- 69 -
INSTRUCTIONS FOR CONVERSION
(3) With the unit still running, set "DIP Switch" No. 6 to ON position to set the combustion at a
maximum capacity level. At this time, a substantial amount of water should be supplied.
"Multiple faucets should be opened to prevent water from boiling, as the maximum capacity
is forced, if the water temperature is high, the heated water may reach its boiling point."
(4) Set the gas pressure for the maximum capacity level by turning the maximum gas adjusting
control knob under the minimum gas adjusting control knob. Then, set the "DIP Switch" No.
6 to OFF.
(5) Shut the hot water supply valve. Open the valve again for combustion. Repeat steps 2 and
4 to check that the settings are correct.
(6) Shut the hot water supply valve to stop combustion. Disconnect the rubber hose of the
manometer from the pressure check fitting. Seal the hole by installing and tightening the
screw.
(7) Restart the unit with full water supply and check for any gas leakage at the pressure check
screw and around the gas manifold itself. If the gas pressure inlet screw was removed and
reinstalled, it should also be leak tested.
Step 6:
Remark the gas type label on the upper left hand side of the cabinet with the new gas type.
Reinstall the front cover with its four screws.
Nozzle pressure
Min.
Max.
Maximum gas adjusting control knob
Minimum gas adjusting control knob
Rubber Tubing
Threaded Hose Fitting
Dip Switch