Section V Compatible Devices
V-4
P/N 446613 Issue I Rev. A
UL Compatible Four-Wire (Separately Powered) Smoke & Heat Detectors
Faraday
Detector
w/Base
Mfg. Detector
w/Base
Maximum
Standby
Current
Maximum
Alarm
Current
Notes
Air Products & Controls
9269
RW-DC-N
0.081mA
115mA
Must use EOL Relay
9270
RW-DC-P
0.110mA
115mA
Must use EOL Relay
Apollo Fire Detectors Limited
9259 w/9266
55000-150 w/45681-227
0.073mA
100mA
Must use EOL Relay
9221 w/9266
55000-151 w/45681-227
0.073mA
100mA
Must use EOL Relay
9274 w/9266
55000-152 w/45681-227
0.073mA
100mA
Must use EOL Relay
9264 w/9266
55000-153 w/45681-227
0.073mA
100mA
Must use EOL Relay
9261 w/9266
55000-250 w/45681-227
0.060mA
100mA
Must use EOL Relay
9260 w/9266
55000-350 w/45681-227
0.125mA
100mA
Must use EOL Relay
9222 w/9266
55000-380 w/45681-227
0.200mA
100mA
Must use EOL Relay
System Sensor,
9377
1424
0.100mA
41mA
Must use EOL Relay
9378
2424
0.120mA
41mA
Must use EOL Relay
9379
2424TH
0.120mA
41mA
Must use EOL Relay
9337
1112/24
0.050mA
25mA
Must use EOL Relay
9338
2112/24
0.050mA
25mA
Must use EOL Relay
9339
2112/24T
0.050mA
25mA
Must use EOL Relay
9340
2112/24TSRB
15mA
45mA
Must use EOL Relay
9358 w/9362
1451 w/B402B
0.120mA
41mA
Must use EOL Relay
9359 w/9362
2451 w/B402B
0.120mA
41mA
Must use EOL Relay
9360 w/9362
2451TH w/B402B
0.120mA
41mA
Must use EOL Relay
9447 w/9362
5451 w/B402B
0.120mA
41mA
Must use EOL Relay
9421 w/9362
4451HT w/B402B
0.120mA
41mA
Must use EOL Relay
9164
DH400ACDCI
25mA
110mA
Must use 6 wires
9165
DH400ACDCP
25mA
110mA
Must use 6 wires
9175
6424
10mA
28.4mA
Must use EOL Relay and 6
wires
Contact Type Heat Detectors
Faraday
Cat. No.
Mfg. Part
Number
Chemetron
9341
601
9342
602
9343
603
9344
604
9345
621
9346
622
9347
623
9348
624
9300-136
A-135
9300-190
A-200
9301-136
AT-135
9301-190
AT-200
PM2872-136
EPB501
PM2872-190
EPB502
PM2872-136F
EPB503
PM2872-190F
EPB504
Faraday
8858
8858
8859
8859
Notes:
1. Any U.L. Listed contact type heat detector with compatible contact
ratings is acceptable. The list to the left is provided for your
convenience.
2. For specific wiring and installation information, read the
instructions provided with each device.
Notes:
1. For specific wiring and installation information, read the
instructions provided with each device.
2.
Each 9273 EOL Relay requires 15 mA standby current.