General Information
Installation instructions Sauna control Series FCUxx00 / Version V 2.27
37
8.6
Light and fan
Light and fan
ATTENTION!
Light and fan:
9
At the dimmable outputs of light and fan, only 230V consumer, or
for low voltage iron core transformer which are suitable for phase cut
on
, will be permitted.
Electronic transformer for phase cut
off
may
not
be connected.
9.1.1
Disable light brightness or fan speed, or exchange triac
ATTENTION
DANGER!
Danger to life due to electric potential!
Before starting any maintenance jobs, the control unit must be
separated from the mains at all poles!
If light and/or fan are not suitable for phase cut
on
, you
can disable this feature.
Fan speed (clamp 1) enabled
Fan speed disabled, only ON/OFF
Light dimming (clamp 3) enabled
Light dimming disabled, only ON/OFF
The jumpers are located only on one side of the pins (as in
the picture above) or they are in the by-pack kit of the
control unit.
Disable user menu for fan speed / light-brightness per “DIP
switch
S1
”
DIP 4=ON, menu fan speed disabled
DIP 5=ON, menu light brightness disabled
If the light dimming no longer works trough a defect in the bulb, then the triac „Tri2“ and possibly the fuse
„Si2“ are blown. When replacing the triac (1 spare part is included in the by-pack kit), set the new component
in correct position (mark metal flag) into the socket. Make sure that all pins are properly in the socket and
then press gently.
If the fan control have been destroyed by a defect, the same applies for triac „Tri1“.
10
ATTENTION!
11
Note ESD protection!
Do not touch on electrical parts because of ESD protection
Take appropriate protections. Touch a grounded piece of metal as a
minimum protection.