CALIBRATIONS / ADJUSTMENTS
Equipment Required for Calibration:
•
Pneumatic Supply capable of delivering up to 150 psig.
•
Current Supply capable of delivering up to 50 mA.
•
Voltage Supply capable of delivering up to 10 VDC.
•
Pressure Gage capable of a digital readout up to 50 psig
with an accuracy of .1%.
•
Digital Volt Meter capable of a readout up to 30 mA or
10 VDC with an accuracy of .02%.
The following adjustments are provided:
Full Range Operation
Forward/Reverse Mode
Calibration - Zero and Span
FULL RANGE OPERATION
Forward Acting Mode Adjustment
NOTE: Air Supply must be on before adjustments are
made.
1.
Connect the input signal to the transducer as shown
in Figure 6. “Electrical Connections.”
•
Forward Acting Calibration-Zero
2.
Apply the minimum input signal and adjust the Zero
screw for minimum output pressure. Turn screw
counterclockwise to increase pressure and clock
wise to decrease pressure.
•
Forward Acting Calibration-Span
3.
Apply the maximum input signal and adjust the Span
screw on the potentiometer for maximum output
pressure. Turn screw clockwise to increase pres
sure and counterclockwise to decrease pressure.
4.
Repeat steps 2-3 until the desired output range is
obtained. For more information, see Figure 7. “T5220/
TXPD5220 Calibration Configuration.”
Reverse Acting Mode Adjustment
NOTE: Intrinsically safe units cannot be set for re
verse acting mode in field.
5.
Connect the input signal to the transducer as shown
in Figure 6. “Electrical Connections.”
•
Reverse Acting Calibration-Zero
6.
Apply the minimum input signal and adjust the Zero
screw for maximum output pressure. Turn screw
counterclockwise to increase pressure and clock
wise to decrease pressure.
•
Reverse Acting Calibration-Span
7.
Apply the maximum input signal and adjust the Span
screw on the potentiometer for minimum output pres
sure. Turn screw counterclockwise to increase pres
sure and clockwise to decrease pressure.
8.
Repeat steps 6-7 until the desired output range is
obtained. For more information, see Figure 8. “T5200/
TXPD5200 Calibration Configuration.”
Figure 7.
T5220 / TXPD5220 Calibration Configuration.
5