For installers and professionals
thermostat.
③
In order to protect the heat pump, the heat pump is equipped with start delay
function. When starting the heat pump, the fan will start to run in 3 minutes, in another
30 seconds, the compressor will start to run.
④
After pool heat pump starts up, check for any abnormal noise from the heat pump.
⑤
Check the temperature setting
2.4. Maintenance and winterizing
2.4.1 Maintenance
The maintenance should be carried out once per year by qualified professional
technician.
①
Cut off power supply of the
heat pump before cleaning,
examination and repairing .
Do not touch the electronic
components until the LED
indication lights on PCB turn off.
②
Please clean the evaporator with household detergents or clean water, NEVER use
gasoline, thinners or any similar fuel.
③
Check bolts, cables and connections regularly.
2.4.2 Winterizing
In winter season when you don’t swim, please cut off power supply and drain water out of
the heat pump. When using the heat pump under 2 , make sure there is always water
℃
flow.
3. Trouble shooting for common faults
Failure
Reason
Solution
Heat pump doesn’t run
No power
Wait until the power recovers
Power switch is off
Switch on the power
14
Important:
Unscrew the water union of inlet pipe
to let the water flow out.
When the water in machine freezes in
winter season, the titanium heat
exchanger may be damaged.
vivapool.pl
vivapool.pl
vivapool.pl
Содержание Inverter-Plus Series
Страница 3: ...vivapool pl vivapool pl vivapool pl...
Страница 5: ...For users 2 vivapool pl vivapool pl vivapool pl...
Страница 22: ...Note vivapool pl vivapool pl vivapool pl...
Страница 40: ...F r Monteure und H ndler 16 Erdung Erdung vivapool pl vivapool pl vivapool pl...
Страница 42: ...Version M89I vivapool pl vivapool pl vivapool pl...