Start-up
7.1
Prerequisites for commissioning
Attention!
1. You must mount and connect the device in accordance with the operating instructions.
2. Double check that all connections are correct.
3. The mains voltage must match the information on the rating plate.
4. The rated current on the rating plate will not be exceeded.
5. Make sure that no persons or objects are in the hazardous area.
7.2
Procedure for commissioning
Sequence
Setting
1
"
Check if Thermostats or Thermistors of the motor are connected to input
“
TB/TP In
”
.
"
If the motor protection function of the device is not neccesary the both terminals
“
TB / TP
”
have to be
bridged.
2
"
Check connection and close housing carefully.
3
"
Turn on mains voltage.
Display after
fi
rst turning on the mains voltage.
4
In the menu group
Start
the adjustment for
Motor
is
OFF
for factory setting => display:
|
STOP
|
.
This prevents the system from inadvertently starting up before con
fi
guration is complete.
Operation of the device after pressing the
|
Esc
|
hotkey combination.
Switch-over between
“
OFF
”
and
“
Start
”
with the key shortcut for Es-
cape ((Esc =
▼
+
▲
).
5
Menu group:
Start
"
Set the menu language if necessary (factory setting English = Language GB).
6
Menu group:
Base setup
"
Setting the desired operation Mode (factory setting
1.01
= Speed controller see Selection Mode).
"
Further settings depend on the selected mode and the sensor / setting signal used.
Attention!
When saving the operating mode, the respective preset factory operating-mode setting is loaded. That means,
the settings you have made, e.g., in
“
Motor setup
”
are lost. An exception: the menu language setting remains
preserved.
7
The
Motorsetup
factory installed values are for variable voltage external rotor motors
400 V / 50 Hz
. After
checking of the motor data the setting are to be adapted if necessary.
Motor rated voltage
(see Rating plate)
Setting
Edgefrequency
Setting
Max. Frequency
3 ~ 400 V, 50 Hz
48.5 Hz
50 Hz
3 ~ 400 V, 50/60 Hz
48.5 Hz
60 Hz
3 ~ 400 V, 60 Hz
57 Hz
60 Hz
Additional settings see Motor Setup.
8
Menu group
Setting
:
"
Set the parameters for the control operation
9
Menu group
Start
:
"
Switch setting for
Motor
to
ON
.
Information
Settings for U/f characteristic can only be made when no motor modulation is present! This is the same
also for the setting of Mode.
Quick Start Guide
Fcontrol
–
model series FXDM
Start-up
L-BAL-E223-GB 1623 Index 003
Part.-No. 00153236