7
XG1.5K-1T
XG2.2K-1T / XG3K-1T
1 box contains: 2 boxes contain:
Box 1:
UPS module with fitted battery pack UPS module without battery
RS-232 cable RS-232 Cable
Software CD Software CD
Manual Manual
19” rack ears (+ screws) 19” rack ears (+ screws)
Tower Mounting feet Tower Mounting feet
Box 2:
Battery Module
Battery connection cable
Keyhole hardware
19” rack ears (+ screws)
1 set of mounting plates
INSPECTING THE EQUIPMENT
Visually inspect the UPS for freight damage. If any equipment has been damaged during
shipment, keep the shipping cartons and packing materials for the carrier, and immediately
file a claim for shipping damage with the carrier. If you discover damage after acceptance, file
a claim for concealed damage.
To file a claim for shipping damage or concealed damage:
1. YOU MUST file with the carrier within 15 days of receipt of the equipment;
2. YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.
CAUTION
The UPS and Battery Module are heavy. Take proper precautions when lifting or moving them.
Install the UPS indoors in a controlled environment; place it in an area with unrestricted
airflow around the unit, away from water, flammable liquids, gases, corrosives, and
conductive contaminants. Maintain a minimum clearance of 4 inches in the front and rear of
the UPS. Maintain an ambient temperature range of 32
o
F to 104
o
F (0
o
C to 40
o
C). To maximize
the life time of the batteries, an ambient temperature of 68
o
F to 77
o
F (20
o
C to 25
o
C) is
recommended. OPERATION IN TEMPERATURES ABOVE 77
O
F (25
O
C) WILL REDUCE
BATTERY LIFE.
The XG Series UPS can be installed in either a free-standing mini-tower or into a 19 inch
equipment rack. Follow the appropriate instructions in either RACK-MOUNT UPS SETUP or
FREE-STANDING UPS INSTALLATION.
RACK-MOUNT UPS SETUP
All XP Series UPSs are shipped with front panel mounting ears that allows the unit to be
installed in a 19” rack. Each UPS unit and external battery enclosure needs 2U of rack space.