11
Index
Parameter
Values
Preset
P01
Type of system
1-2
1
P02
External probe
3-4-5
5
P03
Display visualization
1-2
1
P07
Ambient
temperature
correction
-4°C –+ 4°C
(step 0.1°C)
0
P08
“Winter” lower
limit set-point
temperature
2°C – 40°C
(step 1°C)
2,0 °C
P09
“Winter” upper
limit set-point
temperature
2°C–40°C
(step 1°C)
40,0 °C
P10
“Summer” lower
limit set-point
temperature
2 °C – 40°C
(step 1°C)
5,0 °C
P11
“Summer” upper
limit set-point
temperature
2 °C – 40°C
(step 1°C)
30,0 °C
P14
Differential
adjustment
±0.3 - ±2°C
±0.3 °C
END
Thermostat saving
and reset
P01: Type of system.
1
two-tube system: the thermostat will drive
only the valve (ON/OFF type) used for heat-
ing both during the heating and the cooling: in
fact, the valve will control both hot water and
cold water.
2
four-tube system: the thermostat will drive
one valve (ON/OFF type) used for heating,
plus one additional valve (ON/OFF type) used
for cooling, depending on the needs of the en-
vironment.
P02: External probe.
1
not available with this version.
2
not available with this version.
3
minimum window/thermostat contact: when
the contact is open, the thermostat will carry
out heat regulation; when it is closed, the heat
regulation will not be carried out.
4
inverted minimum window/thermostat con-
tact: the window contact will operate with an
inverted logic with respect to the statements
made in previous step 3.
5
none: the external probe input will not be
controlled by the thermostat.