H 8 - 3  

are described in the following

 

 

Y3 

Y2 

Y1 

Y0 

Error 

Code 

Description 

0 0 0 1 

Application program contains the functions not supported by this
CPU 

Mismatch of PLC ID VS. program ID 

Checksum error in LADDER program 

System STACK abnormal 

0 1 0 1 

5 Watch-Dog 

occurs 

Exceed main unit I/O 

Syntax check error occurs 

Expansion I/O modules over limit 

Expansion I/O points over limit 

10 

System FLASH ROM CRC error 

1 0 1 1  11 

Reserved 

1 1 0 0  12 

Reserved 

1 1 0 1  13 

Reserved 

1 1 1 0  14 

Reserved 

1 1 1 1  15 

Reserved 

 

  Indicator on Transmit/Receive of Built-In Communication Port (Port0) “TX”

“RX”  

These two LED indicators are used for the status of transmit/receive of the built-in communication port (Port0). The RX 

indicator (green) is for indication when PLC receives external signals, while the TX indicator (red) is for indication when 

PLC transmits signals, both of which are very helpful in monitoring communication condition and debugging. When PLC 

communicates with external equipment (computer, programmer, intelligent peripherals, etc.), Port0 in FB

S

-PLC can only 

be used in slave mode (Port1~4 can be used in master mode). Therefore, during its operation, PLC must first receive 

external signals (RX on) before it can transmit signals back to external equipment (TX on now). When the 

communication is fail, one can tell if it’s PLC is not receiving signals or PCL is not replying by looking at the these two 

indicators. The currents in these two LED are constant and their lighting duration is proportional to the reception or 

transmission time. The more received/transmitted data or the slower (bps) reception/transmission, the longer the 

reception/transmission time and so is the indication time (brighter visually). If in high speed but small amount of data, 

only short and dim brightness is observed. Therefore, the communication condition can be easily distinguished by these 

two indicators. 

  Indicator of Input Status

Xn

 

When external input Xn is ON, the corresponding LED indicator Xn will be on, otherwise it will be off. If it fails to respond 
to external input, please check if the terminal wiring is securely connected, or measure the voltage between

Xn

and 

common

C

to see if it has a change of    0V/22V with ON/OFF of input. If it does, it means that an error occurs in PLC 

input circuit or LED indicator. Or you can locate the problem by using the monitor mode of the programmer to check if 
this input status works correspondingly with the external input state. 

 

  Indicator of Output Status

Yn

 

When the Yn output of PLC is ON, its corresponding output indicator will also be on and its external load will be ON. If 

ON/OFF condition of external load is inconsistent with output indicator, please check the wiring of the load, power, and 

terminal for secure connection. If the connection is good, then it should be the PLC output component failure. The main 

reasons to cause the output component failure are: 

1.  Overload or short circuit that burns output component and results in permanent open or short circuit. 

Содержание FBs Series

Страница 1: ...l I O Expansion Unit H1 13 1 7 4 Digital I O Expansion Module H1 14 1 7 5 High Density Digital I O Expansion Module H1 15 1 7 6 Numeric I O Expansion Module H1 15 1 7 7 Analog I O Expansion Module H1...

Страница 2: ...n and Wiring H4 6 Chapter 5 Power Supply Wiring Power Consumption Calculation and Power Sequence Requirements 5 1 Specifications and Wiring of AC Power Sourced Power Supply H5 1 5 2 Specifications and...

Страница 3: ...up the Single End Transistor Output Circuit only applicable to high and medium speed H7 6 7 5 Output Device Protection and Noise Suppression in DO Circuit H7 6 7 5 1 Protection of Relay Contacts and N...

Страница 4: ...example for illustration OUT Y Y6 Y1 AC100 240V C0 Y0 Y4 Y2 C2 Y3 PORT0 Y5 C4 C6 0 4 8 2 I 6 5 9 Y8 Y7 Y9 3 7 IN X X8 X0 PROGRAMMABLE CONTROLLER 24V OUT S S RX TX RUN ERR I2 I3 POW X4 X2 X1 X3 0 8 4...

Страница 5: ...tion board for 7 types CB of CB2 CB22 CB5 CB55 CB25 CBE CBCAN 3 types AIO of B2DA B2AD B4AD and 2 types DAP of BDAP and BPEP 17 Left side communication expansion header only available in MC MN model f...

Страница 6: ...put expansion slot with cover plate removed FBs 16XYR Output expansion slot cover plate z Expansion module with 40mm width case 8XY 8Y 8X 6AD 2DA 4DA 4A2D 2A4TC 2A4RTD 7SG1 7SG2 2TC 6TC 6RTD CM5H 6NTC...

Страница 7: ...h case 24X 24YT 24YJ 32DGI 1 3 Appearance of Communication Expansion Module The Communication Module CM of FBS PLC has a 25mm width case which can be used in the following seven modules CM22 CM25 CM55...

Страница 8: ...ed total 5KHz 10 points relay or transistor output 4 points high speed 200KHz 4 points medium sped 20KHz 1 RS232 or USB port expandable up to 5 built in RTC detachable terminal block FBs 32MC 20 point...

Страница 9: ...nication module FBs CM55 2 ports RS485 Port3 Port 4 communication module FBs CM25 1 port RS232 Port3 1 port RS485 port 4 communication module FBs CM25E 1 port RS232 Port3 1 port RS485 port 4 Ethernet...

Страница 10: ...32DGI connector 30pin Socket 22AWG I O cable length200cm 16 7 Segment LED display DBAN 8 nR 0 8 4 digit 16 segment LED display n means R Red 16 segment LED characters display installed can be 1 4 DBA...

Страница 11: ...retentive C140 C199 60 Can be configured as retentive type 32 Bit Retentive C200 C239 40 Can be configured as non retentive type Non retentive C240 C255 16 Can be configured as retentive type HR DR D...

Страница 12: ...4 32KHz with 1 resolution Captured input Points Max 36 points all of main units have the feature 10 S super high speed high speed input Captured pulse width 47 S medium speed input 470 S mid low speed...

Страница 13: ...S 24V OUT X0 Y8 Y10 Y6 Y4 Y3 Y2 Y1 Y2 SG0 Y3 C4 Y5 Y7 C8 Y9 Y11 X1 X1 X2 X4 X4 X3 X5 X6 X5 X8 X7 X9 X10 X11 X12 X16 X13 X14 X15 X18 X17 X19 FBS 32MN D24 D12 max 400mA IN 24VDC 12VDC z 44 point digita...

Страница 14: ...FBS 14MC D24 D12 IN 400mA max 24VDC 12VDC z 20 point digital I O main unit 12 points IN 8 points OUT AC Power DC Power AC100 240V C0 Y1 Y0 Y2 C2 Y4 Y3 Y6 Y5 C4 C6 Y7 24V OUT S S X0 X2 X1 X4 X3 X8 X6 X...

Страница 15: ...S 40MC AC X21 Y15 C4 C0 C2 Y0 Y1 Y3 Y2 Y4 Y9 Y7 C6 Y5 Y6 C8 Y8 C12 Y11 Y10 Y13 Y12 Y14 X5 24V OUT S S X1 X0 X3 X2 X4 X13 X9 X7 X6 X8 X11 X10 X12 X17 X15 X14 X16 X19 X18 X20 X23 X22 FBS 40MA D24 D12 FB...

Страница 16: ...C7 C5 Y6 Y8 Y7 S S 24V OUT X5 X1 X4 X2 X3 X8 X6 X7 X10 X9 X11 Y11 Y9 C9 Y10 Y12 C13 Y16 Y14 Y13 Y15 X19 X15 X14 X13 X16 X18 X17 X22 X20 X21 X24 X23 FBS 40XY D24 D12 IN 400mA max 24VDC 12VDC z 60 poin...

Страница 17: ...1 Y12 Y15 Y13 C13 Y14 Y16 Y1 C1 Y2 C3 Y3 Y6 C5 Y4 Y5 Y7 Y8 FBS 16Y z 24 point digital I O module 14 points IN 10 points OUT Y1 C1 Y2 C7 C5 Y4 C3 Y3 Y5 Y6 Y7 S S X1 X2 X3 X4 X5 X6 X7 X8 X9 Y10 Y8 Y9 X1...

Страница 18: ...Y13 Y15 V2 Y17 Y19 Y21 Y23 V3 FBS 24YJ 2 54mm Header connector z 7 segment LED display module 8 digits 7SG1 16 digits 7SG2 16 pin 2 54mm Header connector CH1 CH0 FBS 7SG1 2 z Thumbwheel switch multip...

Страница 19: ...T0 T2 T3 T5 T1 FBS 6TC z 16 channel thermocouple input module T0 T1 T2 T3 T4 T5 T6 T6 T5 T4 T3 T2 T1 T0 T7 T7 T8 T8 T9 T10 T11 T12 T13 T13 T12 T11 T10 T9 T14 T15 T14 T15 FBS 16TC z 6 channel RTD input...

Страница 20: ...S 2A4RTD P1 P1 7 62mm fixed terminal block AC Power 24V OUT AC100 240V IN 250mA max FBS EPW AC DC Power 24V OUT 24VDC IN max 250mA FBS EPW D24 7 62mm fixed terminal block 7 62mm fixed terminal block 7...

Страница 21: ...RS232 1 RS485 ports FBs CM25 PORT3 RS232 RX TX T RX N TX PORT4 RS485 G z 1 RS232 1 RS485 Ethernet FBs CM25E PORT3 RS232 RX TX TX TX RX RX RUN LNK PORT4 RS485 T G N ETHERNET 1 2 6 3 z 2 RS485 ports Et...

Страница 22: ...ER PORT2 PORT1 TX RX RX TX FBs CB55 FBS CB55 z 1 RS232 1 RS485 ports PORT1 RX PORT2 TX PROGRAMMABLE CONTROLLER TX RX FBs CB25 FBS CB25 z 1 Ethernet port LINK CONTROLLER PROGRAMMABLE RX TX ETHERNET FBS...

Страница 23: ...BLE CONTROLLER II0 VI0 VI1 II2 VI3 VI2 FBS B4AD z 2 channel D A analog output board Gnd IO1 CONTROLLER VO1 IO0 VO0 PROGRAMMABLE FBS B2DA z 2 channel A D analog input 1 channel D A analog output board...

Страница 24: ...ent top cover as shown in the figure 4 4 80 60 90 PROGRAMMABLE CONTROLLER 2 4 5 90 7 5 2 Outlook II Main Unit FBS 20M FBS 24M FBS 32M FBS 40M FBS 60M Expansion Module FBS 24XY FBS 40XY FBS 60XY FBS 16...

Страница 25: ...24YJ FBS 32DGI Modules 1 and 2 have the same type of base with different top cover Top cover of Module 1 is shown in the following figure 2 4 5 90 20 3 8 21 40 80 90 7 5 4 Outlook IV Communication Mod...

Страница 26: ...H1 23 5 Outlook V Programming Panel FP 08 4 4 53 25 55 5 32 90 188 6 Outlook VI Data Access Panel FB DAP 98 112 148 7 7 14 8 12 17 6 14 75 22 43 9 98 6 5 units mm...

Страница 27: ...B4 0 4R DBAN 8 4R DBAN2 3 4R 3 2 8 8 7 5 08 41 27 5 08 5 6 4 3 2 5 08 1 41 91 31 75 5 08 102 86 10 16 41 27 DB 56 8R 3 2 8 5 08 68 9 10 16 158 12 68 9 5 08 48 26 38 1 5 08 5 08 1 2 3 4 5 6 7 8 DB 8 8R...

Страница 28: ...92 4 6 6 78 53 12 98 78 18 3 2 1 364 46 12 98 78 18 12 98 4 64 78 63 6 DB4 0 4R 2 97 33 91 5 08 79 8 6 03 33 90 48 26 38 1 5 08 DBAN 8 4R 37 85 192 02 10 16 37 85 10 16 37 85 5 08 91 44 37 85 10 16 82...

Страница 29: ...14MA MC FBS 20MA MC FBS 24MA MC FBS 32MA MC FBS 40MA MC FBS 60MA MC FBS 20MN FBS 32MN FBS 44MN FBS 24XY FBS 40XY FBS 60XY FBS 8XY FBS 8X FBS 8Y FBS 16XY FBS 16Y FBS 20X FBS 24X FBS 24YT FBS 24YJ Serve...

Страница 30: ...bus master slave protocol or any user defined protocol This functionality easily renders the connections with intelligent peripherals such as electronic scale bar code reader and various meters and ga...

Страница 31: ...evel computer or other systems with this architecture the FBs PLC is playing the Slave role FBs PLC supports the FATEK and Modbus protocol Connection can be established as long as the upper level comp...

Страница 32: ...the ERR LED and put the error code in Y0 Y3 LED refer the page 8 2 Chapter 8 The corresponding error code will also be indicated in the CPU status register R4049 Warning 1 The maximum length of the I...

Страница 33: ...I O numbers on main units The number of a terminal only represents its order on the expansion unit module For example the first contact is X1 or Y1 the second X2 or Y2 etc All numbers on the expansio...

Страница 34: ...user friendly BCD number signal Either the magnitude of voltage or current or the value of BCD number is represented by the 16 bit value of the corresponding register The corresponding current voltage...

Страница 35: ...e starts from the first expansion unit module main unit itself does not have any NI O The first NI channel corresponds to the first IR register R3840 Adding R3840 with the number of IR used by the fir...

Страница 36: ...operation the FBs PLC will read the CH input values from the NI module and stores them into corresponding IR R3804 R3903 and outputs OR values R3904 R3967 to channels on the NO module No pre configur...

Страница 37: ...onnector The labels of communication ports are marked on the cover plate of communication boards and modules from which users can easily identify each port Except that the built in communication port...

Страница 38: ...installed to keep from noise sources such as high voltage or high current lines and high power switches Other precautions are 4 2 1 Placement of PLC Fixation of FBS PLC which can be fixed by DIN RAIL...

Страница 39: ...C6 Y9 Y8 9 7 3 6 5 2 I Y6 FBs 24MCR2 AC FBs 24MCR2 AC Heat ventilation Hanged On floor Vertical with front facing out Horizontal 4 2 2 Ventilation Space The heat in FBS PLC is ventilated via air circu...

Страница 40: ...l the upper edge of DIN RAIL groove on PLC back touches the upper tab of DIN RAIL Then use this locked in point as a pivot to press the PLC forward on the bottom and lock it in position The procedure...

Страница 41: ...itions and sizes of screw holes in various models of FBS PLC are illustrated in the following A 60mm 2 362in 90mm 3 543in 21mm 0 827in 4mm 0 157in 2 4 5 mm 0 177 in B 90mm 3 543in 90mm 3 543in 4mm 0 1...

Страница 42: ...21mm 0 827in 1750mm 6 890in 2 4 5 mm 0 177 in D E 90mm 3 543in 21mm 0 827in 40mm 1 575in 20mm 0 787in 3 8mm 0 150in 2 4 5 mm 0 177 in F 25mm 0 984in 90mm 3 543in 21mm 0 827in 2 4 5 mm 0 177 in 3 8mm...

Страница 43: ...ires are preferred It is advised that the length of I O wiring does not exceed 100m 10m for high speed input 4 Input wiring should be separated from output or power wiring at least 30 50mm apart In ca...

Страница 44: ...herals 5 1 Specifications and Wiring of AC Power Sourced Power Supply The available AC power supplies of FBS PLC are the 14 Watt SPW14 AC supply for 10 14 PTs main unit the 24 Watt SPW24 AC supply for...

Страница 45: ...n unit FBS M SW Input CPU 0V 5V 24V 0V AC DC Power Supply F 24V OUT OR 24VDC output for Input Sensor FBS 6AD 2DA 6TC 6RTD 24VDC external power Expansion module Expansion unit Output Output FBS XY AC c...

Страница 46: ...diagram of DC power supply in main expansion unit is shown below Also be cautious about the following Please follow the wiring schemes regulated by local national standards to choose single pole swit...

Страница 47: ...y Model Output Power 5VDC logic circuit 24VDC output circuit 24VDC input circuit output communication block or expansion cable output expansion cable output terminal block AC P O W E R Main Unit FBS 1...

Страница 48: ...tion will cause a voltage drop by overloading the power supply or intermittent powered with the supply in protection mode either of which will result in unexpected action of PLC and cause harm to peop...

Страница 49: ...FBS CM5H 135 mA Others FBs BDAP 47 mA FBs BPEP 58 mA FBS DAPB 75 mA FBS DAPC 193 mA FP 08 125 mA z The above table lists the required current for the maximum consumption in each expansion module The...

Страница 50: ...DC logic power supply 325 124 136 65 OK External 24VDC Sensor power supply 295 162 53 80 OK Result 1 First calculate current consumption of internal 5VDC logic power supply 722mA 120mA 223mA 119mA 40m...

Страница 51: ...External 24VDC Sensor power supply 295 162 53 80 OK 250 250 OK Result 1 First calculate the current consumption of expansion modules which provided from the main unit current consumption of internal...

Страница 52: ...or the same power but different switches or external power supply is used for expansion modules time sequence of both powers should be considered To solve the problem of the expansion unit module powe...

Страница 53: ...urrent 20mA 10 5mA 7 6mA 4 5 mA Input Status Indication Displayed by LED Lit when ON dark when OFF Isolation Type Photocoupler signal isolation SINK SOURCE Wiring Independent Wiring Via variation of i...

Страница 54: ...e 24VDC single end SINK or SOURCE input by connecting a 3K 0 5W resistor in series as shown in the figure below A Wiring of 5VDC differential input for Line Driver driving with frequency up to 920KHz...

Страница 55: ...nd called the external common wire while the other ends of input circuits are connected to the input terminals X0 X1 X2 etc of PLC Then finish it by connecting the external common wiring and internal...

Страница 56: ...SOURCE is distinct At the right side of terminal block of FBS PLC there is a place for making SINK or SOURCE label Warning No over current protection is available in the FBS series PLC Except for the...

Страница 57: ...ction N A Isolation Type Photocoupler Isolation 500VAC 1 minute Electromagnetic Isolation 1500VAC 1 minute SINK SOURCE Output Type Independent Dual Terminals for arbitrary connection Choose SINK SOURC...

Страница 58: ...int Combination of any output common with its individual single end outputs are called a Common Output Block which is available in 2 4 and 8PTs high density module in FBS PLC Each Common Output Block...

Страница 59: ...ring of Single End Transistor SINK and SOURCE Output Circuit A Transistor Single End SINK Output 1A FUSE 2A FUSE FBS PLC C2 Y2 Y3 C4 Y4 Y5 Y6 Y7 Contact Current A Times of Action ten thousand AC DC po...

Страница 60: ...s in structural and wiring for SINK and SOURCE output circuits respectively 8PTs common has the same block structure and wiring except with different point number The single end SINK output and SOURCE...

Страница 61: ...omponents The effect of surge currents or counter electromotive force voltages is particularly serious when heavy capacitive or inductive loads are incorporated which may cause damage to the output co...

Страница 62: ...hematic diagrams for AC and DC powers are shown below respectively R C R R 100 120 C 0 1 0 24uF PLC Relay output Inductive load Scheme of AC power load R D 1N4001 diode or equivalent device PLC Relay...

Страница 63: ...high power or frequent ON OFF please construct another suppression circuit to lower noise interference and prevent voltage from exceeding the limit or overheating that may damage the transistor outpu...

Страница 64: ...age to the output circuit 8 2 Test Run and Monitoring The FBS PLC provides a convenient feature to Disable Enable the I O points by whole or individually Namely while PLC performs the normal logic sca...

Страница 65: ...enter into Run state or switch from RUN to STOP state it has to be done through the programmer FP 08 or WINPROLADDER Once PLC is set to RUN or STOP it will keep that state even after power off The onl...

Страница 66: ...eplying by looking at the these two indicators The currents in these two LED are constant and their lighting duration is proportional to the reception or transmission time The more received transmitte...

Страница 67: ...till not functioning well to local distributors 8 5 The Charge of Battery Recycle of Used Battery Every FBs PLC main units have inside one re chargeable lithium battery to safely maintain program and...

Отзывы: