6.2

Select operation mode

Information

Simple installation is possible through the selection of the preprogrammed mode of operation.
This determines the basic function of the device; factory setting 

1.01

 = Speed controller (activation via 

0 - 10 V signal). The controller con

guration is automatically carried out during selection of the 

application related mode of operation. The factory presets in accordance with the mode of operation 
are based on many years of experience, which is suitable for many applications. Under special 
circumstances, these can be individually adapted (see Controller Setup: 

Controller Con

guration

). 

The purpose of the device is to reach and maintain the target values set. To accomplish this, the 
measured actual value (sensor value) is compared with the adjusted target value, and the controlled 
value (modulation) is deduced from this.

Mode

Signal or Sensor

(input)

Function

1.01

Signal 0 - 10 V (PWM)

Speed controller, two step operation wih external switch over (factory setting)

1.02

-

Manual speed controller with direct setting by the 

 keys (0 - 100 % or in 1 - 

5 steps)

 

 

 

2.01

Sensor TF..(E1)

Temperature control airconditioning and refrigeration.
(preset set-point 20.0 

°

C,  P-band 5.0 K) 

2.02

Sensor TF..(E2)

Temperature control depending on outdoor temperature
(preset set-point 5.0 

°

C, - P-band 20.0 K)

2.03

Sensor TF..(E1)

Temperature control with additional functions (shutter and heating)

2.04

1x Sensor TF..(E1) 
1x Sensor TF..(E2)

Temperature control with two sensors, comparison or average

2.05

1x Sensor TF..(E1) 
1x Sensor TF..(E2)

Temperature control with two sensors differential temperature

 

 

 

3.01

Sensor MBG.. (E1)

Pressure control condensers (refrigeration)

3.02

Sensor MBG..(E1)

Pressure control for condensers with input for refrigerant

3.03

1x Sensor MBG..(E1) 
1x Sensor MBG..(E2)

Pressure control for two circuit condensers

3.04

1x Sensor MBG..(E1) 
1x Sensor MBG..(E2)

Pressure control for two circuit condensers with input for refrigerant

 

 

 

4.01

Sensor DSG..(E1)

Pressure control for ventilation systems

4.02

1x Sensor DSG..(E1) 
1x Sensor TF..(E2)

Pressure control depending on outdoor temperature

4.03

1x Sensor DSG..(E1) 
1x BUS RS 485

Pressure control depending on outdoor temperature, MODBUS for outdoor tem-
perature and remote control by central operating device type AXE-200

 

 

 

5.01

Sensor DSG..(E1)

Volume control (constant) for ventilation systems

5.02

1x Sensor DSG..(E1) 
1x Sensor TF..(E2)

Volume control with setpoint depending on outdoor temperature

 

 

 

6.01

Sensor MAL..(E1)

Air velocity control e.g. clean room

Quick Start Guide 

Fcontrol

 

 model series FXDM

Base setup

L-BAL-E223-GB 1623 Index 003

Part.-No. 00153236

13/22

Содержание FXDM series

Страница 1: ...egrated sine lter for 3 fans Quick Start Guide Detailed Description on www ziehl abegg com Software version D1333A from Version 2 37 L BAL E223 GB 1623 Index 003 Part No 00153236 english CZ D DK E F F...

Страница 2: ...up 12 6 1 Jumper for the input signal 12 6 1 1 External Setpoint External speed setting in manual operation 12 6 2 Select operation mode 13 7 Start up 14 7 1 Prerequisites for commissioning 14 7 2 Pro...

Страница 3: ...ety instructions 2 1 Intended use The equipment is to be used solely for the purposes speci ed and con rmed in the order Any other use above and beyond this is considered not for the intended purpose...

Страница 4: ...ue to faults It is only permitted to remove the housing cover after waiting for 3 minutes once the line supply cable has been shut down Should measurement or adjustment work be unavoidable on the open...

Страница 5: ...ssible shipping damage Start up is not allowed in the case of transport damage At a weight greater than 25 kg for men 10 kg for women the device should be lifted out by two persons according to REFA T...

Страница 6: ...ondingly larger clear ance or thermal shielding is required 4 3 Fastening the device The type of fastening and the number of fastening points are dependent on the housing design All the fastening poin...

Страница 7: ...ning at 8 points GM00002A_M 15 12 2015 1 7 2 3 4 5 6 8 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws...

Страница 8: ...cable inlet for cable glands Metal sheet housings are supplied with stoppers Any cable ducts openings not used must be sealed Strip and insert the cables properly Attach cover for terminal compartment...

Страница 9: ...ective ground must be made double in accordance with EN 50178 Point 5 2 11and 5 3 2 1 up to a cross section of at least 10 mm For an installation of r c d protection it shall be observed that this mus...

Страница 10: ...erminals TB TP have to be bridged Motor fault Motor fault When a connected thermostat or thermistor responds interruption between the two terminals TB TP the device switches off and does not switch ba...

Страница 11: ...selection Mode GND A D B D RS 485 MODBUS Interface for networking via MODBUS RTU A D must always be connected to A D of the next devices the same applies to B D In addition a GND connection must be e...

Страница 12: ...guration in base setup For Potentiometer Analog Out1 terminal A program to function 1A 10 V like factory setting see IO Setup If a second sensor is connected at input 2 external Setpoint or speed sett...

Страница 13: ...02 Sensor TF E2 Temperature control depending on outdoor temperature preset set point 5 0 C P band 20 0 K 2 03 Sensor TF E1 Temperature control with additional functions shutter and heating 2 04 1x S...

Страница 14: ...5 Menu group Start Set the menu language if necessary factory setting English Language GB 6 Menu group Base setup Setting the desired operation Mode factory setting 1 01 Speed controller see Selectio...

Страница 15: ...MotorRa tedVolt OTM 00010 56 11 GB Lan guage 8 W Input power 0 0 Hz Min Speed 2 ext Fault OFF E2 Func tion OFF Save User Setup 10 0 V A max Level max 48 5 Hz Edgefre quency 585 V DC Voltage OFF Reset...

Страница 16: ...3 gures display unit etc 12 Text line 16 gures display text menu P Program key and open menu Menu selection reduce value Menu selection increase value ESC key combination Escape leave menu 8 2 Menu op...

Страница 17: ...In order to simplify the initial start up operation the service level is enabled at rst I e not protected by the PIN 0010 see Controller Setup PIN protection OFF If PIN protection is activated ON the...

Страница 18: ...6 8 7 54 FXDM14M 308143 14 13 5 12 3 40 16 310 54 6 8 5 54 FXDM18AM 308174 18 16 7 15 5 40 20 400 9 1 54 FXDM18M 308173 18 16 7 15 5 40 20 400 8 9 54 FXDM22AM 308108 22 19 2 17 7 40 25 520 14 5 54 FX...

Страница 19: ...for 4 20 mA input Ri 100 Voltage supply e g for sensors 24 V 20 Imax 120 mA for connection to an external AXG terminal minus approx 50 mA Output 0 10 V Imax 10 mA short circuit proof Digital inputs D...

Страница 20: ...issible temperature for the rated current at rated voltage is speci ed as rated temperature Since the dissipation of the power loss heat development in the device is decisively dependent on the ambien...

Страница 21: ...Normal 7 M 3 U V W PE TB Y q 3 Motor mit eingebauten Thermostatschaltern with internal thermostats 3 TB C 24V GND MODBUS RS 485 GND 24 V A D B D A D GND Terminal AXG 1A E B D 1 Line 3 208 480 V 50 60...

Страница 22: ...technical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries ou...

Отзывы: