LED
3.6V
Lithium
Battery
Antenna
Circuit
Board
Clip
L Brackets
Plastic
Pegs
Antenna Guides
11.
Check the WiNG‑MGR web interface or BMS to make sure the sensor status
reports accurately.
12. Use DIP1 and DIP2 to set the read frequency for the sensor. The read
frequency is the amount of time that passes between when each sensor
reading is reported to the WiNG‑MGR or BMS‑WiNG. The shorter the read
frequency, the more frequently the sensor data will be reported to and
updated in the controller. The shorter the read frequency, the shorter the
battery life of the sensor.
WiNG-AIR3 Sensors
DIP1
DIP2
Read Frequency
Battery Life
On (Up)
On (Up)
20‑40 seconds (~30 seconds)
5.5 years
Off (Down)
On (Up)
40‑80 seconds (~60 seconds)
8 years
On (Up)
Off (Down)
60‑120 seconds (~90 seconds)
9.5 years
Off (Down)
Off (Down)
80‑160 seconds (~120 seconds)
*
11 years
*
WiNG-AIR4 and WiNG-AIR10 Sensors
DIP1
DIP2
Read Frequency
Battery Life
On (Up)
On (Up)
40‑80 seconds (~60 seconds)
2.25 years
Off (Down)
On (Up)
80‑160 seconds (~120 seconds)
4 years
On (Up)
Off (Down)
120‑240 seconds (~180 seconds)
5 years
Off (Down)
Off (Down)
160‑320 seconds (~240 seconds)
*
7 years
*
*Default setting
13.
Replace the lid, ensuring that the antenna is held in place by the antenna
guides and feeds out the vent hole in the side of the enclosure. Do not pinch
the antenna between the lid and the case.
Airflow
Sensor
Connection
SW2
DIP
Switches
Channel
Selection
Button
Airflow Sensor
Leader Cable
WiNG-AIR3
AIR IN
AIR OUT
AIR OUT
AIR IN