CALIBRATIONS / ADJUSTMENTS 

Equipment Required for Calibration: 

• 

Pneumatic Supply capable of delivering up to 150 psig. 

• 

 Current Supply capable of delivering up to 50 mA. 

• 

 Voltage Supply capable of delivering up to 10 VDC. 

• 

Pressure Gage capable of a digital readout up to 50 psig

 with an accuracy of .1%. 

•  

Digital Volt Meter capable of a readout up to 30 mA or

 10 VDC with an accuracy of .02%. 

The following adjustments are provided: 

Full Range Operation
Forward/Reverse Mode
Calibration - Zero and Span

FULL RANGE OPERATION 
Forward Acting Mode Adjustment
NOTE:  Air Supply must be on before adjustments are 

made. 

    1. 

Connect the input signal to the transducer as shown 
in Figure 6. “Electrical Connections.” 

•  

Forward Acting Calibration-Zero 

2. 

Apply the minimum input signal and adjust the Zero 
screw for minimum output pressure.  Turn screw 
counterclockwise to increase pressure and clock­
wise to decrease pressure. 

•  

Forward Acting Calibration-Span 

3. 

Apply the maximum input signal and adjust the Span 
screw on the potentiometer for maximum output 
pressure.  Turn screw clockwise to increase pres­
sure and counterclockwise to decrease pressure. 

4. 

Repeat steps 2-3 until the desired output range is 
obtained.  For more information, see Figure 7. “T5220/ 
TXPD5220 Calibration Configuration.” 

Reverse Acting Mode Adjustment

NOTE:  Intrinsically safe units cannot be set for re­

verse acting mode in field. 

    5. 

Connect the input signal to the transducer as shown 
in Figure 6. “Electrical Connections.” 

•  

Reverse Acting Calibration-Zero 

6. 

Apply the minimum input signal and adjust the Zero 
screw for maximum output pressure.  Turn screw 
counterclockwise to increase pressure and clock­
wise to decrease pressure. 

•  

Reverse Acting Calibration-Span 

7. 

Apply the maximum input signal and adjust the Span 
screw on the potentiometer for minimum output pres­
sure.  Turn screw counterclockwise to increase pres­
sure and clockwise to decrease pressure. 

8. 

Repeat steps 6-7 until the desired output range is 
obtained.  For more information, see Figure 8. “T5200/ 
TXPD5200 Calibration Configuration.” 

Figure 7. 

T5220 / TXPD5220  Calibration Configuration. 

5

Содержание T5220

Страница 1: ...Mounting Kit 15268 Sold Separately INSTALLATION TheModelT5220canbemounteddirectlyontoaflatsurface The Model T5220 can be Panel Mounted using the usingthetwo10 32tappedmountingholesinthebaseofthe mount...

Страница 2: ...or use mount the T5220 in an upright Optional Mounting Kit 14596 For more information see position This will help prevent rain water from Figure 3 below entering into the unit For more information see...

Страница 3: ...ns below Mounting Kit surfaceusingthefour1 4 20x7 16 tappedmountingholes 14140 is available for Panel or 2 Pipe Mounting For inthebaseofthehousing Formoreinformation seeFigure more information see Fig...

Страница 4: ...nection FortheT5220Transducer makeconnectionstotheTermi nal Block through a 1 2 NPT Conduit Connector not supplied and a plastic sleeve as shown below in Figure 7 ElectricalConnections FortheTXPD5220T...

Страница 5: ...ApplythemaximuminputsignalandadjusttheSpan screw on the potentiometer for maximum output pressure Turn screw clockwise to increase pres sure and counterclockwise to decrease pressure 4 Repeat steps 2...

Страница 6: ...fore reas 4 Place Magnet 11 over Coil 10 and tighten with three Screws 12 sembling To clean the Inner Valve Assembly use the following 5 Using a non matalic rod Raise up on the arm to make procedure s...

Страница 7: ...PC Board 1 5 VDC PC Board 1 9 VDC PC Board 1 9 VDC PC Board 1 2 For T5220 TFI5220 TFN5220 TFNI5220 TXPD5220 TXPDI5220 Units Only For TCI5220 Only Table 4 Trouble Shooting Problem Solution check NoOut...

Страница 8: ...IS 500T5220 Litho in USA Rev M 06 07...

Отзывы: