LED

3.6V

Lithium

Battery

Antenna

Circuit 

Board

Clip

L Brackets

Plastic 

Pegs

Antenna Guides

11. 

Check the WiNG‑MGR web interface or BMS to make sure the sensor status 

reports accurately.

12. Use DIP1 and DIP2 to set the read frequency for the sensor. The read 

frequency is the amount of time that passes between when each sensor 

reading is reported to the WiNG‑MGR or BMS‑WiNG. The shorter the read 

frequency, the more frequently the sensor data will be reported to and 

updated in the controller.  The shorter the read frequency, the shorter the 

battery life of the sensor. 

WiNG-AIR3 Sensors

DIP1

DIP2

Read Frequency

Battery Life

On (Up)

On (Up)

20‑40 seconds (~30 seconds)

5.5 years

Off (Down)

On (Up)

40‑80 seconds (~60 seconds)

8 years

On (Up)

Off (Down)

60‑120 seconds (~90 seconds)

9.5 years

Off (Down)

Off (Down)

80‑160 seconds (~120 seconds)

*

11 years

*

WiNG-AIR4 and WiNG-AIR10 Sensors

DIP1

DIP2

Read Frequency

Battery Life

On (Up)

On (Up)

40‑80 seconds (~60 seconds)

2.25 years

Off (Down)

On (Up)

80‑160 seconds (~120 seconds)

4 years

On (Up)

Off (Down)

120‑240 seconds (~180 seconds)

5 years

Off (Down)

Off (Down)

160‑320 seconds (~240 seconds)

*

7 years

*

*Default setting

13. 

Replace the lid, ensuring that the antenna is held in place by the antenna 

guides and feeds out the vent hole in the side of the enclosure. Do not pinch 

the antenna between the lid and the case.

Airflow

Sensor 

Connection

SW2

DIP

Switches

Channel

Selection

Button

Airflow Sensor 

Leader Cable 

WiNG-AIR3

AIR IN

AIR OUT

AIR OUT

AIR IN