P/N 315-049475FA-5

PAGE 2 OF 4

MOUNTING

(Refer to Figure 4) Addressable Interface Models 8702, 8703, and 8704 mount directly into a (user sup-
plied) double gang or 4 inch switchbox. Fasten the module to the switchbox with the switchplate using the
2 screws provided.

A red LED will blink to indicate an off-normal input switch position and/or an internal relay transfer.

NOTE:  Be sure to program the module before fastening the switchplate to the unit.

WIRING

(Refer to Figures 7 - 9 ) Refer to the appropriate wiring diagram and wire the addressable interface module
accordingly.

NOTE:  Recommended wire size: 18 AWG minimum, 14 AWG maximum

Wire larger than 14 AWG can damage the connector.

Power Limited Wiring

In compliance with NEC Article 760, all power limited fire protective signaling conductors must be sepa-
rated a minimum of ¼ inch from all of the following items located within an outlet box:

electric light

power

Class 1 or non-power limited fire protective signaling conductors

To meet the above the requirements, the following guidelines must be observed when installing this
interface module.

NOTE:  If power limited wiring is not used within this outlet box, then these guidelines do not
apply. In that case, be sure to follow standard wiring practices.

8704 Wiring Barrier

The Wiring Barrier must be used when the 8704 relay contacts are connected to non-power limited wires.
Break apart the barrier to the correct size and shape shown in Figure 5 for either the 4-inch square or
double gang box. Install the barrier diagonally into the backbox to create two separate compartments
within the backbox to separate the wires, as shown in Figure 5.

Figure 4

8702/8703/8704 Mounting

SWITCHPLATE

5-INCHES SQUARE

(SUPPLIED)

SWITCHPLATE

5-INCHES SQUARE

(SUPPLIED)

4-INCH SQUARE BOX

2 1/8-INCHES DEEP

DOUBLE GANG BOX

3 1/2-INCHES DEEP