P03: display visualization

ambient temperature: the ambient tempera-

ture will be shown on the display. 

2

 set-point: the current set point will be shown 

on the display.

P07: ambient temperature correction

It can be adjusted from –4.0 to 4.0°C. This pa-
rameter is used to correct the acquired ambient 
temperature. As a matter of fact, the ambient 
temperature reading may, on some instal-
lations, not be satisfying, owing to the probe 
location (i.e. internal or resumption). With this 
parameter, a constant value upon reading can 
be added to or subtracted from.

P08: “Winter” lower limit set-point tempera-
ture

It can be adjusted from 2.0 to 40.0°C. It rep-
resents the lower limit for all the set-points 
(“Comfort” and “Economy”) in the heating 
mode.

P09: “Winter” upper limit set-point tem-
perature

It can be adjusted from 2.0 to 40.0°C. It rep-
resents the upper limit for all the set-points 

(“Comfort” and “Economy”) in the heating 
mode.

P10: “Summer” lower limit set-point tem-
perature

It can be adjusted from 2.0 to 40.0°C. It repre-
sents the lower limit for all the set-points (“Com-
fort” and “Economy”) in the cooling mode.

P11: “Summer” upper limit set-point tem-
perature

It can be adjusted from 2.0 to 40.0°C. It rep-
resents the upper limit for all the set-points 
(“Comfort” and “Economy”) in the cooling 
mode.

P14: differential adjustment

It can be set staring from ±0.3°C (value suit-
able for slow-inertia systems) to ±2°C (value 
suitable for very reactive systems).

Содержание CH130RR

Страница 1: ...CH130RR AMBIENT THERMOSTAT FOR FAN COILS WITH ACTUATOR...

Страница 2: ...uators with a thermostat 15 Technical features of the actuator 16 TABLE OF CONTENTS Introduction 3 Controls and signals 4 Controls 4 Signals 4 User s manual 5 Summer Winter selection 5 Operating modes...

Страница 3: ...wo pole cable The CH130R is powered directly by the actuator and is able to drive two valves and also control a 3 speed fan coil motor in manual mode The thermostat measures the ambient temperature ei...

Страница 4: ...stem ON in winter operation Controls and signals Controls 5 1 2 3 4 1 Fan speed increase button 2 Fan speed decrease button 3 Selected program temperature value increase button 4 Selected program temp...

Страница 5: ...the operating mode 3 Select the fan speed Summer Winter selection To switch from the Winter operation i e heat ing system to the Summer operation i e cooling system and vice versa press the 1 2 button...

Страница 6: ...nged from 2 C to 40 C by 0 1 C steps Operating modes The CH130R thermostat features three dif ferent manual operating modes Comfort Economy and the OFF function OFF Comfort operating mode With the Com...

Страница 7: ...ree fixed levels minimum medium maximum by pressing buttons 1 and 2 Maintenance The thermostat should be cleaned by using a soft cotton cloth No detergent should be used Installation The thermostat in...

Страница 8: ...e desired surface by means of the special fastening holes make sure that the socket is properly engaged with no deformation and that the connecting multi DRILLING CENTERS SCREWS SOCKET FASTENING HOLES...

Страница 9: ...e CH172D actuator with terminals A and B as illustrated in the figure The terminals take flexible conductors having a maximum section of 2 5 mm2 External probe connection Connect the two external prob...

Страница 10: ...button 3 Warning The configuration shall be performed only by qualified personnel The configuration parameters are represented by an index P01 P02 on the display and by pressing buttons 1 and 2 the p...

Страница 11: ...ve ON OFF type used for heat ing both during the heating and the cooling in fact the valve will control both hot water and cold water 2 four tube system the thermostat will drive one valve ON OFF type...

Страница 12: ...usted from 2 0 to 40 0 C It rep resents the lower limit for all the set points Comfort and Economy in the heating mode P09 Winter upper limit set point tem perature It can be adjusted from 2 0 to 40 0...

Страница 13: ...l controls 5 buttons Dimensions L x H x D 135 X 83 X 21 External temperature probe distance 10 m max Reference temperature gradient 4 K h Actuator cable max length 100m Conforming to the directives 20...

Страница 14: ...ntact between terminals C and V1 In case of a four tube system valve 1 is dedicated to heating whereas valve 2 be tween C and V2 is dedicated to cooling WARNING Prior to carrying out any operation on...

Страница 15: ...to control up to five fan coils at the same time by making use of only two ca bles to get connected with the actuators One of such actuators shall be a CH172D whereas the others four at most shall be...

Страница 16: ...puts Network voltage switch ing contacts 3 motor contact outputs Container IP00 pollution degree 2 Software class A Max temperature T45 Conforms with the directives 2006 95 CE 2004 108 CE 1993 68 CE C...

Страница 17: ...17 Fantini Cosmi S p A reserve the right to make any necessary technical and construction modification without any obligation to give prior notice...

Страница 18: ...18 NOTES NOTE...

Страница 19: ...indicates that the product was placed on the market after August 13 2005 By participating in separate collection of products and batteries you will help to assure the proper disposal of products and b...

Страница 20: ...ANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it EXPORT DEPARTMENT Ph 39 02 95682229 export fantinicosmi it www fantin...

Отзывы: