5.6.1. Thermal image measurement evolution graphic
On next graphic, thermal image measurement evolution can be observed depending on applied
current:
Supposing that thermal image protection has an adjusted tap of 1,1 times the nominal current and an
alarm level of 75%:
Zone 1: The machine is de-energized for a long time. Thermal image is 0%.
Zone 2: The machine is supplied with the nominal current. Thermal image evolutions so as to
get the value of the thermal balance corresponding to one time the nominal current Th = (I/It)
2
= 82%. The time that it takes in getting the thermal balance depends on the adjusted heating
constant.
Zone 3: Once reached the thermal image corresponding to the application of one time the
nominal current, it is applied 1,2 times the nominal current. Thermal image would evolve so as
to get the thermal balance corresponding to 1,2 times the nominal current Th = (I/It)
2
= 119%.
This would occur if the permission of the thermal function is disabled. If the permission is
disabled, 49 protection function performs when the thermal image reaches the value of 100%.
Once tripped, current is cut and thermal image is getting cool based on the cooling constant.
Zone 4: Before getting totally cool, nominal current is applied again and thermal balance is
reached once passed the time determined by the heating thermal constant.
Thermal image protection alarm bit is active if the thermal image measurement is over the adjusted
alarm level.
Thermal image protection trip bit is active when the measurement of the thermal image is over 100%
and it is reset when the measurement of the thermal image is under the adjusted alarm level.
Th %
t
100%
1
2
3
4
75%
alarm
trip
Содержание SIA B
Страница 7: ...www fanox com Rev 06 7 99 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Frontal view...
Страница 8: ...www fanox com Rev 06 8 99 2 2 Case dimensions The dimensions are in mm Cut out pattern...
Страница 9: ...www fanox com Rev 06 9 99 2 3 Connection diagram NOTE STRIKER 6 24 Vdc 0 1 W s...
Страница 18: ...www fanox com Rev 06 18 99 Dimensions...
Страница 28: ...www fanox com Rev 06 28 99...
Страница 29: ...www fanox com Rev 06 29 99...
Страница 30: ...www fanox com Rev 06 30 99...
Страница 31: ...www fanox com Rev 06 31 99...
Страница 33: ...www fanox com Rev 06 33 99...
Страница 34: ...www fanox com Rev 06 34 99...
Страница 35: ...www fanox com Rev 06 35 99...
Страница 97: ...www fanox com Rev 06 97 99 11 5 Comments Person in charge of commissioning Date Maintenance performed on the by...
Страница 98: ...www fanox com Rev 06 98 99 NOTES...
Страница 99: ...www fanox com Rev 06 99 99...