PNEUMATIC CONNECTIONS

Clean all pipelines to remove dirt and scale before

installation.

Apply a minimum amount of pipe compound to the male

threads of the air line only. 

Do Not use teflon tape as a

sealant.

 Start with the third thread back and work away

from the end of the pipeline to avoid the possibility of

getting pipe compound into the air lines.

The inlet and outlet ports are labeled on the bottom of the

Pressure Controller. Tighten connections securely. Avoid 

undersized fittings that will limit the flow through the 

transducer. For more information, see Figure 1. "T9000 

Outline Dimensions" on page 1.

CAUTION:

Oil free air is required. Use a filter to remove dirt and liquid 

in the air line ahead of the pressure controller. If an air line 

lubricator is used, it MUST be located downstream to avoid 

interference with pressure controller performance.

Supply pressure must be no less than 5 psig, [0.35 BAR], 

(35 kPa), above maximum output.

ELECTRIC CONNECTION

For the T9000 Pressure Controller, make connections as 

shown below in Figure 2. "Electrical Connections". For 

compatible cord sets and connections refer to Table 1. 

below.

For signal lines of six feet or less, 22 gage wire may be used.

For longer signal lines, use 18 gage wire. Shielded cable

must be used for the signal lines for noise immunity.

¹ Colors apply only to FIPC DeviceNet compatible cables.

 

Figure 2.

 Electrical Connections.

Model T9000 Series

Table 1. T9000 Cables

 (Sold Separately)

Part number

Description

032-IPI-018-2

Cable w/one straight connector (2 

meter)

032-IPI-019-2

Cable w/one right angle connector (2 

meter) shown

Pressure Controller Electrical Connections

PIN # Wire Color

Function

1

Brown

(+) 4-20mA or 0-10vdc FEEDBACK

2

White

(-) FEEDBACK RETURN

3

Blue

(+) 4-20mA or 0-10vdc CONTROL SIGNAL

4

Black

(-) CONTROL SIGNAL RETURN

5

Gray

(-) SUPPLY RETURN

6

Pink

(+) 18-32VDC SUPPLY