13400 Owner’s Manual
P/N 446613 Issue I Rev. A
V-3
Faraday
Detector
w/Base
Mfg. Detector
w/Base
Number of
Detectors Per
Circuit
Maximum
Standby
Current
Detector
Identifier
Base
Identifier
System Sensor (Cont’d)
9419
2100
0-30
0.100mA
A
---
9420
2100T
0-30
0.100mA
A
---
9358 w/9361
1451 w/B401B
0-25
0.120mA
A
A
9358 w/9364
1451 w/B401
0-25
0.120mA
A
A
9358 w/9424
1451 w/B406B
0-25
0.120mA
A
A
9359 w/9361
2451 w/B401B
0-25
0.120mA
A
A
9359 w/9364
2451 w/B401
0-25
0.120mA
A
A
9359 w/9424
2451 w/B406B
0-25
0.120mA
A
A
9360 w/9361
2451TH w/B401B
0-25
0.120mA
A
A
9360 w/9364
2451TH w/B401
0-25
0.120mA
A
A
9360 w/9424
2451TH w/B406B
0-25
0.120mA
A
A
9447 w/9361
5451 w/B401B
0-25
0.120mA
A
A
9447 w/9364
5451 w/B401
0-25
0.120mA
A
A
9447 w/9424
5451 w/B406B
0-25
0.120mA
A
A
9421 w/9361
4451HT w/B401B
0-25
0.120mA
A
A
9421 w/9364
4451HT w/B401
0-25
0.120mA
A
A
9421 w/9424
4451HT w/B406B
0-25
0.120mA
A
A
9176
DH400I (1451DH w/DH400)
0-25
0.120mA
A
A
9177
DH400P (2451 w/DH400
0-25
0.120mA
A
A
Faraday
8854 w/8853
8854 w/8853
0-27
0.110mA
8854
8853
8842 w/8853
8842 w/8853
0-27
0.110mA
8842
8853
8843 w/8853
8843 w/8853
0-27
0.110mA
8843
8853
8854 w/8840
8854 w/8840
0-27
0.110mA
8854
8840
8854 w/8853 &
8845 or 8849
8854 w/8853
& 8845 or 8849
0-27
0.110mA
8854
8853
8842 w/8853 &
8845 or 8849
8842 w/8853
& 8845 or 8849
0-27
0.110mA
8842
8853
8843 w/8853 &
8845 or 8849
8843 w/8853
& 8845 or 8849
0-27
0.110mA
8843
8853
8854 w/8840 &
8845 or 8849
8854 w/8840
& 8845 or 8849
0-27
0.110mA
8854
8840
8854 w/8853 &
8844 or 8848
8854 w/8853
& 8844 or 8848
0-13
0.220mA
8854
8853
8842 w/8853 &
8844 or 8848
8842 w/8853
& 8844 or 8848
0-13
0.220mA
8842
8853
8843 w/8853 &
8844 or 8848
8843 w/8853
& 8844 or 8848
0-13
0.220mA
8843
8853
8854 w/8840 &
8844 or 8848
8854 w/8840
& 8844 or 8848
0-13
0.220mA
8854
8840
Notes:
1. These detector models may be mixed and matched as long as the total maximum standby
current does not exceed 3.0 mA per initiating device circuit. The total number of detectors on
a circuit should not exceed 30.
2. This control unit is not intended to handle more than one 2-wire detector in alarm, per circuit.
3. The activation of a manual pull station or any other contact device, will prevent any 2-wire
detector on the same circuit from remaining activated or from activating.
4. If the smoke detector has an alarm verify function, the circuit must not be programmed for
alarm verify,
5. For specific wiring and installation information, read the instructions provided with each
device.