Rev. 06
92/99
9.6.
Commands Map
7
Reset thermal image
9.7.
Examples of ModBus frames
9.7.1.
Writing the access password “5555” to equipment nº 1
Address
01
Function
10
H start address
00
L start address
A8
Number of H registers
00
Number of L registers
02
Number of bytes
04
Password
35,35,35,35
Checksum H
4A
Checksum L
50
And SIAB respond OK:
Address
01
Function
10
H start address
00
L start address
A8
Number of H registers
00
Number of L registers
02
Number of bytes
04
Checksum H
29
Checksum L
93