background image

CH130ARR

ROOM THERMOSTAT FOR FAN-COILS 
(AUTO VERSION WITH ACTUATOR)

Содержание CH130ARR

Страница 1: ...CH130ARR ROOM THERMOSTAT FOR FAN COILS AUTO VERSION WITH ACTUATOR...

Страница 2: ...th a thermostat 17 Technical features of the actuator 18 TABLE OF CONTENTS Introduction 3 Controls and signals 4 Controls 4 Signals 4 User s manual 5 Summer Winter selection 5 Operating modes 6 Comfor...

Страница 3: ...ble The CH130AR is powered directly by the ac tuator and is able to drive two valves and also control a 3 speed fan coil motor either in man ual or automatic mode The thermostat measures the ambient t...

Страница 4: ...ion 9 System ON in winter operation Controls and signals Controls 5 1 2 3 4 1 Fan speed increase button 2 Fan speed decrease button 3 Selected program temperature value increase button 4 Selected prog...

Страница 5: ...the operating mode 3 Select the fan speed Summer Winter selection To switch from the Winter operation i e heat ing system to the Summer operation i e cooling system and vice versa press the 1 2 button...

Страница 6: ...ged from 2 C to 40 C by 0 1 C steps Operating modes The CH130AR thermostat features three dif ferent manual operating modes Comfort Economy and the OFF function OFF Comfort operating mode With the Com...

Страница 7: ...t even the antifreeze one The system will switch off automatically and the OFF message will appear on the display Fan speed selection The fan speed can be set to three fixed levels minimum medium maxi...

Страница 8: ...y engaged with no deformation and that the connecting multi pole connector is located in the right bottom corner DRILLING CENTERS SCREWS SOCKET FASTENING HOLES MULTI POLE CON NECTOR Maintenance The th...

Страница 9: ...e The terminals take flexible conductors having a maximum section of 2 5 mm2 To ensure correct operation the socket shall be placed at a height of approximately 1 5 me tres from the floor far from hea...

Страница 10: ...own to the socket make sure that the multi pole connec tor is engaged correctly Fit the battery top cover back into place Thermostat configuration The thermostat configuration allows you to customize...

Страница 11: ...will save the modified parameters and will auto matically exit the parameter menu N B The thermostat will send the switch on off controls for the three fans and the two valves to the actuator to a fi...

Страница 12: ...hermostat will drive one valve ON OFF type used for heating plus one additional valve ON OFF type used for cooling depending on the needs of the en vironment P02 External probe 1 resumption instead of...

Страница 13: ...he water flow P05 Winter valve type 1 normally open in this case the water flow is normally open and will be closed when the valve is fed 2 normally closed when the valve is energized it will open the...

Страница 14: ...mmer lower limit set point tem perature It can be adjusted from 2 0 to 40 0 C It repre sents the lower limit for all the set points Com fort and Economy in the cooling mode P11 Summer upper limit set...

Страница 15: ...ling LCD display Local controls 5 buttons Dimensions L x H x D 135 X 83 X 21 External temperature probe distance 10 m max Reference temperature gradient 4 K h Actuator cable max length 100m Conforming...

Страница 16: ...tact between terminals C and V1 In case of a four tube system valve 1 is dedicated to heating whereas valve 2 be tween C and V2 is dedicated to cooling WARNING Prior to carrying out any operation on t...

Страница 17: ...to control up to five fan coils at the same time by making use of only two cables to get connected with the actuators One of such actuators shall be a CH172D whereas the others four at most shall be...

Страница 18: ...y output fea tures 5 3 A250 V Voltage free switch ing contacts 2 valve outputs Network voltage switching contacts 3 motor contact outputs Container IP00 pollution degree 2 Software class A Max tempera...

Страница 19: ...indicates that the product was placed on the market after August 13 2005 By participating in separate collection of products and batteries you will help to assure the proper disposal of products and b...

Страница 20: ...ANTINI COSMI S p A Via dell Osio 6 20090 Caleppio di Settala Milano ITALY Tel 39 02 956821 Fax 39 02 95307006 info fantinicosmi it EXPORT DEPARTMENT Ph 39 02 95682229 export fantinicosmi it www fantin...

Отзывы: