Chapter 5 Managing USHA/UPS via SNMP

 

Setting SNMP parameters in USHA   

If you intend to manage your USHA/UPS via SNMP NMS (Network Management station), you may 

want to customize some of the SNMP settings (such as System Name, System Contact and System 
Location and so on).   

 

Before using USHA in SNMP environment, the IP address and gateway must be properly 

configured. Please refer to Chapter 2 for the details. 

 

SNMP Access Control Setting 

Because of the USHA supports SNMP network protocol, you can use SNMP NMS to manage UPS 

through the network. The IP address of the workstation must be set up in the USHA write access 
table to prevent unauthorized users from configuring USHA via HTTP or SNMP protocols.   

 

 

Note: If you  do not enter the IP address of the workstation to the Access Control Table (via 

Serial Port or Telnet) or the SNMP/HTTP Access Control (via Web Browser) in USHA, the SNMP 

NMS  can  only  view  the  UPS  status;  it  will  not  be  able  to  perform  any  configuration  on 

USHA/UPS. (See Pg. 14 SNMP Control Table and Pg. 22 SNMPv3 USM Table for details.) 

SNMP Trap Receivers Setting 

See Pg. 21 SNMP Trap Receivers for details. 

 

Set up SNMP Manager Software 

1.

 

Add the MIB file of USHA from the USHA CD-ROM to the MIB database of the SNMP 
manager. 

2.

 

Search the USHA equipment in the network 

3.

 

To access the USHA SNMP agent, use ‘public’ for the GET community string and the 
Read/Write password (default is 

admin

) for the SET community string. 

 
GET Community string: public 
SET Community string: admin 

 

For more information, see the MIB file on the USHA CD-ROM. 

 

 

 

Содержание mimi USHA EX900 Series

Страница 1: ...U US SH HA A I IX X E EX X 9 90 00 0 U UP PS S S SN NM MP P H HT TT TP P A AG GE EN NT T User s Manual USHA IX900 series mimi USHA IX900 series mimi USHA EX900 series Version 2 00 Dec 2021...

Страница 2: ...Comprehensive View 15 UPS Identification 16 Battery Parameters 16 Input Parameters 17 Output Parameters 17 Alarm Table 18 Client Table 19 UPS Management 20 UPS Configuration 20 UPS Control 21 UPS Bat...

Страница 3: ...pter 4 Configuring the USHA via SSH 47 Configuring via SSH 47 Setting the IP Address Gateway Address Network Mask and Date Time 48 Network Control Group Setting 50 Account Control Group Setting 52 Ema...

Страница 4: ...Managing the UPS Shutdown Schedule 64 Appendix A Technical Information 65 LED Definition 65 Technical Specification 66...

Страница 5: ...d in a commercial environment CE Notice This device complies with the EMC directive of the European Community and meets or exceeds the following technical standard EN55022 2010 Class B EN55024 2010 IE...

Страница 6: ...management and flexible configuration via Web Browser NMS SSH and SNMP Automatic events notification via E mail short message SMS and SNMP Trap Graceful shutdown to protect up to 250 servers workstat...

Страница 7: ...ion via the network USHA also provides shutdown software tool for sending the event notifications to the connected clients The shutdown software can be installed on various operating systems It can co...

Страница 8: ...Software 1 Piece 4 Serial Cable for connecting UPS Only for EX901 902 952 1 Piece Interface of USHA IX900 mini USHA IX EX900 The interface of USHA IX901 includes a Network port EMD port USB port Setu...

Страница 9: ...scription 1 Network port Connects to network LED indication LAN 10 100 link Activity 2 EMD port Connects to an environmental sensor EMD LED indication System power System status 3 USB port Connects t...

Страница 10: ...p1 Insert the USHA Card into the UPS slot Step2 Lock the screws of the USHA card bracket Step3 Procure a workstation Microsoft Windows XP Vista 7 or above installed Step4 Insert the Ethernet cable int...

Страница 11: ...d the USHA FITility v1 xx exe in CD contents and install the Upgrade Tool on your PC Step2 Execute USHA FITility USHA FITility will auto discover and list up the devices on your LAN Step3 If necessary...

Страница 12: ...12 Step4 Type in Account and Password Step5 Type in new settings and click Next to finish the IP setting Step6 Select your device and click Browse to open webpage...

Страница 13: ...13 Step7 The webpage display the USHA Comprehensive View...

Страница 14: ...ddress in the network 5 Enter the USHA Subnet Mask of the network 6 Enter the IP address of the Primary Time Server and Secondary Time Server in the network 7 Click the Set Values to save the settings...

Страница 15: ...tage Battery Capacity Remaining The remaining battery capacity expressed in percent of full capacity Current Battery Voltage The current battery voltage expressed in Volts UPS Temperature This shows t...

Страница 16: ...0E 900VA UPS Name This is the name of the UPS configured by Administrator UPS Firmware Revision The firmware revision of the UPS USHA Firmware Revision The firmware revision of USHA UPS Manufacturer T...

Страница 17: ...alue should be reset by the Administrator Input Parameters The page will refresh automatically Current Utility Line Voltage This shows the current input voltage in Volts Max Utility Line Voltage Last...

Страница 18: ...current output Current in Amps Output Load This shows the current load on the UPS in terms of percentage Alarm Table This menu will refresh automatically Number of Active Alarms Number of current act...

Страница 19: ...ent system that has the Shutdown Program running and has registered with USHA Index Serialized index number of the client registered IP Address IP address of the client running the Shutdown Program an...

Страница 20: ...output voltage in Volts Output Frequency This shows the nominal output frequency in Hertz Output VA The maximum number of Volts multiply by Amps that the UPS can deliver Output Power This shows the n...

Страница 21: ...be count down synchronize to the shutdown delay time set in the Shutdown Program in all connected clients To avoid improper shutdown of the clients the UPS shutdown delay time set in USHA should alwa...

Страница 22: ...ery Test Command None No action Quick Battery Test Perform battery test for a short time Test Until Battery Low Perform battery test until battery low Timed Test Perform the battery test for the perio...

Страница 23: ...broadcast to the connected clients Client Shutdown warning message will be broadcast and shutdown command will be sent to the connected clients UPS Turn Off warning message will be broadcast shutdown...

Страница 24: ...he UPS is over the pre set value Please check the configuration in UPS Shutdown menu for UPS Over Temperature Weekly Schedule This Shutdown occurs as per the timings given in the Weekly Schedule shutd...

Страница 25: ...utput power Special Schedule This page shows the special day schedule for the UPS From this page the UPS can be scheduled to shutdown and restart on a specific day and time Index This column provides...

Страница 26: ...he USHA will synchronize its time with the server periodically If Daylight Saving Time enabled the time will be one hour earlier than NTP server time Set Manually User can set the date and time with t...

Страница 27: ...tem Contact The value set in System manager System Contact defined in MIB II System Location The value set in System installation place System Location defined in MIB II History Log Interval This valu...

Страница 28: ...eful auto configuration via DHCPv6 USHA IPv6 Local Address The IPv6 link local address of system eg FE80 2E0 D8FF FEFF 8A59 The prefix of link local address is always FE80 64 64 is the prefix length T...

Страница 29: ...has to enter user name and password when he she access to USHA SSH Connection Enable Disable the SSH connection with the USHA The user may configure SSH protocol to use a port number other than standa...

Страница 30: ...er User can set the Share Secret of Secondary Server Packet Timeout Interval sec User can set the Packet Timeout Interval Packet Retry Times User can set the Packet Retry Times Multi User Table This p...

Страница 31: ...This field allows the administrator to set the privacy password of the associated user Priv Protocol This field allows the administrator to set the privacy protocol DES or AES Security Level This fiel...

Страница 32: ...he trap to be received Information All traps are received Warning Trap that need to be noticed and are in dangerous is received Severe The significant traps such as the UPS failure and low battery whi...

Страница 33: ...f the string is 31 characters Wake On LAN test Send the packet to turn on the client PC Unix Linux Shutdown This page allows user to set UNIX Linux remote shutdown function and user will be able to sh...

Страница 34: ...ld allows the administrator to key in the script content Administrator can select Show or Hide the script content Test result To display the result of Unix Linux Shutdown Test Email Notification This...

Страница 35: ...email support TLS Mail Account As Administrator you may enter the email address of the individual you wish to have the SNMP WEB Adapter send mail to Description As Administrator you may enter a descri...

Страница 36: ...ion of Informational Warning or Severe Refer to the MIB documentation included with the adapter for more information If the Event Filter is by Event administrator can select which trap should be sent...

Страница 37: ...viders User Name The account that has created with the selected DDNS provider Password The password that collocate to your DDNS account DDNS Domain Name The Domain Name has created from the selected D...

Страница 38: ...0 128 IPv6 Action Accept this IP or IP segment could be accessed USHA Reject this IP or IP segment could not be accessed USHA Modbus TCP Configuration This page lets the administrator to set Modbus co...

Страница 39: ...lave To set the USHA to be master or slave device Slave Address This field will display the IP address of the device Alarm Number Number of current active UPS alarms Alarm Description This field will...

Страница 40: ...for a two wire detector that will emulate an open close state When the wires are closed to loopback the signal for the sensor the sensor will detect the state as closed The sensor will NOT activate th...

Страница 41: ...on Security To select the wireless security Password To enter wireless password Channel The operating frequency to be used Signal Strength The signal strength of wireless device External Links Setup T...

Страница 42: ...tup in the USHA Server Control This field allows to Enabled or Disabled USHA connecting to IoT server Server IP This field allows to set the IP address of USHA which administrator wants to connect to...

Страница 43: ...the values were recorded Input Voltage This shows the input voltage in Volts at the time of recording Output Voltage This shows the output voltage in Volts at the time of recording Output Current Thi...

Страница 44: ...his column shows the date when consolidation of the record started Start Time This gives the time in a 24 hour format when the values were recorded End Date This column shows the ending date of the co...

Страница 45: ...the average temperature of the UPS battery in o C in the consolidated interval EMD Temperature This shows the current temperature measurement of the EMD EMD Humidity This shows the current humidity m...

Страница 46: ...low Administrator can save the various USHA log data to a file with the extension csv that can be opened and read in MS Excel Save all logs to USB Flash This function allow administrator to save all l...

Страница 47: ...een please enter the user name and password the default username is SNMP and the password is admin Then the USHA configuration utility main menu will show on the screen Login as SNMP usha 192 168 53 2...

Страница 48: ...0va 1 IP Time and System Group 2 Network Control Group 3 Account Control Group 4 Email Group 5 SNMP Group 0 Back to Main Menu Please Enter Your Choice 1 2 Select 1 to enter the IPv4 Group page or 2 t...

Страница 49: ...s 2001 1234 100 f101 2e0 d8ff feff b406 64 0 Return to previous menu Please Enter Your Choice 0 4 Select 3 to enter the Date and Time Group pages IP Time and System Group Date and Time Group 1 System...

Страница 50: ...Email Group 5 SNMP Group 0 Back to Main Menu Please Enter Your Choice 2 1 Select 6 8 to enter the related network control pages USHA Configuration Utility USHA Network Control Group 1 BOOTP DHCP Cont...

Страница 51: ...setting as shown below Network Control Group SMTP Control Group 1 SMTP Control Enabled 2 SMTP Port 25 0 Return to previous menu Please Enter Your Choice 0 4 Enter the related SSH setting as shown bel...

Страница 52: ...odel 0va 1 IP Time and System Group 2 Network Control Group 3 Account Control Group 4 Email Group 5 SNMP Group 0 Back to Main Menu Please Enter Your Choice 3 1 Select 1 3 to enter the related account...

Страница 53: ...3 0 Return to previous menu Please Enter Your Choice 0 3 Enter the related access control setting as shown below Account Control Group Access Control Table User Name User Level 1 Disabled 2 Disabled...

Страница 54: ...setting as shown below Super User Name Password Group Super User Group 1 User Name SNMP 2 User Password 0 Return to previous menu Please Enter Your Choice 0 After completing these settings press 0 to...

Страница 55: ...3 Account Control Group 4 Email Group 5 SNMP Group 0 Back to Main Menu Please Enter Your Choice 4 1 Enter the related E mail setting as shown below USHA Configuration Utility Email Group 1 Mail Serve...

Страница 56: ...Level 1 None Information 2 None Information 3 None Information 4 None Information 5 None Information 6 None Information 7 None Information 8 None Information Command 1 Display one entry 2 Modify one e...

Страница 57: ...Group 0 Back to Main Menu Please Enter Your Choice 5 If you want to use a PC and perform the SNMP manager trap function in order to manage UPS through USHA the IP address of the PC must be added to th...

Страница 58: ...to previous menu Please Enter Your Choice 0 2 Enter the related SNMPv3 USM setting as shown below If you want to use a workstation with SNMP Manager or set up more restrictive access you can add the...

Страница 59: ...pleting the configuration press 0 to end the console connection Reboot USHA is not necessary unless you press 3 to end the console connection and force USHA reboot again USHA Configuration Utility USH...

Страница 60: ...g USHA via HTTP or SNMP protocols Note If you do not enter the IP address of the workstation to the Access Control Table via Serial Port or Telnet or the SNMP HTTP Access Control via Web Browser in US...

Страница 61: ...omatically during holiday or after office hour by using the Weekly Shutdown schedule or Special Day schedule These schedules can also assist MIS staff to prevent unauthorised access to the server afte...

Страница 62: ...trol in the UPS Management menu Login the web user interface as an administrator identity Select the radial button beside UPS Sleep and click the Send button UPS Shutdown Delay Sec 180 default value U...

Страница 63: ...s an administrator identity Configure the UPS Shutdown table to meet your need Click the Set Value button when finished Status UPS Turn Off default value Delay Min 10 default value 1st Warning Sec 30...

Страница 64: ...A is correct Scenario Status UPS Turn Off default value Delay Min 10 default value 1st Warning Sec 0 default value Warning Interval sec 60 default value UPS Shutdown Delay Sec 180 default value Shutdo...

Страница 65: ...ction 1 Network ON Flashing 1sec Ethernet 100 Traffic 2 OFF Flashing 1sec Ethernet 10 Traffic 3 ON ON 100 Base TX Ready 4 OFF ON 10 Base T Ready 5 OFF OFF Ethernet Disconnection 6 Status EMD ON OFF Po...

Страница 66: ...Watts Maximum without USB Host function 6 0 Watts Maximum with USB Host function SMT Switch SMT switch on the board for configuration Dimension L x W x H mm USHA IX900 series 129 9 L x 60 0 W mm miniU...