Input Range: -2.5 ~ 2.5[V] 

9.2.3 

When the Input Range value is 2, the range of analog input is -2.5 ~ 2.5[V] in Voltage Input Mode. The analog 
input signals are converted to digit data -4096 ~ 4095 (Full Scale). If the input signal is out of range, it is 
converted to the minimum or maximum data. 
Every 1[V] of the analog signal is converted to 1638.4 digital data data (After the conversion, the decimal places 
are removed). 
 
 

 

Table 9-5. Data Conversion for Input Range -2.5 ~ 2.5[V] 

 

 

Figure 9-3. Data Conversion for Input Range -2.5 ~ 2.5[V] 

 

Input Range 

Converted Data 

2 (-2.5 ~ 2.5[V]) 

-4096 ~ 4095 (-2.5 ~ 2.5[V]) 

Содержание Ezi-IO-EC-AD08-T

Страница 1: ...User Manual...

Страница 2: ...m Configuration 12 Ezi IO EC AD08 T 12 3 3 1 Connection Panel View 13 Chapter 4 4 1 Names and Functions Ezi IO EC AD08 T 13 EtherCAT ID Setting Switches SW1 SW2 14 4 1 1 Input Mode Voltage Current Sel...

Страница 3: ...g 23 PDO Mapping 23 7 2 1 PDO Assign 24 7 2 2 7 3 EtherCAT Communication Status 24 EtherCAT State Machine 24 7 3 1 EtherCAT Communication Status Indication 25 7 3 2 7 4 Synchronization 26 Free Run 26...

Страница 4: ...42 10 2 4 Object 100Ah Software Version 42 10 2 5 Object 1011h Restore Default Parameters 42 10 2 6 Object 1018h Identity 42 10 2 7 Object 10F1h Error Setting 43 10 2 8 10 3 PDO Mapping Object 44 Obj...

Страница 5: ...damaged or lost please contact FASTECH or our agents You can find our contact information on the last page of this manual FASTECH is not responsible for a product breakdown due to the user s dismantl...

Страница 6: ...eration Checking and Repairing should be done by a qualified personnel Otherwise a fire or other kinds of accidents may occur Cable Connection Keep the rated range of input voltage for the drive Other...

Страница 7: ...shock may occur or the product and machine get damaged And the reconstructed product cannot get after service 1 3 Notes on Installation This product has been designed for indoor use Use the product i...

Страница 8: ...witch 0 99 Physical Address Setting in Master Unit 1 65535 Topology Line Configured by I O modules only Tree Star Ring When using a switching hub Protocol CoE CANopen application protocol over EtherCA...

Страница 9: ...nput Range Setting Method SDO Communications Separate setting for CH1 8 DIP Switch Separate setting for CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Input Impedance 1M 249 Resolution 13bit Measuring Error 25 0 3 F...

Страница 10: ...10 2 3 Module Dimensions Ezi IO EC AD08 T Unit mm Can be installed on 35mm DIN Rail...

Страница 11: ...11 Configuration Chapter 3 3 1 Ezi IO EtherCAT AD Part Numbering 3 2 Ezi IO EtherCAT AD Part Number...

Страница 12: ...12 3 3 System Configuration Ezi IO EC AD08 T 3 3 1...

Страница 13: ...13 Connection Panel View Chapter 4 4 1 Names and Functions Ezi IO EC AD08 T...

Страница 14: ...y switches is applied when the power is supplied to the I O module Input Mode Voltage Current Selection Switch SW4 4 1 2 Select either Voltage or Current Input Mode for each channel with SW4 referring...

Страница 15: ...ng method SW3 1 ON select voltage input range referring to the chart Selecting Voltage Input Range CH1 CH2 CH3 CH4 SW3 3 SW3 4 SW3 5 SW3 6 Input Voltage Range 10 10V OFF OFF OFF OFF 5 5V OFF ON OFF ON...

Страница 16: ...mmunication Status Indication LED Color Status Description ERR Red OFF No Error or Power OFF Blinking Invalid Configuration Single Flash Local Error Double Flash Watchdog Time Out Refer to 7 3 2 Ether...

Страница 17: ...GND Input 2 GND Input 3 Analog In 1 Input 4 Analog In 2 Input 5 Analog In 3 Input 6 Analog In 4 Input 7 Analog In 5 Input 8 Analog In 6 Input 9 Analog In 7 Input 10 Analog In 8 Input 11 GND Input 12 G...

Страница 18: ...t suitable model for Ezi IO EtherCAT AD Another equivalent connector can be used Part Number Cable Length m Remarks CGNR EC 001F 1 STP Shielded Twisted Pair cable Category 5e or higher Maximum cable l...

Страница 19: ...alog devices to Ezi IO EtherCAT AD are also simplified 5 1 Signal Wiring Ezi IO EC AD08 T Ezi IO EtherCAT AD has one terminal block which has 8 input pins Users can connect up to 8 analog input signal...

Страница 20: ...plying power to the module Connect the analog input signal and ground to the pin 2 and GND of Input Connector CN2 Figure 6 1 Setting Voltage Input Mode through SDO Communication Setting Voltage Input...

Страница 21: ...ation for setting method SW3 1 OFF Example Setting Channel 2 Set LSET switch SW3 1 of INPUT RANGE to OFF before supplying power to the module Set Channel 2 to Current Input Mode with the Input Mode Se...

Страница 22: ...of data objects which are saved in an EtherCAT slave unit EtherCAT masters can read and write data through the index or sub index of objects Mailbox Communication 7 1 2 In the Mailbox SDO communicatio...

Страница 23: ...which transmits the analog input data to the master and is used when the Ezi IO EtherCAT AD is in Operational or Safe Operational status Figure 7 2 EtherCAT PDO Communication 7 2 PDO Mapping Through...

Страница 24: ...e FoE File over EtherCAT It is an EtherCAT slave node through which the product firmware can be updated State SDO Tx PDO Description INIT Disabled Disabled EtherCAT communication is initialized Commun...

Страница 25: ...te ON OPERATIONAL State Flickering BOOTSTRAP State Table 7 2 EtherCAT Communication Status LED The ERR LED indicates operational errors of the product LED Color Status Description ERR Red OFF No Error...

Страница 26: ...r SM Event of EtherCAT communication SM Event occurs when an EtherCAT Frame is received by the module and each SM Event synchronized module has a range of jitter in s or less DC Sync Event 7 4 3 The I...

Страница 27: ...T setting device 7 6 EtherCAT Device ID To use the EtherCAT Network you must configure a master and all slaves The master must assign the EtherCAT Device IDs to the slaves to identify them and to send...

Страница 28: ...check the following Check the power status LED PWR turns Red After connecting the communication check EtherCAT Link Activity LED LA IN LA OUT turns Green Activate EtherCAT communication Check the Ethe...

Страница 29: ...ck OK If no device is found on the new I O devices founds window check the power and cable connection for the product and try again When Scan for boxes pops up click Yes Make sure a device or box is a...

Страница 30: ...el On Off function and converts analog input signals to digital data Change in Channel On Off for each channel is updated after the reboot Channel On Off Value Description 0 Channel Off The channel is...

Страница 31: ...put range for each channel before supplying power to the module Value Input Range Input Mode 0 10 10V Voltage 1 5 5V 2 2 5 2 5V 3 0 10V 4 0 20mA Current Table 9 2 Input Range Input Range 10 10 V 9 2 1...

Страница 32: ...96 4095 Full Scale If the input signal is out of range it is converted to the minimum or maximum data Every 1 V of the analog signal is converted to 819 2 digital data data After the conversion the de...

Страница 33: ...95 Full Scale If the input signal is out of range it is converted to the minimum or maximum data Every 1 V of the analog signal is converted to 1638 4 digital data data After the conversion the decima...

Страница 34: ...0 8191 Full Scale If the input signal is out of range it is converted to the minimum or maximum data Every 1 V of the analog signal is converted to 819 2 digital data data After the conversion the dec...

Страница 35: ...rted to 409 6 digital data data After the conversion the decimal places are removed Turn OFF the Input Range Setting Switch SW3 1 before supplying power to the module Setting by SDO communication Sele...

Страница 36: ...lter Buffer Length Time Range of Filter 0 0ms 100 20ms 200 40ms 300 60ms 400 80ms 500 100ms Table 9 8 Time Range of Moving Average Filter example The Moving Average Filter is set for each channel Each...

Страница 37: ...nction does not work 9 4 Setting ADC Offset The ADC Offset function is set by Object 220x 04h The deviation of voltage and current input data which is caused by installing or device conditions can be...

Страница 38: ...0 RO Ezi IO EtherCAT AD08 Index and Sub Index 10 1 1 The following areas are assigned with Object Index of four digit hexadecimal numbers as shown in Table 10 1 Index Area Description 0000h 0FFFh Data...

Страница 39: ...ly Variables for read only RW Read Write Variables for read or write Table 10 3 Access Type of Object SAVE 10 1 5 The Object values are automatically saved in EEPROM PDO Mapping 10 1 6 Indicates wheth...

Страница 40: ...indicates the range of input signal stored in the Object The range can have a random range or a range of Data Type Default Value 10 1 9 Default value of the Object Restores the default values using th...

Страница 41: ...ect 1001h Error Register 10 2 2 Index Sub Index Name Type Access SAVE PDO Mapping Value Range Default Value 1001h 0 Error Register U8 RO No No 00h This Object indicates types of error that occurred in...

Страница 42: ...lue 1011h 0 Number of Entries U8 RO No No 1 1 Restore Default Parameters U32 RW No No It commands that the Object values saved in EEPROM are restored with default values To reset the Objects with the...

Страница 43: ...ting 10 2 8 Index Sub Index Name Type Access SAVE PDO Mapping Value Range Default Value 10F1h 0 Number of Entries U8 RO No No 2 1 Local Error Reaction U32 RO No No 0000 0000h 2 Sync Error Counter Limi...

Страница 44: ...PDO Object U32 RW Yes No 0000 0000h 32 32th PDO Object U32 RW Yes No 0000 0000h This Object indicates the TxPDO Map setting Read Analogue Input 16bit 6401h Object is mapped TxPDO Map is not changeable...

Страница 45: ...h SM Output Parameter 10 4 2 Index Sub Index Name Type Access SAVE PDO Mapping Value Range Default Value 1C32h 0 Number of Entries U8 RO No No 32 1 Synchronization Type U16 RW No No 0002h 2 Cycle Time...

Страница 46: ...cle Time U32 RO No No 0000 0000h 4 Synchronization Type Supported U16 RO No No 401Fh 5 Minimum Cycle Time U32 RO No No 0003 D090h 6 Calc And Copy Time U32 RO No No 0000 2710h 8 Get Cycle Time U16 RW N...

Страница 47: ...RO No Tx PDO 0 2 Analog Input CH2 I16 RO No Tx PDO 0 3 Analog Input CH3 I16 RO No Tx PDO 0 4 Analog Input CH4 I16 RO No Tx PDO 0 5 Analog Input CH5 I16 RO No Tx PDO 0 6 Analog Input CH6 I16 RO No Tx P...

Страница 48: ...or the channel Value Description 0 The channel is Off 1 The channel is On Table 10 9 Channel On Off Value With the Input Range value select the input range of analog voltage or current Refer to Table...

Страница 49: ...hange without prior notice due to product improvement change in specifications etc Ezi IO EtherCAT AD is a trademark of FASTECH Co Ltd registered in Korea Copyright 2021 FASTECH Co Ltd Mar 25 2021 Rev...

Отзывы: