INSTALLATION INSTRUCTIONS 

Read and become familiar with these instructions before doing installation. 
 
1.  Install STP per STP/IST Fixed and Variable Length Installation and Owner’s Manual. 
2.  Remove cover of STP-SCI and mount base to wall or other surface. 

 

Note: 

The STP-SCI must be mounted indoors and can operate at ambient temperatures between 40

°

and105

°

 F (4

°

-41

°

 

C).

 

 
3.  Connect input power of 208-240 VAC to L1 and L2 and Ground wire to terminals per Figure 2. 
4.  Connect dispenser hook signal to terminals, 110-250V supply and return per Figure 2. 
5.  Using an ohmmeter, verify the motor leads (M1 and M2) are not  shorted to ground. 
 

Damage to the STP-SCI may occur if motor leads are shorted together or to ground and power is 
applied. 

 

6.  Connect motor leads to M1 and M2 and Ground wires to terminals per Figure 2. 
7.  For Stand Alone controller configuration set SW1 and SW2 poles 1-8 per Figure 1(Stand Alone configuration is 

Factory setting).  For Master-Slave and/or Alternating Circuit configurations, go to 

“Master-Slave/Alternating 

Circuit” 

section, step 9. 

8.  All STP-SCI controllers must be calibrated.  Continue to step 14 

“Calibration”

 section to complete installation. 

 
 
MASTER-SLAVE/ALTERNATING CIRCUIT 

The Master-Slave feature allows the master to turn on additional STP’s when the first STP operating needs help due to 
loading (flow rate) or an abnormal condition exists.  The Alternating Circuit (AC) feature continuously alternates the lead 
pump, thus turning on a different STP each time all dispensers are shut off and at least one dispenser is turned back on.  
The Master-Slave/AC configuration combines the features of the Master-Slave and AC functions. 

 
Note: • 

 

STP-SCI is not compatible with the STP-SC or the STP-SCB in Master-Slave, Alternating Circuit configurations. 

•  

Master-Slave will not work with PMA33, PMA75B (50 Hz PMA), or PMAH150B (50 Hz PMA). 

 

9.  Wire STP-SCI controllers according to Figure 3 for Master-Slave, Figure 4 for AC or Figure 5 for Master-Slave & AC 

Configurations. Connect Communication cable, RS 485, to terminals (+, G, and  –) wire “+” together, “G” together and 
“-“ together then wire the shielded cable drain wire to Ground (G) at one end only, Use at least 22 AWG three 
conductor shielded cable with drain wire. 

 

10.  Connect dispenser hook signal to the STP-SCI designated as Master per Figures 3,4, and 5. 

 

Note: 

Be sure L1, L2, M1, M2 and Grounds are installed at each STP-SCI. 

 

11.  Configure Master-Slave and Alternating Circuit features by setting SW2 poles 3 and 4 per Figure 1. 
12. Create an address for each controller by setting SW1 poles 1-5 per Table 1.  Each Controller must have its own 

unique address. 

13.  Attach cover of controller to base and complete the 

“Calibration”

 section of the installation manual, step 14. 

 

Note: 

There can only be one Master in a system and up to 31 slaves. 

 
 

CALIBRATION 

Note: 

Before calibration process can begin, fuel level in tank must be above the motor intake 

 

1.  It is recommended to close either the STP clamp valve or a ball valve at the STP discharge. Turn on power supply to 

the STP-SCI.  The green light indicator will come on steady, the red light indicator will flash eight times and the 
audible alarm will beep eight times.  This indicates the STP-SCI is Uncalibrated. 

2.  Put the controller in calibration mode by pressing and holding the 

reset button

, the push-button on the right side of 

the control box, until all three light indicators blink alternately. This will take approximately 10 seconds.  Release the 
reset button.  

For Master Slave and Alternating Circuit configurations put the master and all the slaves into 

calibration mode before going to step 3.

 

3.  Lift a handle on a dispenser to turn the pump on.  After approximately 16 seconds the controller will take a “snapshot” 

of the voltage, current and power.  The three lights will quit alternating and only the green light will remain flashing.  
This indicates the calibration is complete and the dispenser handle can be turned off. Remember to open the STP 
clamp valve or ball valve when calibration is complete. If the controller does not calibrate the red light will flash and 

Warning 

Содержание STP-SCI

Страница 1: ...klin Fueling 3760 Marsh Rd Madison WI 53718 USA Tel 1 608 838 8786 800 225 9787 Fax 1 608 838 6433 www franklinfueling com Installation and Owner s Manual Software Revision 1 4 SMART CONTROLLER I STP...

Страница 2: ...identally turned on while the STP SCI is being installed electrical power could be applied to the STP SCI creating the risk of potentially lethal electrical shock hazard ALWAYS tag and lock breakers s...

Страница 3: ...gure 5 for Master Slave AC Configurations Connect Communication cable RS 485 to terminals G and wire together G together and together then wire the shielded cable drain wire to Ground G at one end onl...

Страница 4: ...c line leak detection is used make sure the STP SCI is in calibration mode all three lights flashing alternately before the dispenser handle is turned on If it is not the STP SCI will not turn on and...

Страница 5: ...n Off Off Slave 8 Off Off Off On Off Slave 9 On Off Off On Off Slave 10 Off On Off On Off Slave 11 On On Off On Off Slave 12 Off Off On On Off Slave 13 On Off On On Off Slave 14 Off On On On Off Slave...

Страница 6: ...ed switch in the ON position the controller will operate as a standard control box It will not indicate or shut down any abnormal condition with the exception of an over current condition short or loc...

Страница 7: ...y still be power present at the STP SCI Hook Terminal If this condition exists call FE Petro Technical Service for assistance Red Light Flashing Alarm Beeping Abnormal condition Determine the number o...

Страница 8: ...acement Inspection 2 Disconnect input voltage at load center lock and tag out circuit breakers 3 See PMA Replacement Instructions P N 400289002 included with New PMA Disengage the 3 4 securing bolt of...

Страница 9: ...t step 7 Remove the junction box cover and do conductivity test on wires in the junction box after the capacitor through the extractable discharge head orange to orange red to red and black to black I...

Страница 10: ...10 Figure 2 STP SCI Stand Alone Wiring Diagram...

Страница 11: ...11 Figure 3 STP SCI Master Slave Wiring Diagram...

Страница 12: ...12 Figure 4 STP SCI Alternating Circuit Wiring Diagram...

Страница 13: ...13 Figure 5 STP SCI Master Slave Alternating Circuit Wiring Diagram...

Страница 14: ...14 REPLACEMENT PARTS Upper Board Relay Assembly P N 225005930 Lower Board Control Assembly P N 225000930 Lower Board Upper Board Picture 4...

Страница 15: ...15 This page intentionally left blank...

Страница 16: ...2004 FE Petro Form No 223987101 Rev 4...

Отзывы: