System Wiring and Hookup
x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
DETAIL A
21 16
1
2
3
4
ZONE
CONTROL PANEL
POWER
SMOKE DETECTOR
9.5 - 12.2 VDC
UL LISTED
SMOKE
DETECTOR
MODEL
ESL445AT
MODEL ESL2048
EOL RELAY
RED
BLACK
BROWN
BAT
2.2 K EOL RESISTOR
UL INSTALLATIONS REQUIRE LISTED
END-OF-LINE DEVICE. USE RESISTOR
FROM EOL22 KIT. LOOK FOR LISTING
MARK ON ITEM.
WARNING:
THIS UNIT INCLUDES AN ALARM
VERIFICATION FEATURE THAT WILL
RESULT IN A DELAY OF THE SYSTEM
ALARM SIGNAL FROM THE INDICATED
CIRCUITS. THE TOTAL DELAY (CONTROL
UNIT PLUS SMOKE DETECTOR) SHALL
NOT EXCEED 60 SECONDS. NO OTHER
INITIATING DEVICES SHALL BE CON-
NECTED TO THESE CIRCUITS UNLESS
APPROVED BY THE LOCAL AUTHORITY
HAVING JURISDICTION.
CIRCUIT
(ZONE)
SMOKE DETECTOR
MODEL DELAY-SEC
20
PRODUCT COVERED UNDER
US PATENT #4,791,658
NOTES:
1. Connect to a grounded metal water pipe (16ga. at 15 ft.)
2. Total AUX. power available (including keypad power) is 500mA max. (180mA for fire installations).
Used for connection of devices rated from 11.5 to 13.1 VDC. All circuits are power limited.
3. System must be tested on a weekly basis. For information, refer to manual.
4. Do not connect the transformer to a switch-controlled receptacle. Power varies with transformer (SEE NOTE 2).
5. Installation of equipment and wiring methods are required to be in accordance with the National Electrical code
and ANSI/NFPA No. 72, Chapter 2.
6. Maximum of 4 keypads of LED type or LCD type.
7. Limited energy cable must be used.
8. Maximum for UL installations: Entry Delay, 45 sec.; Exit Delay, 60 sec.
9. For connection of VS-299 Siren Driver. Constant positive (+) unregulated output.
10. Programmable trigger outputs. If used for smoke detector power reset see Detail A.
See manual for programming information. Use model XL-2GTC trigger cable.
11. 24 hr battery standby is required for fire installations. 4 hr battery standby is
required for emergency / burglary.
12. System must be checked by a qualified technician once every three years.
13. Question 14, Location 1 must be set to "00" for smoke detector power.
XL-2T
TRANSFORMER
12VAC, 20VA
(Connect to 24 HR.
120VAC, 60 Hz Outlet
SEE NOTE 4)
+
-
SPEAKER
+
_
_
+
SMOKE DETECTOR POWER
(9.1-12.6 VDC,
50mA max.)
P1
25
19 20 21 22 23 24
12 13 14 15 16 17 18
DC POWER (+)
10-15.5VDC
(SEE NOTE 9)
TRIGGER
OUTPUTS
(SEE NOTE 10)
KEYPAD
(SEE NOTE 6)
BLACK
YELLOW
GREEN
RED
FIRE & BURGLARY
ALARM OUTPUT
(11.5-13.1 VDC,1 A max)
650mA UL
INSTALLATION
VBELL
T1
T2
HOME
TELCO
BROWN
GRAY
HOME
GREEN
RED
TELCO
MODEL 368 CORD
TO RJ31X OR
CA31A JACK
AUX POWER
12VDC Reg., 500mA max.
(SEE NOTE 2)
+
_
2.2K
2.2K
ZONE 1
ZONE 2
2.2K
1
7
6
5
4
3
2.2K
EARTH GND.
(SEE NOTE 1)
8
9
10
11
2.2K
2.2K
ZONE 3
ZONE 4
ZONE 6
+
12V, 4-6AH
BATTERY
MODEL 1240A
(SEE NOTE 11)
_
F1
1 A
F2
3 A
F3
4 A
System Wiring Diagram
JP1 JP2
To re-load factory default values, remove all power
(AC & DC). Short JP1 to JP2. With short still applied,
re-apply power (AC then DC), wait 5 seconds, then
remove short with power still applied.
SYSTEM DEFAULT
RESET JUMPERS
2
ZONE 5
ZONE
7
BROWN
NOTE: UL VERSIONS
CONTAIN PTC's IN
PLACE OF FUSES
BLACK
RED
BAT
CONTROL UNIT
DELAY-SEC
WARNING:
To prevent risk from
electrical shock,de-
energize the system
control unit and
disconnect the
telephone lines
before servicing
this unit.
CONNECTIONS FOR HOUSEHOLD FIRE / BURGLAR ALARM SYSTEM
(PER UL STANDARDS UL985 AND UL1023)
BELL
AUX
BATT
LISTED
HOUSEHOLD
THERMOSTAT
ESL104
XL2T-SOC-V0
+
-
BELL
SYSTEM STABILIZATION MODE:
8SRQ SRZHUXS RI WKH V\VWHP DQG DIWHU FRPSOHWLRQ RI V\VWHP SURJUDPPLQJ
DOO WKH OLJKWV RQ WKH /(' NH\SDGV ZLOO IODVK PRPHQWDULO\ DQG WKH /&' NH\SDGV ZLOO GLVSOD\ 67$1'%< PRPHQWDU
LO\ ($&+ .(<3$' ',63/$< :,// 7+(1 5(7851 72 1250$/ +2:(9(5 ,) 7+( 6<67(0 ,6 $50('
7+( =21(6 :,// 127 5(6321' 72 $/$50 &21',7,216 )25 $3352;,0$7(/< 7:2 0,187(6 7KH
PLQXWH LQWHUYDO LV XVHG WR DOORZ PRWLRQ GHWHFWRUV LQWHULRU ]RQHV WR VWDELOL]H RQ SRZHUXS LQ RUGHU WR SUHYHQW IDOVH
DODUPV 7+( 0,187( 5(63216( 7,0( &$1 %( ',6$%/(' %< 6,03/< (17(5,1* $ 9$/,' 86(5 &2'(
WKDW GLVDUPV WKH V\VWHP DQG UHGXFHV WKH SRZHUXS UHVHW WLPH WR DSSUR[LPDWHO\ 6(&21'6
NOTE:
,I WRWDO V\VWHP SRZHU LV ORVW WKHQ XSRQ SRZHU UHVWRUDWLRQ WKH V\VWHP ZLOO UHWXUQ WR WKH SUHYLRXVO\ DUPHG
VWDWH