Technical data
rated supply voltage
mail linia (1-2 terminals)
battery (1-4 terminals)
10÷12 V DC*
maximum permissible voltage
(1-2, 1-3 terminals)
400 V AC
contacts
3×NO
maximum switching current of internal contacts
AC-1
16 A/250 V
AC-15
3 A/250 V
voltage threshold**
lower (adjustable)
150÷210 V
upper
270 V
hysteresis
5 V
switch-off time
lower threshold (adjustable)
1÷15 sec
0.3 sec
switching time
0.3 sec
time to qualify the line as a good
10 sec
generator start time
5÷120 sec
durability of relay contacts
>10⁵ switchings
power consumption
1.5 W
working temperature
-25÷50°C
connection
2.5 mm² screw termianls
tightening torque
0.4 Nm
dimensions
3 modules (52 mm)
mounting
on the TH-35 mm rail
protection level
IP20
*
recommended battery type: URLA, voltage 12 V, capacity 1.2 Ah
**
at voltage over 300 V, the load is disconnected in no more than 0.1 seconds
230 V AC
generator (1-3 terminals)
230 V AC
upper threshold
CE declaration
Declaration of CE conformity of the device can be downloaded
from the product page from the website:
www.fif.com.pl.
AL failure indication
load off
normal operation
incorrect contact configuration
(voltage at the Uk output)
relay lock
(input 5 connected to the neutral line)
on
off
4 blinks/sec
short switching on
L i L' phase status indicators
reduced voltage/lack of voltage
voltage too high
line connected to the reception
qualification of the line as good
voltage correct, phase is not used
off
4 blinks/sec
on
short switching off
short switching on
START generator status indicators
generator off
generator start
countdown of the pause time
between a restart attempt
normal operation
generator error
off
short switching off
short switching on
on
4 blinks/s
- 9 -
- 11 -
D190211
Indication