Fairchild T9000 Скачать руководство пользователя страница 2

TANK

FEEDBACK TUBE

OUTLET TUBE

* Remote Pressure Sense Port Adaptors

Figure 2.

 Remote Pressure Sensing

REMOTE PRESSURE SENSING

The T9000 series pressure controllers can sense 

pressure from a remote location in the process 

system by employing the remote pressure sensing 

port.  Remote pressure sensing can be usefull for 

improving system response and eliminating the 

pressure drop associated with air flowing through 

the outlet tubing between the pressure controller 

and the process.

Remote pressure sensing is accomplished by 

removing the remote sensing port plug and inserting 

the 21665-* remote pressure sensing adaptor in the 

port.  This special adaptor blocks the pressure 

sensing passage coming from the outlet chamber of 

the pressure controller and makes the on board 

feedback pressure sensor connection available at 

the adaptor.

CAUTION:

Because of propagation delays in long 

feedback lines, the there is a limit in the length 

of the feedback line that can be employed, 

otherwise the system pressure will oscillate.  In 

general terms, the longer the feedback line, the 

larger the line must be to affect a stable 

system.  Adjustment of the T9000's PID 

constants may also be required.  Be sure there 

are no restrictions (kinks in the line or 

undersize fittings) in the feedback line.  Some 

experimentation may be required to determine 

the line size for the  length of run of the 

feedback line.

CAUTION:

To prevent damage to the Remote Pressure 

Sense Port Adaptor, support the Remote 

Pressure Sense Adapter with a wrench when 

installing the air line fitting. For more 

information,see Figure 3. below.

21665-*

ADAPTOR

Part Number

Pipe Connection

21665-1N

1/8-27 NPTF

21665-1U

1/8-28 BSPT

2