WARNINGS: 

 

  Always connect the device to ground  

  Do not swap the DIN connectors.  If a connector requires excessive force check 

that they are not swapped. 

  To maintain the IP65 protection level of the DIN connectors follow the following 

recommendations: 

o

  Disconnect and lock out power to the controller. 

o

  Allow 10 seconds for the capacitors to discharge. 

o

  The DIN PG9 compression fitting is designed for 6 to 8 mm (1/4” to 5/16”) 

cable. 

o

  Cable ends and outer insulator must be fully inserted into compression 

fitting. 

o

  Cable wires should be securely fastened to screw terminals. 

o

  Make sure the ground is connected correctly for this circuit extends to the 

brass bodies of the solenoid valves. 

o

  Make sure the DIN gasket is installed correctly. 

o

  The screw on the connectors cap should be the original or an exact 

equivalent. 

  

SPECIAL WARNINGS FOR ATEX NORMATIVE 

 

For the use of this device in a zone where a potentially explosive atmosphere 

could be created due to combustible dust. 

 

Precautions to be taken to avoid the activation of certain ignition sources: 

  The plant designer, the installer and the final user must verify that the maximum surface 

temperature declared for this device (90°C) is less than 2/3 of the minimum ignition 
temperature for the type of dust found in the plant which can cause a potentially 
explosive atmosphere. 

  It is necessary to take protective measures against lightning strikes in the plant where 

this device is installed. It is necessary to protect the device against stray electrical 
currents coming from lightning strikes near where this device is installed 

  Any accessory (electrical or not electrical) applied by the user to this product, must 

conform to the directive 94/9/EC and must have classification CE – Ex compatible. 
Moreover any such accessory must be installed in compliance with the instructions given 
by its manufacturer/supplier.  

Installation 

  During the mounting of this device, be careful not to damage any internal components of 

whatever it is being mounted to. 

  During the mounting of this device in a dangerous zone, it is necessary to prevent the 

formation of sparks due to the rubbing of oxidizable substances like iron or steel. 

  During the installation phase this equipment must be grounded by means of a electrical 

connection. All of the external metallic components will then be grounded. 

  The cables for the power-supply, for the output relay contacts and for the other 

input/output connections must be installed by the user by means of suitable entry 

Содержание camfil STR2

Страница 1: ...ed Dust Collector and Solenoid Controller Model STR2 6 and Model STR2 6 A22 User s Manual Installation Operation and Maintenance Certified ATEX Zone 2 and 22 II 3D Ex mD IP65 A22 T 90 Deg C II 3G Ex mb IP65 T5 ...

Страница 2: ...RISTICS 5 FUNCTIONAL CHARACTERISTICS 5 OPERAION 6 ACCESSING CONTROLS AND REGULATORS 7 ELECTRICAL CONNECTIONS 9 SPECIAL WARNINGS FOR ATEX NORMATIVE 10 Precautions to be taken to avoid that certain ignition sources become active 10 Installation 10 Maintenance 11 Use 11 ...

Страница 3: ... of the timing functions are adjusted with potentiometers which are accessed by removing a clear Lexan cover Electrical connections consist of a power connection and a two wire connection to the control This controller will also operate in on demand mode when connected to a photohelic differential pressure switch An input is provided to initiate a post shutdown cleaning of five pulses per filter T...

Страница 4: ... s r l is equipped with a CE ATEX certificate of conformity with this manual and a nameplate conforming to the 94 9 EC directive that carries the ATEXmark The marking of this instrument is II 3D Ex mD IP65 A22 T 90 C II 3G Ex mb IP65 T5 Simplifying we can say that this mark means that this device has been designed to operate in a potentially explosive atmosphere caused by combustible dusts D dust ...

Страница 5: ...Dimensions Length 12 2 310 mm Width 2 6 65 mm Height 5 1 130 mm Fuses 24 Vdc ac 2A delayed thermal fuse 90 240 Vac 0 5A delayed thermal fuse Functional Characteristics Off Time 15 to 210 seconds in 15 second increments 4 seconds for special purposes 1 second for test purposes see dip switch settings On Time 80 to 650 milliseconds Input for shut down cleaning Close contact to initiate shut down cle...

Страница 6: ...he low pressure set point is reached on the pressure gauge and the contacts are closed The shutdown cleaning cycle is activated by closing contacts 1 and 2 When closed the controller will fire all solenoids 5 times and then go dormant This contact is normally tied to the fan start up The contact must open on start up or the controller will not start The shutdown cleaning cycle can be activated or ...

Страница 7: ... voltage Unscrew the four screws and remove the window Be careful not to lose the screws gasket or the plastic window Adjust settings per the following instructions When finished clean the contacting surface of the gasket and close the transparent window being careful to properly position the gasket and firmly tighten the four screws CONTROLS DIP SWITCHES ROTATING COMMUTATOR AND TRIMMER The STR Co...

Страница 8: ...me Min 80 milliseconds Max 650 milliseconds Adjust on time so that you hear a sharp pulse similar to a shotgun blast The pulse is to long if excessive air hisses out of the valve after the initial blast Table II Off time adjustment Position Pause sec 0 15 1 20 2 25 3 30 4 35 5 44 6 52 7 60 8 75 9 88 A 100 B 118 C 148 D 175 E 210 F 4 ...

Страница 9: ...rom the control DIN connector and avoid interchanging of the connectors The controller contains a bridge rectifier and will accept AC or DC voltage The device is not polarized so DC voltage positive and negative lines can be connected to either L or N terminals The control DIN connector is grey It contains four terminals where 1 and 2 are used for the shutdown sequence activation and 3 and 4 are u...

Страница 10: ...erature declared for this device 90 C is less than 2 3 of the minimum ignition temperature for the type of dust found in the plant which can cause a potentially explosive atmosphere It is necessary to take protective measures against lightning strikes in the plant where this device is installed It is necessary to protect the device against stray electrical currents coming from lightning strikes ne...

Страница 11: ... material e g RILSAN are present in the equipment in order to measure the pressure inside it or in order to carry compressed air to a solenoid valve those tubes can be a source of static electricity therefore rubbing of the tubes must be avoided The plant designer and the final user must check that no excessive adiabatic air compression takes place in the inside of the ducts connected to this devi...