STATIC PRESSURE DROP 

THROUGH DRY COIL* & HOUSING (INCHES WATER COLUMN / CFM)

CHECK AND ADJUST AIRFLOW

Check that the correct amount of air is flowing through the
coil by measuring the pressure drop using an air flow gauge.

Checking Static Drop Across Coil

1.

The coil should be dry and clean. The air filter must be
clean and all registers open. Do not run the condensing
unit when checking air flow.

2.  Run the Blower on cooling speed.

3.  Set the blower motor speed-belt drive or direct drive to

the nominal CFM required across coil and the dry coil
static reading.  See chart below.

Adjusting Air Flow

If gauge reading is below the required pressure, increase
blower speed until reading is the same or slightly above the
required pressure. 

If the gauge reading is above required pressure, decrease the
blower speed. 

Refer to instructions included with your furnace or blower for
directions on changing blower  speed.

NOTE:

You may not be able to obtain a gauge reading exactly

the same as the required pressure due to variations in duct
systems and blower speeds.

A slightly high reading is acceptable. 

A low reading will indicate conditions that could cause a
freeze up. This will shorten compressor life. Too much air will
result in poor humidity control and overheating of the
compressor. It may cause tripping of the compressor overload. 

If you are using a belt driven blower, use an ammeter to check
the motor current draw. If the current draw is higher than the
motor name plate amps, replace the motor with one with
greater horsepower.

* Dry coil static shown. Increase static by 20% for wet coil static.

Содержание AC1A024A

Страница 1: ...nd Field Installed Expansion Valves 3 Condensate Drain Plumbing 4 Heater Exchange Clearance 4 CHECK AND ADJUST AIRFLOW 5 Static Pressure Drop Chart 5 Adjusting Airflow 5 COIL NOMENCLATURE 6 SPECIFICAT...

Страница 2: ...rvice personnel are required by some locales to be licensed Persons not qualified SHALL NOT install this equipment nor interpret these instructions This installation and maintenance manual is provided...

Страница 3: ...rs furnaces the same width 1 Set coil on upflow furnace discharge air opening 2 Ensure coil is level for proper condensate drainage Do not tip coil toward condensate drain 3 When installing wider coil...

Страница 4: ...AL IS REQUIRED 2 MINIMUM 3 MINIMUM Install condensate drain trap as close to the coil as possible Use drain connection size or larger Do not operate unit without trap see illustration below Unit must...

Страница 5: ...gauge reading is below the required pressure increase blower speed until reading is the same or slightly above the required pressure If the gauge reading is above required pressure decrease the blowe...

Страница 6: ...kW 060 60 000 BTU H 17 5 kW Nominal Capacity C Cased Coil Case Designation 1 Upflow Downflow Position A A Series Design Series COIL NOMENCLATURE MODEL INDOOR CASED COILS FLUSH FIT TO FURNACE WIDTH DE...

Страница 7: ...ship WARRANTY LIMITATIONS Limited Warranty does not include allowances for labor or travel expense connected with the installation of parts so furnished in this Limited Warranty or for field repair or...

Страница 8: ...ons cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice For replacement p...

Отзывы: