INTRODUCTION

This manual is intended as an aid to qualified HVAC installers
during the installation of Fedders Cased Coils on upflow or
downflow furnaces. Do not install coil in horizontal position
(see illustration below).

Return

Return

Supply

Supply

Downflow
Furnace

Evaporator 
Coil

Evaporator 
Coil

Upflow
Furnace

Codes

The installer SHALL comply with all local, state, and federal
codes and/or regulations pertaining to this type of
equipment and its installation. Such codes and/or regulations
should take precedence over any recommendations
contained herein. Installations SHALL be made in accordance
with the National Electrical Code, local codes and
recommendations made by the National Board of Fire
Underwriters. Consult local building codes and National
Electrical Code (NEC) for special requirements.

INSTALLATION

CAUTION

EXTERIOR SURFACE COIL HOUSING MAY SWEAT WHEN
UNIT IS INSTALLED IN NON-CONDITIONED SPACE SUCH
AS AN ATTIC OR GARAGE. THE INSTALLER MUST
INSULATE THE CABINET WITH 1” FIBERGLASS
INSULATION.

INSPECTION AND UNPACKING

A thorough inspection of the shipping container should be
made immediately upon receiving your unit. Look for any
punctures or openings, and if it appears damage has
occurred, it should be noted on the freight bill before signing.
The delivering carrier should be contacted immediately to
inspect damage, and no installation work should begin until
this inspection is completed.

Installation of Evaporator Coils

The cased coil is designed to fit Fedders furnaces the same
width. 

1.  Set coil on upflow furnace discharge air opening.
2.  Ensure coil is level for proper condensate drainage. 

Do not tip coil toward condensate drain.

3.  When installing wider coil on narrow furnace, use a

field supplied adapter.

4.  When installing narrow coil on wide furnace, create 

field fabricated adapter. Consult your dealer for
alternate installation instructions.

NOTE: In downflow position installation with Fedders
furnace, break off perforated duct flange on coil/furnace.

CAUTION

THE TXV SENSING BULB CAN BE DAMAGED BY

EXTREME HEAT FROM BRAZING. THE BULB SHOULD
BE REMOVED BEFORE PERFORMING ANY BRAZING
PROCEDURE AND NOT INSTALLED UNTIL AFTER THE
VAPOR AND LIQUID LINES ARE BRAZED AND LEAK
CHECKED.

Connect Refrigerant Piping

Use field supplied tubing of refrigerant grade. Suction tube
must be insulated. Do not use damaged, dirty, or
contaminated tubing because it may plug refrigerant flow
control device. ALWAYS evacuate the coil and field supplied
tubing before opening outdoor unit service valves. 

Factory and Field-Installed Expansion Valves

1.  The bulb and capillary tubing should be routed outside

of the case. Make sure the capillary tube will not
contact any sharp edges of the case. On factory
installed expansion valves, the adjustable sensing bulb
is not permanently installed onto the coils’ vapor line in
order to allow easy removal during installation.

8 o’cl

Sensing bulb
attached with
clamps

Vapor line

4 o’clock

8 o’clock

Attach bulb to
vapor line at four
or eight o’clock
position

CAUTION

THE TXV VALVE CAN BE DAMAGED BY EXTREME

HEAT. PROPER PRECAUTIONS SHOULD BE TAKEN TO
AVOID OVERHEATING THE TXV VALVE AND CAUSING
DAMAGE TO THE INTERNAL COMPONENTS.

Содержание AC1A024A

Страница 1: ...nd Field Installed Expansion Valves 3 Condensate Drain Plumbing 4 Heater Exchange Clearance 4 CHECK AND ADJUST AIRFLOW 5 Static Pressure Drop Chart 5 Adjusting Airflow 5 COIL NOMENCLATURE 6 SPECIFICAT...

Страница 2: ...rvice personnel are required by some locales to be licensed Persons not qualified SHALL NOT install this equipment nor interpret these instructions This installation and maintenance manual is provided...

Страница 3: ...rs furnaces the same width 1 Set coil on upflow furnace discharge air opening 2 Ensure coil is level for proper condensate drainage Do not tip coil toward condensate drain 3 When installing wider coil...

Страница 4: ...AL IS REQUIRED 2 MINIMUM 3 MINIMUM Install condensate drain trap as close to the coil as possible Use drain connection size or larger Do not operate unit without trap see illustration below Unit must...

Страница 5: ...gauge reading is below the required pressure increase blower speed until reading is the same or slightly above the required pressure If the gauge reading is above required pressure decrease the blowe...

Страница 6: ...kW 060 60 000 BTU H 17 5 kW Nominal Capacity C Cased Coil Case Designation 1 Upflow Downflow Position A A Series Design Series COIL NOMENCLATURE MODEL INDOOR CASED COILS FLUSH FIT TO FURNACE WIDTH DE...

Страница 7: ...ship WARRANTY LIMITATIONS Limited Warranty does not include allowances for labor or travel expense connected with the installation of parts so furnished in this Limited Warranty or for field repair or...

Страница 8: ...ons cover the general appearance of the units at the time of publication and the manufacturer reserves the right to make changes in design and construction at any time without notice For replacement p...

Отзывы: