![FATEK FBs Series Скачать руководство пользователя страница 11](http://html2.mh-extra.com/html/fatek/fbs-series/fbs-series_user-manual_3618161011.webp)
H 1 - 8
1.5
Specifications of Main Unit
Item
Specification
Note
Execution Speed
0.33uS
/
per Sequence Command
Space of Control Program
20K Words
Program Memory
FLASH ROM or SRAM
+
Lithium battery for Back-up
Sequence Command
36
Application Command
326 (126 types)
Include Derived Commands
Flow Chart (SFC) Command
4
Single Point
︽
BIT
S
tatus
︾
X Output
Contact(DI)
X0
~
X255 (256)
Corresponding to External Digital Input
Point
Y Output
Relay(DO)
Y0
~
Y255 (256)
Corresponding to External Digital Output
Point
TR Temporary
Relay
TR0
~
TR39 (40)
M
Internal Relay
Non-retentive
M0
~
M799 (800)*
Can be configured as retentive type
M1400
~
M1911 (512)
Retentive M800
~
M1399 (600)*
Can be configured as non-retentive type
Special Relay
M1912
~
M2001 (90)
S Step
Relay
Non-retentive S0
~
S499 (500)*
S20~S499 can be configured as
retentive type
Retentive S500
~
S999 (500)*
Can be configured as non-retentive type
T
Timer ”Time Up” Status Contact
T0
~
T255 (256)
C
Counter ”Count Up” Status Contact C0
~
C255 (256)
Register
︽
WORD Dat
a
︾
TMR
Current
Time
Value
Register
0.01S Time base
T0
~
T49 (50)*
T0 ~ T255 Numbers for each time base
can be flexibly adjusted.
0.1S Time base
T50
~
T199 (150)*
1STime base
T200
~
T255 (56)*
CTR
Current
Counter
Value
Register
Retentive C0
~
C139 (140)*
Can be configured as non-retentive type
Non-retentive C140
~
C199 (60)*
Can be configured as retentive type
32-Bit
Retentive C200
~
C239 (40)*
Can be configured as non-retentive type
Non-retentive C240
~
C255 (16)*
Can be configured as retentive type
HR
DR
Data Register
Retentive
R0
~
R2999 (3000)*
Can be configured as non-retentive type
D0
~
D3999 (4000)
Non-retentive R3000
~
R3839 (840)*
Can be configured as retentive type
HR
ROR
Retentive R5000
~
R8071 (3072)*
When not configured as ROR, it can
serve as normal register (for read/Write)
Read-only
Register
R5000
~
R8071 can be configured as ROR,
default setting is (0)*
ROR is stored in special ROR area and
not consume program space
File Register F0
~
F8191 (8192)*
Must save/retrieved via special
commands
IR Input
register
R3840
~
R3903 (64)
Corresponding to external numeric input
OR Output
Register
R3904
~
R3967 (64)
Corresponding to external numeric
output
SR Special System Register
R3968
~
R4167 (197) R4000
~
R4095 (96)
^
S
pecial Regist
er
﹀
0.1mSHigh Speed Timer register R4152
~
R4154 (3)
High Speed
Counter
Register
Hardware(4 sets) DR4096
~
DR4110 (4
×
4)
Software (4 sets) DR4112
~
DR4126 (4
×
4)
Real Time Calendar Register
(Not available in MA model)
R4128 (sec) R4128 (min) R4130 (hour) R4131 (day)
Optional for MA module
R4132
(month)
R4133 (year) R4134 (week)
XR Index
Register
V
、
Z (2), P0
~
P9 (10)
Interrupt
Control
External Interrupt Control
32 (16 point input positive/negative edges)
Internal Interrupt Control
8 (1, 2 3, 4, 5, 10, 50, 100mS)
0.1mS High Speed Timer (HST)
1 (16bits), 4 (32bits, derived from HHSC)
16-Bit