          FAN COIL ROOM THERMOSTAT

CH130ARR2

PARAMETER

DESCRIPTION

DEFAULT

FIELD

End

Exit the user parameters menu + save 
parameters

End

* Parameters not visible if the remote actuator CH172D is selected in parameter P50

P06  Plant type (plant)

2P  

2-PIPE

 SYSTEM: the thermostat only manages valve 

V1

 (on/off type) regardless of heating or cooling operation.

4P 

4-PIPE

 SYSTEM: the thermostat manage valve 

V1

 (on/off type) for heating and valve 

V2

 (ONE/OFF type) for cooling.

P07  Hot water valve

1  

HOT VALVE

: actuator output 

V1

 

controls the water supply valve in heating.

ELECTRICAL RESISTANCE

: actuator output 

V1

 controls an electrical resistance for heating. In this case, when the 

resistance is switched off, the fan still remains active (two minutes of post-ventilation) to enable the resistance to 
cool down. 

P08  Ventilation modes

1  

CONTINUOUS

: once the set point is reached, the fan still remains active at the manually set speed or at MIN speed 

if automatic ventilation is set.

CONTINUOUS-STOP IN WINTER MODE

: as in 1 except in heating where ventilation is switched off.

CONTINUOUS-STOP IN SUMMER MODE

: as in 1 except in cooling where ventilation is switched off.

AUXILIARY

: the fan is only enabled if the valve is enabled (heating or cooling in progress).

SUBORDINATED-STOP IN WINTER MODE:

 as in 4 except in heating where ventilation is switched off. 

SUBORDINATED-STOP IN SUMMER MODE:

 as in 4 except in cooling where ventilation is switched off.

P09  Adjustment modes

1  

SUMMER/WINTER

: the thermostat carries out temperature control according to the current mode (Summer/Winter).

AUTOMATIC

: the thermostat carries out temperature control by heating or cooling in order to obtain the best climate 

comfort (4-pipe systems only)

Note

:   when selecting option 2, the adjustment involves parameter 

P38

;

 

By selecting option 2 

SUMMER/WINTER

 mode cannot be changed manually.

P10 Anti-stratification operation

This setting is only effective if 

P11

=5 or 

P12

 = 6 (adjustment with return sensor)

1  

NOT ACTIVE

: the function is not managed.

SUMMER ONLY

: the function is only managed if the thermostat is in summer mode.

WINTER ONLY

: the function is only managed if the thermostat is in winter mode.

Note

:   if ventilation is not active for 15 straight minutes, the anti-stratification function switches on for two minutes   

ventilation at MEDIUM speed regardless of minimum sensor consent. 

P11 Temperature sensor on remote actuator sensor input

1  

NOT CONNECTED

: the input is not used.

MINIMUM SENSOR WINTER ONLY

: connecting a temperature probe to the supply pipe, the thermostat will not start 

the fan until the temperature of the water has reached the value set in item 

P33

.

SUMMER/WINTER MINIMUM SENSOR

: connecting a temperature probe to the supply pipe, the thermostat will not 

start the fan until the temperature of the water has reached the value set in item 

P33

 (winter mode) or

 P34

 (summer 

mode).

CHANGE-OVER SENSOR

: connecting a temperature probe to the supply pipe, the thermostat automatically manages 

the Winter/Summer change-over with the temperatures programmed in items 

P36

 

and 

P37

.

Содержание KIT CH130ARR2

Страница 1: ...RUCTIONS FOR USE FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milan ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it www fantinicosmi it ROOM THERMOSTAT AND ACTUATOR FOR...

Страница 2: ...speed motor or a 0 10V motor of a fan coil The thermostat reads the room temperature and controls it from the fan coil s motor valves and speed in order to obtain the best climate comfort Fan adjustme...

Страница 3: ...bles the following settings 1 and 2 Comfort Economy mode change 3 and 4 Summer Winter mode change pressing 3 sec WARNINGS KEY 1 Measured or set temperature 2 Comfort mode 3 Economy mode 4 Summer mode...

Страница 4: ...ating IP20 Degree of pollution 2 Settings memorisation non volatile memory Software Class A Temperature adjustment field 2 C 40 C Maximum temperature T45 User interface LCD display and 4 keys Dimensio...

Страница 5: ...P 8 3 2 SUMMER WINTER MODE SELECTION 8 3 3 OPERATING MODES 8 3 4 COMFORT MODE 9 3 5 ECONOMY MODE 9 3 6 OFF 9 3 7 FAN SPEED SETTING 10 4 KEY LOCK 11 4 1 TEMPORARY KEY UNLOCK 11 5 FAULTS 11 6 MAINTENANC...

Страница 6: ...polar connector Fixing hole Fixing hole Remove the top cover of the thermostat Divide the base and front of the thermostat by removing the screws with a specific tool and extracting the front part Fix...

Страница 7: ...1 and input for remote control SEL1 are subject to certain configuration parameter settings Connection of auxiliary input Connect the two auxiliary input wires to the screw terminals 1 and 2 as shown...

Страница 8: ...hange current operating mode settings simultaneously press keys 1 and 2 pressing 3 sec Note the operating mode cannot be changed if the thermostat is enabled to manage change over locally or remotely...

Страница 9: ...constant To change from Comfort to Economy simultaneously press keys 3 and 4 To check the currently set Economy temperature press key 3 or 4 To change the set Comfort temperature value repeatedly pre...

Страница 10: ...G There are three different fan speeds minimum medium and maximum The speed can be set manually by selecting one of the three speeds or automatic In AUTO the thermostat will use the most suitable fan...

Страница 11: ...Y UNLOCK When one of the disabled keys is pressed in accordance with parameter P20 the display will show Loc and below 000 will flash inviting you to enter the unlock password Confirm by pressing key...

Страница 12: ...ct the new setting and confirm by pressing 3 Once the parameter settings have been completed press 1 until the wording END appears and press 3 to confirm The thermostat will save the new parameters in...

Страница 13: ...um sensor 4 automatic change over 5 return only if P13 is other than 6 P12 Temperature sensor on external sensor input Reading frequency Once a minute Options 7 8 9 are only visible if CH172D was sele...

Страница 14: ...P33 Minimum sensor threshold in winter mode 34 0 C 28 0 C 42 0 C step 0 1 C P34 Minimum sensor threshold in summer mode 22 0 C 10 0 C 25 0 C step 0 1 C P35 Minimum sensor tripping differential 4 0 C...

Страница 15: ...ed off P09 Adjustment modes 1 SUMMER WINTER the thermostat carries out temperature control according to the current mode Summer Winter 2 AUTOMATIC the thermostat carries out temperature control by hea...

Страница 16: ...robe to the supply pipe the thermostat will not start the fan until the temperature of the water has reached the value set in item P33 winter mode or P34 summer mode 9 CHANGE OVER SENSOR connecting a...

Страница 17: ...34 Minimum sensor threshold triggered summer mode This setting is only effective if P11 2 or P11 3 or P12 7 or P12 8 When the supply temperature rises above the set value the thermostat stops ventilat...

Страница 18: ...t a single thermostat to several actuators so as to control more than one fan coil simultaneously with only two cables for this application carefully follow the detailed instructions in the document T...

Страница 19: ...disconnected before making any connections or working on the device The following figure shows the circuit diagram of the connections The distance between the actuator module and thermostat must not...

Страница 20: ...es In this case only one of the two CH176D modules must have the BUS selector in MASTER position while all others must be left in SLAVE mode default setting The temperature probe connected to the actu...

Страница 21: ...ng a command from the thermostat Flashing red and green alternately protection After twenty minutes during which the actuation module does not receive commands from the thermostat the relays are deact...

Страница 22: ...e recycling facilities A black bar indicates that the product was placed on the market after 13 August 2005 Participating in the separate collection of products and batteries contributes to the correc...

Страница 23: ...R2 GENERAL WARRANTY CONDITIONS The conventional warranty lasts 24 months starting from the date the equipment is installed The warranty covers all parts of the equipment with the exception of those su...

Страница 24: ...FANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milan ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it www fantinicosmi it 5679955 01 2021...

Отзывы: