4.11. General Settings
General settings establish some parameters that are necessary for the relay to operate. These
settings are defined as general because they affect the entire relay, and as a result they are not
subject to a change of setting group.
Function
Description
Minimu
m
Maximum
Pitch
Unit
Default
General settings
Equipment identifier
-
-
-
-
“free text”
Frequency
-
-
60/50
Hz
50
Serial Number
-
-
-
-
0
Language
-
-
-
-
English
Settings active group (2*)
1
3
1
-
1
Transformation ratio of the
phase CTs
1.0
3000.0
0.1
-
100
Transformation ratio of the
neutral CTs
1.0
3000.0
0.1
-
100
Local communication
address
1
247
1
-
1
Password
-
-
-
-
****
Remote communication
address
1
247
1
-
2
Remote communication
baudrate
4800
38400
-
bps
19600
(1*) “SERIAL NUMBER” setting is a read only setting.
(2*) “SETTINGS ACTIVE GROUP” setting can be changed also through inputs.
The rest of the settings can be changed from HMI or through communications
NOTE: When the frequency is changed it is necessary to reinitialize the relay twice to ensure
that the setting is loaded correctly.
Содержание SIA-F
Страница 7: ...www fanox com Rev 17 7 119 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Страница 8: ...www fanox com Rev 17 8 119 2 2 Case dimensions The dimensions are in mm CUT OUT PATTERN...
Страница 9: ...www fanox com Rev 17 9 119 2 3 Connection diagram 3 Phase CT and neutral CT Connection...
Страница 10: ...www fanox com Rev 17 10 119 3 Phase CT and residual neutral Connection...
Страница 18: ...www fanox com Rev 17 18 119 3 5 2 Load curve for relay SIA F 1 3 5 3 Load curve of relay SIA F 5...
Страница 34: ...www fanox com Rev 17 34 119...
Страница 35: ...www fanox com Rev 17 35 119...
Страница 36: ...www fanox com Rev 17 36 119...
Страница 117: ...www fanox com Rev 17 117 119 9 6 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 118: ...www fanox com Rev 17 118 119 NOTES...
Страница 119: ...www fanox com Rev 17 119 119...