1st edition, 03-05-2018
7000.05063, 1st edition, 03-05-2018
7000.05063
Installation
54
4.3
Information on initial commissioning
During the initial commissioning, the correct function of the entire safety circuit must be
tested and documented.
DANGER
DANGER
!
Errors during the installation and commissioning of the Motion Controller could impair its
safety function.
If safety functions are unavailable, the drive can start up unexpectedly or shutdown of the
torque may be ineffective. Depending on the use of the Motion Controller, this can lead to
severe or fatal injury.
Observe the safety information in the chap. 2.2.2, p. 10.
Prior to the initial commissioning, also take the following measures:
Ensure that all operating materials within the safety circuit are professionally installed
and functional.
Check all electrical connections.
Visually inspect all safety-relevant components.
If necessary, take additional safety measures to protect persons from danger during the
initial commissioning which could arise from incorrect function of the safety circuit.
When started, the Motion Controller performs an automatic self-test. An error message is
output if the self-test fails.
When starting the Motion Controller, pay attention for error and STO status messages.
Do not commission a Motion Controller whose self-test has failed.
Perform a self-test daily (see chap. 2.4, p. 11).
During commissioning, check whether the following results are achieved (see
chap. 3.4.1.3, p. 20):
D
The configuration and commissioning of the Motion Controller are described in the
manuals for the Motion Manager 6 and the drive functions (see chap. 1.2, p. 5).
Test criterion
Test result
STO In 1 = high, STO In 2 = high
STO Off
STO In 1 = high, STO In 2 = low
STO On
STO In 1 = low, STO In 2 = high
STO On
STO In 1= low, STO In 2 = low
STO On
Switch-off time via STO In 1
<10 ms
Switch-off time via STO In 2
<10 ms
Power consumption during STO On
<1500 mW
Содержание MC 5004 P STO
Страница 1: ...WE CREATE MOTION Installation Instructions MC 5004 P STO Original Instructions EN ...
Страница 64: ...1st edition 03 05 2018 7000 05063 1st edition 03 05 20187000 05063 Additional documents 64 ...
Страница 65: ...1st edition 03 05 2018 7000 05063 1st edition 03 05 20187000 05063 Additional documents 65 ...
Страница 67: ...1st edition 03 05 2018 7000 05063 1st edition 03 05 20187000 05063 Additional documents 67 ...
Страница 68: ...1st edition 03 05 2018 7000 05063 1st edition 03 05 20187000 05063 Additional documents 68 ...