FOR INSTALLERS AND PROFESSIONALS
2.2.2. Heat pump installation.
The frame must be fixed by bolts
(M10)
to concrete foundation or brackets. The concrete
foundation must be solid; the bracket must be strong enough and anti-rust treated;
The heat pump needs a water pump
(Supplied by the user)
. The recommended pump
specification-flux: refer to Technical Parameter, Max. lift
≥10m
When the heat pump is running, there will be condensation water discharged from the bottom,
please pay attention to it. Please insert the drainage tube(accessory) into the hole and clip it well,
then connect a pipe to drain off the condensation water.
2.2.3. Wiring & protecting devices and cable specification
Connect to appropriate power supply, the voltage should comply with the rated voltage of the
products.
Well earth the heat pump.
Wiring must be connected by a professional technician according to the circuit diagram.
Set breaker or fuse according to the local code (leakage operating current
≤ 30mA
).
The layout of power cable and signal cable should be orderly and not affecting each other.