED BY A
QUALIFIED, LICENSED ELECTRICIAN. IMPROPER
ELECTRICAL HOOK-UP MAY DAMAGE EQUIPMENT, CAN
CREATE A HAZARD, CAUSE PERSONAL INJURY OR
DEATH,  AND WILL VOID THE WARRANTY.

DANGER

BEFORE PERFORMING ANY WORK ON THIS EQUIPMENT,
POWER SUPPLY MUST BE TURNED OFF AT THE HOUSEHOLD
SERVICE BOX TO AVOID THE POSSIBILITY OF SHOCK,
INJURY, DEATH OR DAMAGE TO EQUIPMENT.

Control box cover

Wiring diagram and rating
plate are located inside
control box cover

Opening for 
low-voltage wiring

Opening for line
voltage conduit or cable

2. Install a line service disconnect switch within sight of the

condensing unit. The line voltage service wiring for the
condensing unit should include a fused disconnect switch.

3. Use correct wire size and fuse size. To ensure that adequate

voltage will be available at the condensing unit, the line
voltage service wiring must be of adequate size. Minimum
recommended wire ampacities and maximum fuse sizes are
listed on the unit name plate.

4.  Two holes are provided in the control box.

a. One is for the connection of the line voltage conduit or

cable. The hole is sized for 3/4" conduit.

b. One is for low-voltage wiring. (Refer to the wiring 

diagram attached to electrical box cover for connection.)

5. Be sure to ground the condensing unit by securing the

ground wire to the grounding lug inside the control box.

6. Be sure to follow National Electrical Code and all local

codes.

11

1

11

2

11

3

on 3 side

to wall

Содержание C18ABZ1VF

Страница 1: ...alve Step Valve 3 REFRIGERANT PIPING 4 Precautions 4 Liquid Line Sizes 4 Suction Line Sizes 4 SUBCOOLING CHARGING 5 OPERATION INSTRUCTIONS 6 MAINTENANCE INSTRUCTIONS 6 CONDENSING UNIT NOMENCLATURE 7 CIRCUIT DIAGRAM 6 NOTE THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION ADJUSTMENT AND OPERATION OF THIS EQUIPMENT READ THE ENTIRE INSTRUCTION MANUAL THO...

Страница 2: ...local state and federal codes and or regulations pertaining to this type of equipment and its installation Such codes and or regulations should take precedence over any recommendations contained herein in lieu of local codes Installations SHALL be made in accordance with the National Electrical Code local codes and recommendations made by the National Board of Fire Underwriters Consult local build...

Страница 3: ...ssible to the evaporator will increase the system capacities by reducing the line set refrigerant pressure drop and will make the system less susceptible to liquid migrations due to less refrigerant charge 1 The installer shall check available power to make certain it matches the unit rating plate located inside control box cover and that constant voltage can be maintained to the unit Unsatisfacto...

Страница 4: ...d wire If thermostat is located more than 100 ft from unit as measured along the control voltage wires use No 16 AWG wire to avoid excessive voltage drop 3 All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power Note Use of available 24 volt accessories may exceed the minimum power requir...

Страница 5: ...cessary use hanger straps which are 1 in wide and conform to shape of tubing insulation Isolate hanger straps from insulation by using metal sleeves bent to conform to shape of insulation Condensing units are available with pre charged sweat type copper connecting fittings Units are factory charged for 15 of line set tubing Adjust charge 0 65 oz per foot of variation from chart for 1 4 and 5 8 lin...

Страница 6: ...function NOTE When removing refrigerant always use standard reclaim procedures FINAL CHECKS FOR INSTALLER 1 Ensure that all wiring is routed away from tubing and sheet metal edges to prevent rub through or wire pinching 2 Ensure that all wiring and tubing is secure in unit before adding panels and covers 3 Tighten service valve stem caps to 1 12 turn past finger tight 4 Leave Owner s Manual with o...

Страница 7: ...res are equalized the compressor motor may trip on its overload An additional waiting period will be required before restarting OPERATION INSTRUCTIONS For continuing high performance and to minimize possible equipment failure periodic maintenance must be performed on this equipment Frequency of maintenance may vary depending upon geographic areas such as costal applications MAINTENANCE INSTRUCTION...

Страница 8: ...e Township NJ 08831 24 A B 1 V Z C 18 18000 BTU H 5 28 kW 24 24000 BTU H 7 03 kW 30 30000 BTU H 8 79 kW 36 36000 BTU H 10 55 kW 42 42000 BTU H 12 31 kW 48 48000 BTU H 14 07 kW 60 60000 BTU H 17 5 kW 1 208 230 Volts 1 Phase 60 Hz 2 230 Volts 1 Phase 50 Hz 3 208 230 Volts 3 Phase 60 Hz 4 460 Volts 3 Phase 60 Hz 5 230 Volts 3 Phase 50 Hz 6 380 Volts 3 Phase 50 Hz C Air Conditoner CH Heat Pump A Poduc...

Отзывы: