MOUNTING

On a 4-inch square box with or without
plaster ring. Minimum depth 1.5 inches.

On a 3.5-inch octagonal box. Minimum depth
1.5 inches.

INSTALLATION

Place the detector into the detector base. Turn the de-

tector clockwise until the detector locks into place.

To use the tamper-proof feature, break the smaller tab

on the scribed line in the tamper proof tab located on the
detector mounting bracket. Install the detector. To re-
move the detector from the base when using the tam-
per-proof feature, insert the blade of a small
screwdriver into the hole on the side of the base and
push the plastic lever away from the detector head. This
will allow the detector to be rotated counterclockwise
for removal. NOTE: The decorative ring must be re-
moved in order to remove the head when using the tam-
per-proof feature.

The tamper-proof feature may be defeated perma-

nently by breaking the plastic lever off the base.

NOTE: The number of two-wire smoke detectors

which can be accommodated per zone varies with dif-
ferent control panels. Consult the control panel in-
struction manual to determine the capacity.

Refer to NFPA 72, Chapter 5-3, “Smoke Sensing Fire

Detectors” for spacing, location of detectors and other
guidelines.

TESTING

Detectors may be tested in the following ways:

Place a test magnet against the detector as
directed in the installation instructions. The de-
tector should go into alarm within 30
seconds.

Field metering of detector sensitivity may be
performed with the aid of a voltmeter and Test
Kit, P/N 119-9010N.

For the complete procedure, refer to the Installation

and Maintenance instructions furnished with each de-
tector.

MAINTENANCE

Cleaning programs should be adapted to the individ-

ual environment in conformance with NFPA Standard
72. We recommend at least an annual cleaning of the
unit. The detector screen and cover assembly can be re-
moved, revealing the sensing chamber. A vacuum
cleaner can be used to remove dust from the screen,
cover and sensing chamber. For the complete proce-
dure, refer to the Installation and Maintenance instruc-
tions furnished with each detector.

2 of 2

9020-0375

ORDERING AND TECHNICAL INFORMATION

Part No.

Model

Contacts

Description

112-90001

301PL

Photoelectronic Detector

110-90008

301BL

Base, Two-wire

110-90009

301BL4

Form A & C

Base, four-wire, 24 VDC operation

110-90010

301BL4AC Form A, C & Supv. Base, four-wire, 120 VAC operation

110-90014

B401BH

Base, four-wire, with audible sounder

138-01005

RA-400Z

Remote Alarm Indicator

119-63020

2040-24

Form B

End of Line Relay, 24 VDC

119-9010N

Test Kit