37
Set temperature difference between temperature set
point and actual temperature reading before 1st stage
heating or cooling is initiated.
38
Set temperature difference between 1st stage
initiation (37) and 2nd stage heating or cooling
initiation.
37
38
39
40
35
Set maximum compressor cycles per hour.
36
Set Minimum difference between auto mode heat and
cool temperature set points. See 14.
39
Set temperature difference between 2nd stage
initiation (38) and 3rd stage heating or cooling
initiation.
NOTE: Number of stages depends on your system;
see 33
& 34.
40
Reverses the Heat Pump OB Valve contact;
(manufacturer dependant)
34
36
33
35
33
Select system heating and/or cooling equipment:
Heat Pump, 2-stage Heat Pump, Air Conditioning, No
Compressor – see Wiring Diagram.
34
Select the system Furnace Type:
Furnace Off (No Furnace), Electric Furnace, Emergency
Electrical Furnace (additional electric furnace which
will come on in emergency mode in conjunction with
electric furnace), Gas Furnace, Oil Furnace, and 2-stage
Gas Furnace; see Wiring Diagram.
ADVANCED SETTINGS
PAGE 2
ADVANCED SETTINGS
PAGE 3
PLEASE NOTE THAT INADVERTENTLY
MODIFYING COMPRESSOR AND
FURNACE SETTINGS, MAY SERIOUSLY
DEGRADE SYSTEM PERFORMANCE.